10 Technical Parameters
39
User Manual V1.0-2022-12-15
Max Power at 40℃ (including AC
overload)(W)(For Brazil only)
3000
3680
4200
5000
6000
Nominal Output Voltage (V)
220/230
220/230
220/230
220/230
220/230
Nominal AC Grid Frequency (Hz)
50/60
50/60
50/60
50/60
50/60
Max. Output Current (A)
13.6
16.0
19.0
22.8
27.3
Max. Output Fault Current (Peak
and Duration) (A)
35
35
35
35
35
Inrush Current (Peak and
Duration) (A)
60
60
60
60
80
Nominal Output Current (A)
13.6/13.0
16.0/15.6
19.0/18.2
22.8/21.7
27.3/26.1
Power Factor
~1 (Adjustable from 0.8 leading to 0.8 lagging)
Max. Total Harmonic Distortion
<3%
<3%
<3%
<3%
<3%
Maximum Output Overcurrent
Protection (A)
42
42
42
42
50
Efficiency
Max. Efficiency
97.8%
97.8%
97.8%
97.8%
97.8%
European Efficiency
97.5%
97.5%
97.5%
97.5%
97.5%
Protection
PV String Current Monitoring
Integrated
PV Insulation Resistance
Detection
Integrated
Residual Current Monitoring
Integrated
PV Reverse Polarity Protection
Integrated
Anti-islanding Protection
Integrated
AC Overcurrent Protection
Integrated
AC Short Circuit Protection
Integrated
AC Overvoltage Protection
Integrated
DC Switch
Optional
DC Surge Protection
Type III(Type II Optional)
AC Surge Protection
Type III
AFCI
Optional
Emergency Power Off
Optional
Remote Shutdown
Optional
General Data
Operating Temperature Range
(℃)
-25 - +60
Relative Humidity
0 - 100%
Max. Operating Altitude (m)
*5
4000
Cooling Method
Natural Convection