SS-SSZ14
www.goodmanmfg.com
3
P
roduct
S
PecificationS
S
peCifiCationS
SSZ14
0181A
SSZ14
0241A
SSZ14
0301A
SSZ14
0361B
SSZ14
0381A
SSZ14
0421A
SSZ14
0481A
SSZ14
0601A
Nominal Capacities
Cooling (BTU/h)
18,000
24,000
30,000
36,000
36,000
42,000
48,000
60,000
Heating (BTU/h)
18,000
24,000
30,000
36,000
36,000
42,000
48,000
60,000
Decibels
70
72
72
74
74
73
74
75
Compressor
RLA
9.0
12.8
14.1
14.1
14.1
17.9
19.9
26.4
LRA
48.0
58.3
73.0
77.0
77
112.0
109.0
134.0
Condenser Fan Motor
Horsepower
1/12
1/6
1/6
¼
1/6
¼
¼
¼
FLA
0.6
1.1
1.0
1.5
1
1.5
1.5
1.5
Refrigeration System
Refrigerant Line Size¹
Liquid Line Size (“O.D.)
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
Suction Line Size (“O.D.)
¾"
¾"
¾"
⅞"
⅞"
1⅛"
1⅛"
1⅛"
Refrigerant Connection Size
Liquid Valve Size (“O.D.)
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
Suction Valve Size (“O.D.)
¾"
¾"
¾"
¾"
⅞"
⅞"
⅞"
⅞"
Valve Connection Type
Sweat
Sweat
Sweat
Sweat
Sweat
Sweat
Sweat
Sweat
Refrigerant Charge
140
160
185
186
211
210
270
275
Electrical Data
Volts-Phase (60 Hz)
208/230-1 208/230-1 208/230-1 208/230-1 208/230-1 208/230-1 208/230-1 208/230-1
Minimum Circuit Ampacity ²
11.9
17.1
18.6
19.1
19.0
23.9
26.4
34.5
Max. Overcurrent Protection ³
20
25
30
30
30
40
45
60
Min / Max Volts
197 / 253
197 / 253
197 / 253
197 / 253
197/253
197 / 253
197 / 253
197 / 253
Electrical Conduit Size
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
Equipment Weight (lbs)
173
183
185
192
253
246
278
292
Ship Weight (lbs)
191
201
203
210
275
268
300
314
¹ Tested and rated in accordance with AHRI Standard 210/240
² Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes
³ Must use time-delay fuses or HACR-type circuit breakers of the same size as noted.
Notes
• Always check the rating plate for electrical data on the unit being installed.
• Installer will need to supply ⅞” to 1⅛” adapters for suction line connections.
• Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.
• Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE OUTDOOR UNIT
NOT THE INDOOR COIL.