P
rodUct
s
Pecifications
P
rodUct
s
Pecifications
SS-GPG13M
www.goodmanmfg.com
5
s
Pecifications
(
cont
.)
GPG1348
070M41A*
GPG1348
090M41A
GPG1348
115M41A
GPG1360
090M41A
GPG1360
115M41A
GPG1360
140M41A
Cooling Capacity
Total BTU/h
46,000
46,000
46,000
57,000
57,000
57,000
Sensible BTU/h
36,700
36,700
36,700
43,800
43,800
43,800
SEER / EER
13.0 / 11.0
13.0 / 11.0
13.0 / 11.0
13.0 / 10.75
13.0 / 10.75
13.0 / 10.75
Decibels
80
80
80
80
80
80
AHRI Reference #s
4385097
4385097
4385097
4385099
4385099
4385099
Heating Capacity
Input BTU/h
69,000
92,000
115,000
92,000
115,000
138,000
Output BTU/h
55,000
73,600
92,000
73,600
92,000
110,400
AFUE
80
80
80
80
80
80
Temperature Rise Range
35 - 65
45 - 75
45 - 75
45 - 75
45 - 75
45 - 75
No. of Burners
3
4
5
4
5
6
Orifice Size (Natural/Propane)
43 / 55
43 / 55
43 / 55
43 / 55
43 / 55
43 / 55
Evaporator Motor
Type
EEM
EEM
EEM
EEM
EEM
EEM
Wheel (D x W)
11” x 10”
11” x 10”
11” x 10”
11” x 10”
11” x 10”
11” x 10”
Indoor Nominal CFM
1,550
1,550
1,550
1,750
1,750
1,750
Motor Speed Tap (Cooling)
T4
T4
T4
T4
T4
T4
RPM/Amps (Cooling)
1,050/5.8
1,050/5.8
1,050/5.8
1,050/7.6
1,050/7.6
1,050/7.6
Horsepower
3/4
3/4
3/4
1.0
1.0
1.0
Evaporator Coil
Face Area (ft²)
5.67
5.67
5.67
5.67
5.67
5.67
Rows Deep/Fins per Inch
4/14
4/14
4/14
4/14
4/14
4/14
Piston Size (Cooling)
0.076
0.076
0.076
0.087
0.087
0.087
Filter Size (ft²)
5.1
5.1
5.1
6.3
6.3
6.3
Drain Size (NPT)
¾”
¾”
¾”
¾”
¾”
¾”
Refrigerant Charge (oz.)
125
125
125
185
185
185
Condenser Fan / Coil
Horsepower - RPM
1/4 - 1100
1/4 - 1100
1/4 - 1100
1/4 - 1100
1/4 - 1100
1/4 - 1100
Diameter / # of Blades
22” / 3
22” / 3
22” / 3
22” / 3
22” / 3
22” / 3
Outdoor Nominal CFM
3,500
3,500
3,500
3,500
3,500
3,500
Face Area (ft²)
15.4
15.4
15.4
15.2
15.2
15.2
Rows Deep/Fins per Inch
1/24
1/24
1/24
2/16
2/16
2/16
Compressor
Quantity / Type
1 / Scroll
1 / Scroll
1 / Scroll
1 / Scroll
1 / Scroll
1 / Scroll
Stage
Single
Single
Single
Single
Single
Single
Compressor RLA/LRA
19.9/109
19.9/109
19.9/109
26.4 / 134
26.4 / 134
26.4 / 134
Electrical Data
Voltage/Phase/Frequency
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
Indoor Blower FLA/LRA
5.8
5.8
5.8
7.6
7.6
7.6
Outdoor Fan RLA/LRA
1.4/ 2.9
1.4/ 2.9
1.4/ 2.9
1.4/ 2.9
1.4/ 2.9
1.4/ 2.9
Total Unit Amps
27.1
27.1
27.1
35.4
35.4
35.4
Min. Circuit Ampacity
32.1
32.1
32.1
42
42
42
Max. Overcurrent Protection
50 amps
50 amps
50 amps
60 amps
60 amps
60 amps
Entrance Size Power Supply
1⅛”
1⅛”
1⅛”
1⅛”
1⅛”
1⅛”
Entrance Size Control Voltage
⅞”
⅞”
⅞”
⅞”
⅞”
⅞”
Operating Weight (lbs)
518
523
528
533
538
543
Ship Weight (lbs)
540
545
550
555
560
565
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² Must use time-delay fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.