Fig. 1: Connection and installation tank dimensions [mm]
OTHER HEATING SOURCES
-
SENSOR INSTALLATION
On the left side of the hot water storage tank are two openings (J1, J2), where the sensors for the control system of the connection of
the hot water tank to other heating sources. The maximum diameter of the probe is 8 mm. The length of the sensor tube is 180 mm.
Insert the sensor into the tube and attach it:
•
If the sensor is installed in the top (higher) position, then the thermostat will respond sooner, operating intervals of the circulation
pump will be sorter, difference between water temperature in the hot water storage tank and the heating medium after the
thermostat is switched off; as a result, the amount of hot water in the hot water storage tank will be lower.
•
If you install the sensor in the bottom (lower) position, the circulation pump operating intervals will be longer, the difference between
the temperature of the heating medium and the actual water temperature in the hot water storage tank will be lower, and as a result,
the amount of hot water in the hot water storage tank will be greater.
LEGEND
HV
Cold water inlet (H – blue rosette)
IM
Heat exchanger medium outlet (black rosette)
CV
Circulation pipeline (black rosette)
VM
Heat exchanger medium inlet (black rosette)
TV
Hot water outlet (T – red rosette)
J1
Sensor pipe
J2
Sensor pipe
VZ
Air inlet
IZ
Air outlet
TCM200ZG
TCM201ZG
TCM300ZG
TCM306ZG
A (mm)
25
25
25
25
B (mm)
130
130
140
140
C (mm)
/
218
/
245
D (mm)
/
490
/
490
E (mm)
880
880
880
880
F (mm)
1240
1240
1250
1250
G (mm)
1835
1835
1930
1930
H (mm)
570
570
670
670
I (mm)
585
585
685
685
J1 (mm)
/
765
/
805
J2 (mm)
/
1185
/
1185
HV
G3/4
G3/4
G1
G1
IM
/
G1
/
G1
CV
G3/4
G3/4
G3/4
G3/4
VM
/
G1
/
G1
TV
G3/4
G3/4
G1
G1