10 Technical Parameters
41
User Manual V1.0-2022-12-15
Nominal Output Apparent Power (VA)
*4
5000
6000
Max. AC Active Power (W)
5000
6000
Max. AC Apparent Power (VA)
5000
6000
Nominal Power at 40℃ (W)(For Brazil only)
5000
6000
Max Power at 40℃ (including AC overload)(W)(For
Brazil only)
5000
6000
Nominal Output Voltage (V)
220
220
Nominal AC Grid Frequency (Hz)
60
60
Max. Output Current (A)
22.8
27.3
Max. Output Fault Current (Peak and Duration) (A)
35
35
Inrush Current (Peak and Duration) (A)
60
80
Nominal Output Current (A)
22.7
27.3
Power Factor
~1 (Adjustable from 0.8 leading to 0.8 lagging)
Max. Total Harmonic Distortion
<3%
<3%
Maximum Output Overcurrent Protection (A)
42
50
Efficiency
Max. Efficiency
97.8%
97.8%
European Efficiency
97.5%
97.5%
Protection
PV String Current Monitoring
Integrated
PV Insulation Resistance Detection
Integrated
Residual Current Monitoring
Integrated
PV Reverse Polarity Protection
Integrated
Anti-islanding Protection
Integrated
AC Overcurrent Protection
Integrated
AC Short Circuit Protection
Integrated
AC Overvoltage Protection
Integrated
DC Switch
Optional
DC Surge Protection
Type III
AC Surge Protection
Type III
AFCI
Optional
Remote Shutdown
Optional
General Data
Operating Temperature Range (℃)
-25 - +60
Relative Humidity
0 - 100%
Max. Operating Altitude (m)
*5
4000