background image

11

Safe Refrigerant Handling

While these items will not cover every conceivable situation,
they should serve as a useful guide.

Refrigerants are heavier than air. They can "push out"
the oxygen in your lungs or in any enclosed space.To
avoid possible difficulty in breathing or death:

•  

Never purge refrigerant into an enclosed room or

   space. By law, all refrigerants must be reclaimed.

•  

If an indoor leak is suspected, throughly ventilate the

   area before beginning work.
•  Liquid refrigerant can be very cold. To avoid possible
   frostbite or blindness, avoid contact and wear gloves
   and goggles.  If liquid refrigerant does contact your
   skin or eyes, seek medical help immediately.
•  Always follow EPA regulations. Never burn refrig-
   erant, as poisonous gas will be produced.

WARNING

To avoid possible explosion:
 

•  

Never apply flame or steam to a refrigerant cylinder.

    If you must heat a cylinder for faster charging,
    partially immerse it in warm water.

•   

Never fill a cylinder more than 80% full of liquid re-

    frigerant.
•   Never add anything other than R-22 to an R-22 cy-
    linder or R-410A to an R-410A cylinder. The service
    equipment used must be listed or certified for the
    type of refrigerant used.
•   Store cylinders in a cool, dry place. Never use a cy-
    linder as a platform or a roller.

WARNING

To avoid possible explosion, use only returnable (not
disposable) service cylinders when removing refrig-
erant from a system.
 •  Ensure the cylinder is free of damage which could
    lead to a leak or explosion.
•   Ensure the hydrostatic test date does not exceed
    5 years.
•   Ensure the pressure rating meets or exceeds 400
    lbs.

When in doubt, do not use cylinder.

WARNING

Use caution when handling the packed valve:

Open the valve stem unit it comes in contact against the
stopper.   Do not attempt to open further.

C

D

B

Figure 24

Securely tighten the valve stem cap with a spanner or
similar tool.

See tightening torque table in Tightening Connection
section.

Safety Check

After completing  the electrical installation:

1. Grounding: After grounding the unit, measure the ground-

ing resistance by visually inspecting the unit and by us-
ing a grounding resistance tester, making sure the ground-
ing resistance is less than 4.0 ohms.

2. Electrical leakage check (to be performed during opera-

tion): During the test operation after complete installation
of the unit, the qualified installer may use the electroprobe
and multimeter to perform the electrical leakage check.
Turn off the unit immediately if leakage occurs.

Test Running

After completing the gas leak check at the flare nut connec-
tions and electrical safety check, perform the test operation.

Ensure all tubing and wiring have been properly con-
nected.

Make sure both the gas and liquid side service valves
are fully open.

1. Connect the power; press the ON/OFF button on the re-

mote control to turn the unit on.

2. Using the MODE button, select COOL, HEAT, AUTO and

FAN to ensure all the functions are operating.

Summary of Contents for MSC 15 Series

Page 1: ...P 5151 San Felipe Suite 500 Houston TX 77056 www goodmanmfg com or www amana hac com IO 412A April 2013 To prevent the risk of property damage personal injury or death do not store combustible materia...

Page 2: ...steps in the orderpresentedshouldensureproperinstallation 2 4m 8 ft MOUNT WITH THE LOWEST MOVING PARTS AT LEAST ABOVE FLOOR OR GRADE LEVEL INDOORUNIT To avoid property damage personal injury or death...

Page 3: ...crew A ST3 9x25 5 8 depending on model 4 Seal for cooling heating models only 1 5 Drain joint 1 Connection Pipe Assembly Liquid Side 1 4 6 35 3 8 9 52 Gas Side 3 8 9 52 1 2 12 7 5 8 16 0 7 Remote Cont...

Page 4: ...lways use wall hole conduit when drilling metal grid metal plate etc 15 SEER MODELS A C D Indoor unit outline Figure 5A 12 000 Btu h A C D Figure 5B 18 000 Btu h 19 SEER MODELS Model B 18 000 A 31 790...

Page 5: ...iping and wrapping Evenly bundle the tubing connecting cable and drain hose securely with tape as shown in Figure 12 Because the condensed water from the rear of the indoor unit gathers in the drain p...

Page 6: ...x 250 21 5 549 11 276 MS 18 E15 30 x 23 x 11 760 x 590 x 285 21 530 11 5 290 MS 12 E19 30 x 23 x 11 760 x 590 x 285 21 530 11 5 290 MS 18 E19 33 x 27 5 x 12 5 840 x 700 x 320 22 560 13 335 Mounting Di...

Page 7: ...ength Max Elevation Max Length Additional Refrigerant Gas Liquid ft m B ft m A ft m oz ft g m 1 2 1 4 12 7 6 35 3 8 1 4 9 52 6 35 3 8 1 4 9 52 6 35 1 2 1 4 12 7 6 35 26 25 8 0 3 20 26 25 8 66 20 0 3 2...

Page 8: ...ring must comply with local and national electrical codes Installation should be done by qualified electri cians To avoid the risk of personal injury wiring to the unit must be properly polarized and...

Page 9: ...ect proper cord diameter to fill the holes on the cord clamp Figure 23B 2 Remove caps on the conduit panel 3 Temporarily mount the conduit tubes not included on the conduit panel 4 Connect the power s...

Page 10: ...test If no leaks exist proceed to System Evacuation System Evacuation Condensing unit liquid and suction valves are closed to contain the charge within the unit The unit is shipped with the valve ste...

