![GORMAN-RUPP PUMPS Super T T4A60S-4LET2T FT4-ESP Series Installation, Operation, And Maintenance Manual With Parts List Download Page 16](http://html1.mh-extra.com/html/gorman-rupp-pumps/super-t-t4a60s-4let2t-ft4-esp-series/super-t-t4a60s-4let2t-ft4-esp-series_installation-operation-and-maintenance-manual-with-parts-list_2246932016.webp)
SUPER T SERIES
OM-07116
PAGE B - 9
INSTALLATION
Connect the valve outlet to a bleed line which
slopes back to the wet well or sump. The bleed line
must be the same size as the outlet opening or
larger, depending on which Air Release Valve is be
ing used. If
piping
is used for the bleed line, avoid
the use of elbows whenever possible.
NOTE
For multiple pump installations, it is recommended
that each Air Release Valve be fitted with an inde
pendent bleeder line directed back to the wet well.
If multiple Air Release Valves are installed in a sys
tem,
do not
direct bleeder lines to a common mani
fold pipe. Contact your Gorman‐Rupp distributor or
the Gorman‐Rupp Company for information about
installation of an Automatic Air Release Valve for
your specific application.
ALIGNMENT
The alignment of the pump and the engine is criti
cal for trouble‐free mechanical operation. See Sec
tion E,
Securing Pump End To Engine
for detailed
information.