SS-SSZ14
www.goodmanmfg.com
21
E
xpandEd
d
ata
h
eating
D
ata
(
Cont
.)
SSZ140381A* / ASPT42C14A*
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
42.7
40.5
38.1
35.6
34.0
32.9
30.6
28.2
25.7
23.7
21.8
20.6
19.8
17.8
15.8
13.8
11.7
9.6
T/R
33.7
31.9
30.0
28.1
26.8
26.0
24.1
22.2
20.2
18.7
17.2
16.2
15.6
14.0
12.4
10.8
9.3
7.6
KW
2.46
2.40
2.35
2.29
2.25
2.23
2.17
2.11
2.10
2.04
1.98
1.94
1.92
1.86
1.80
1.74
1.68
1.62
AMPS
13.4
12.3
11.5
10.7
10.3
10.1
9.5
8.9
8.5
8.1
7.7
7.4
7.3
6.9
6.4
5.9
5.4
4.8
COP
4.57
4.42
4.26
4.07
3.94
3.86
3.66
3.46
3.17
3.00
2.84
2.72
2.65
2.44
2.23
2.00
1.76
1.48
HI PR
400
383
368
352
344
337
324
311
298
285
273
267
262
252
243
233
224
216
LO PR
149
138
129
119
112
108
99
88
80
71
63
58
56
47
41
35
30
24
SSZ140421A* / CA*F4860*6A*+TXV / MBR2000**-1
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
51.5
48.8
45.9
42.9
40.0
39.7
36.9
34.0
34.3
31.6
29.1
27.5
26.5
23.8
21.1
18.4
15.7
12.8
∆T
34.1
32.3
30.4
28.4
27.1
26.3
24.4
22.5
22.7
20.9
19.3
18.2
17.5
15.7
13.9
12.1
10.4
8.5
kW
3.40
3.33
3.27
3.21
3.17
3.14
3.08
3.02
3.07
3.00
2.94
2.90
2.87
2.81
2.74
2.68
2.61
2.54
Amps
15.2
14.1
13.2
12.4
12.0
11.8
11.1
10.6
10.1
9.7
9.2
9.0
8.9
8.5
7.9
7.5
6.9
6.3
COP
4.44
4.28
4.11
3.92
3.79
3.70
3.50
3.30
3.26
3.08
2.90
2.78
2.70
2.48
2.25
2.01
1.76
1.48
EER
15.2
14.6
14.0
13.4
12.9
12.6
12.0
11.3
11.2
10.5
9.9
9.5
9.2
8.5
7.7
6.9
6.0
5.1
Hi PR
370
354
341
326
318
312
300
288
276
263
253
247
242
233
224
215
207
200
Lo PR
142
132
123
113
107
103
95
84
76
68
60
56
53
45
39
33
29
23
SSZ140481A* / CA*F4860*6A*+TXV / MBR2000**-1
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
57.8
54.7
51.5
48.2
47.0
44.6
41.4
38.2
36.6
33.8
31.1
29.4
28.3
25.4
22.5
19.6
16.8
13.7
∆T
34.5
32.7
30.8
28.8
27.5
26.6
24.7
22.8
21.9
20.2
18.6
17.6
16.9
15.2
13.4
11.7
10.0
8.2
kW
3.98
3.90
3.83
3.75
3.71
3.68
3.60
3.53
3.65
3.57
3.49
3.44
3.41
3.32
3.24
3.16
3.08
3.00
Amps
19.4
17.6
16.1
14.8
14.1
13.7
12.7
11.7
11.0
10.3
9.5
9.2
9.0
8.3
7.4
6.6
5.7
4.6
COP
4.25
4.10
3.94
3.76
3.63
3.55
3.36
3.17
2.94
2.77
2.61
2.50
2.43
2.24
2.03
1.82
1.59
1.34
EER
14.5
14.0
13.5
12.8
12.4
12.1
11.5
10.8
10.0
9.5
8.9
8.5
8.3
7.6
6.9
6.2
5.4
4.6
Hi PR
408
391
376
359
351
344
331
318
304
291
279
272
267
257
247
237
229
221
Lo PR
136
126
118
109
103
99
91
81
73
65
57
53
51
43
37
32
28
22
SSZ140601A* / CA*F4860*6A*+TXV / MBE2000**-1
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
57.8
57.8
57.8
57.8
57.0
55.2
51.3
47.3
47.9
44.2
40.7
38.4
37.0
33.2
29.4
25.7
21.9
17.9
∆T
35.9
33.9
32.0
29.9
28.5
27.6
25.7
23.7
24.0
22.1
20.4
19.2
18.5
16.6
14.7
12.8
11.0
9.0
kW
4.83
4.74
4.64
4.54
4.48
4.44
4.35
4.25
4.42
4.32
4.21
4.15
4.11
4.00
3.90
3.80
3.69
3.59
Amps
24.7
22.3
20.4
18.8
17.9
17.4
16.0
14.8
13.9
12.9
12.0
11.5
11.3
10.4
9.2
8.2
7.1
5.7
COP
4.34
4.19
4.03
3.85
3.72
3.64
3.45
3.26
3.17
2.99
2.83
2.71
2.63
2.43
2.21
1.98
1.74
1.46
EER
14.8
14.3
13.8
13.1
12.7
12.4
11.8
11.1
10.8
10.2
9.7
9.3
9.0
8.3
7.5
6.8
5.9
5.0
Hi PR
404
387
372
356
347
341
327
314
301
288
276
269
265
255
245
235
226
218
Lo PR
136
126
119
109
103
99
91
81
73
65
57
53
51
43
37
32
28
22
Calculations are based on nominal CFM and 70°F indoor dry bulb.
Amps = Outdoor unit amps (comp.+fan)
High pressure is measured at the suction service valve ( the larger valve).
kW = Total system power
Low pressure is measured at the gauge port connection.