Page 11: ...removing refrig erant from a system Ensure the cylinder is free of damage which could lead to a leak or explosion Ensure the hydrostatic test date does not exceed 5 years Ensure the pressure rating me...

Page 12: ...e operation can be done manually Manually controlling the unit is to be done only when the remote control is disabled or maintenance is required Grasp the panel sides and lift up the panel to an angle...

Page 13: ...etension D connectez TOUTES les alimentions lectriques avant d effectuer un entretien Il peut y avoir de multiples sources d alimentation Ne pas le faire peut entra ner des dommages mat riels des domm...

Page 14: ...us les codes et ordonnances locaux ou en leur absence selon la version la plus r cente du Code lectrique national L installation correcte de cette unit est d crite dans lessectionssuivantes Sivoussuiv...

Page 15: ...de 1 Les pi ces doivent tre achet es s par ment Consultez le fournisseur pour con na tre les tailles de tuyaux Une paisseur de paroi du tuyau minimum de 1 32 po 0 7 mm est recommand e Remarque Les pi...

Page 16: ...r frig rant et du condensat INSTALLATION 5 Le tuyau d vacuation doit tre install avec une l g re inclinai son vers le bas Voir Figure 6 Mur Int rieur Ext rieur 3 16 po 1 4 po 5 7 mm Figure 6 Le tuyau...

Page 17: ...ation soit positionn sur le c t inf rieur du tubage empaquet Le positionner sur le c t sup rieur peut entra ner le d bordement du bac de purge l int rieur de l unit Le tuyau d vacuation doit tre incli...

Page 18: ...longe de tuyau d vacuation fournie par l installateur Figure 16A Figure 16B Figure 16C Connexion des conduites de r frig rant Remarque La cause principale des fuites de r frig rant se situe au niveau...

Page 19: ...arquesimportantes Si des probl mes de s curit li s l alimentation se produisent l unit ne doit pas tre connect e avant la r solution de ces probl mes Veillez ce que l alimentation lectrique suffise al...

Page 20: ...rieure en d vissant la vis comme illustr sur la Figure 23A Figure 23A Figure 23B Remarque Le serre c ble doit tre d une taille ad quate pour pr venir le rel chement ou le glissement des c bles du ser...

Page 21: ...e et maintenez le vide pendant 10 minutes Normalement lapressionmonteradurantcettep riode Remarques Si la pression augmente 1 000 microns ou moins et reste stable le circuit est consid r sans fuite vo...

Page 22: ...t s du panneau et soulevez celui ci selon un angle qui le maintienne fixe et jusqu ce que vous entendiez un clic Appuyez sur le bouton de contr le manuel pour s lectionner AUTO ou COOL L unit fonction...

Page 23: ...IO 412A www goodmanmfg com 11 Remarques...

Page 24: ...12 www goodmanmfg com IO 412A Remarques...

Page 25: ...zar el servicio t cnico Podr a haber m ltiples fuentes de alimentaci n Si no se cumple esta medida se podr an ocasionar da os mate riales lesiones personales o la muerte I Advertencia S LO pueden usar...

Page 26: ...do con estas instrucciones de instalaci n y funcionamiento y seg n los c digos y reglamentos locales o en su defecto seg n la ltima edici n del C digo El ctrico Nacional La instalaci n adecuada de est...

Page 27: ...orte de control remoto 1 Las piezas deben comprarse por separado Consulte a su proveedor sobre los tama os de las tuber as Se recomienda un m nimo de espesor de pared de tuber a de 1 32 pulgadas 0 7 m...

Page 28: ...R 19 Figura 5C Instalaci n de tuber as de refrigerante y condensaci n Instalaci n 5 La manguera de drenaje deber a instalarse con una ligera pendiente hacia abajo vea la figura 6 Figura 6 No deber a i...

Page 29: ...m s bajo del manojo de tuber as Colocarla en el lado superior puede hacer que la bandeja de drenaje se desborde dentro de la unidad La manguera de drenaje deber a inclinarse hacia abajo para asegurar...

Page 30: ...necte la junta de drenaje con una manguera de drenaje de extensi n proporcionada por el instalador Figura 16A Figura 16B Figura 16C Conexiones del conducto de refrigerante Nota lacausaprincipaldep rdi...

Page 31: ...enores que lo indicado podr an provocar un mal desempe o del equipo da os o incendios NotasImportantes Si tiene problemas de seguridad con el suministro el ctrico no deber a conectar la unidad hasta r...

Page 32: ...ando el tornillo como se ve en la figura 23A Figura 23A Figura 23B Nota la abrazadera debe ser del tama o correcto para impedir que los cables se suelten o se deslicen de ella Elija el di metro apropi...

Page 33: ...o durante 10 minutos Por lo general la presi n subir durante ese tiempo Notas Si la presi n se eleva a 1000 micrones o menos y permanece estable se considera que el sistema est libre de fugas proceda...

Page 34: ...panel y lev ntelo hasta un ngulo en el que permanezca fijo y se oiga un clic Presione el bot n de control manual para seleccionar AUTOM TICO o FR O La unidad funcionar en modo forzado AUTOM TICO o FR...

Page 35: ...IO 412A www goodmanmfg com 11 Notas...

Page 36: ...12 www goodmanmfg com IO 412A Notas...

Reviews: