4
You can install a pellet burner on your boiler. Pellet burner should be purchased from the
boiler supplier. Before any purchase, first check if the pellet burner you find in the market fits
your boiler. Maximum burner tube diameter you can fit on this boiler is 170 mm. Burner must
be installed and operated in accordance with burner manufacturer’s regulations. Any misuse
will terminate all warranty terms given by boiler manufacturer.
3 BEFORE
INSTALLATION
3.1 PRODUCT
HANDLING
ECO HEAT is a heavy product and care should be taken at transport to the boiler room. The
weight of the boiler is listed in the technical data page. Additional equiptment used for
transport must be sufficient for its weight.
3.2 ROOM
SELECTION
ECO HEAT boiler must be installed in an individual boiler room particularly organized for
heating. The boiler room should be of enough volume for installation, firing, and maintenance
of the boiler. There should be enough fresh air circulation for combustion, the chimney
design must ensure an dequate draught for related boiler type, and must comply with
construction criteria given further in this manual and in mandatory regulations. Your boiler
must never be installed in open spaces or balconies, in spaces occupied by people like
kitchen, living room, bathroom, bedroom, in spaces where there are explosive and
combustible materials.
The boiler room should have air ventillation holes through outside to let fresh air in. One air
ventillation hole must be built maximum 40 cm below the level of room ceiling, the other must
be built maximum 50 cm above the floor level. These ventillation holes should always be kept
open. The upper hole should be at least 40x40 cm in size, the lower hole at least 30x30 cm.
All hydraulic and electrical circuits must be arranged by authorized staff in accordance with
mandatory regulations specified by legal organizations.
Solid fuels should be stored by keeping minimum 800 mm distance from the boiler. We
recommend you to keep the solid fuel in another room.