SS-PCB50 

7

P

RODUCT

 S

PECIFICATIONS

Motor Sheave - Adjustable          Factory Setting

       Fan Sheave - Fixed                     2 Turns Opens

Motor Sheave Turns Open

0

1

2

3

4

5

Fan RPM

5.0 HP Motor

1400

1446

1273

1209

1146

1082

Note:

 Allow ±5% variation in blower RPM due to pulley manufacturing tolerances.

Conversion Factor:

1 CFM = 0.472 L/S
1” W.C. = 2.5 M Bar
1 HP = 0.747 kW

F

AN

 P

ERFORMANCE

 D

ATA

 (

CONT

.)

S

UPPLY

 F

AN

 P

ERFORMANCE

 - PCB180

CFM

External Static Pressure (Inches W.C.) See Last Note

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

4000

784

1.14

876

1.44

959

1.76

1036

2.10

1108

2.47

1176

2.86

1239

3.26

1300

3.67

4200

814

1.29

903

1.60

983

1.93

1058

2.28

1129

2.66

1195

3.05

1258

3.46

1318

3.89

4400

844

1.45

930

1.78

1008

2.12

1081

2.48

1150

2.86

1215

3.26

1277

3.68

1337

4.12

4600

874

1.63

957

1.97

1034

2.32

1105

2.69

1172

3.08

1236

3.49

1297

3.92

1356

4.37

4800

904

1.82

986

2.17

1060

2.54

1129

2.92

1195

3.32

1258

3.74

1318

4.17

1375

4.63

5000

932

2.02

1014

2.39

1086

2.77

1159

3.16

1218

3.57

1280

4.00

1338

4.44

1395

4.91

5200

966

2.24

1043

2.62

1113

3.01

1179

3.42

1242

3.84

1302

4.27

1360

4.73

1416

5.20

5400

997

2.48

1071

2.87

1141

3.28

1205

3.70

1267

4.12

1326

4.57

1382

5.03

1437

5.51

5600

1029

2.74

1101

3.14

1168

3.56

1231

3.99

1291

4.43

1394

4.88

1405

5.36

1458

5.85

Notes:

Selections in

 ITALICS 

require a 

fi

 eld drive change. See following table below for drive ranges.

Table includes all internal pressure drops including cabinet losses. See Pressure Drops table that must be considered as part of 
external static pressure drop.
DO NOT SELECT IN SHADED AREAS (FOR INTERPOLATION ONLY).


F

IGURE

 6. F

AN

 

CURVE

 - PCB180

S

UPPLY

 F

AN

 D

RIVE

 D

ATA

 - PCB180

Summary of Contents for PCB090-5

Page 1: ...nized steel powder coated drain pan with 3 4 19mm NPT condensate connection Belt driven variable pitch sheave permits multi speed adjustment Centrifugal fan for quiet and efficient operation Filters 2...

Page 2: ...24 610 24 610 22 559 Motor Horsepower kW 1 2 0 37 1 2 0 37 1 2 0 37 Outdoor CFM Nominal L S 4300 2030 6100 2880 7000 3300 Condenser Coil Qty 1 1 1 Face Area Total Ft m 15 6 1 45 23 8 2 21 23 8 2 21 R...

Page 3: ...dimensions in inches and millimeters Drawings are not to scale Note The Horizontal Conversion Kit is required to convert a factory duct configuration downflow to a horizontal duct configuration as sho...

Page 4: ...265 13 1 7 3 19 6 10 9 26 2 14 6 5000 2360 12 6 7 0 18 8 10 4 25 2 14 0 5200 2454 12 1 6 7 18 1 10 1 24 2 13 4 5400 2548 11 6 6 4 17 4 9 7 23 3 12 9 5600 2643 11 2 6 2 16 8 9 3 22 5 12 5 5800 2737 10...

Page 5: ...1159 1 65 1259 1 87 1324 2 09 1384 2 31 Notes Selections in ITALICS require a field drive change See following table below for drive ranges Table includes all internal pressure drops including cabinet...

Page 6: ...8 1034 1 91 1105 2 26 1171 2 26 1233 2 99 3600 706 0 83 805 1 10 894 1 39 975 1 71 1051 2 05 1121 2 41 1188 2 78 1249 3 17 3800 733 0 95 829 1 23 916 1 53 995 1 85 1069 2 20 1139 2 57 1204 2 95 1266 3...

Page 7: ...08 2 12 1081 2 48 1150 2 86 1215 3 26 1277 3 68 1337 4 12 4600 874 1 63 957 1 97 1034 2 32 1105 2 69 1172 3 08 1236 3 49 1297 3 92 1356 4 37 4800 904 1 82 986 2 17 1060 2 54 1129 2 92 1195 3 32 1258 3...

Page 8: ...4 C 35 0 C 40 6 C 46 1 C L S WB Total Cap Sens Cap Kw Total Cap Sens Cap Kw Total Cap Sens Cap Kw Total Cap Sens Cap Kw Total Cap Sens Cap Kw 1203 22 2 32 77 15 48 8 36 30 67 14 52 9 29 28 56 13 56 1...

Page 9: ...22 2 46 65 25 03 10 50 43 81 23 49 11 85 40 96 21 94 13 20 38 11 20 39 14 55 35 26 18 84 15 90 19 4 42 90 33 53 9 86 40 28 31 41 11 17 37 66 29 29 12 48 35 04 27 18 13 78 32 41 25 06 15 09 16 7 40 29...

Page 10: ...2 191 1 174 8 14 77 180 5 164 7 17 00 169 8 154 6 19 23 159 1 144 5 21 46 148 4 134 4 23 68 57 191 1 174 8 14 77 180 5 164 7 17 00 169 8 154 6 19 23 159 1 144 5 21 46 148 4 134 4 23 68 6440 72 233 9 1...

Page 11: ...b for equipment in the down discharge application Curb includes provisions for duct attachment prior to setting unit Curb is shipped knocked down with all necessary hardware and gasket material MANUAL...

Page 12: ...every unit is run tested before it leaves the factory That s why we know there s no better quality Visit our website at www goodmanmfg com for information on Goodman Products Customer Services Parts...

Reviews: