P
RoDUcT
S
PeciFicATionS
P
RoDUcT
S
PeciFicATionS
SS-GPC13H
www.goodmanmfg.com
3
S
PeciFicATionS
GPC13
24H41AC
GPC13
30H41AA
GPC13
30H41AC
GPC13
36H41AA
GPC13
36H41AC
Cooling Capacity
Total BTU/h
24,000
28,600
28,600
36,000
36,000
Sensible BTU/h
18,600
22,700
22,700
26,000
26,000
SEER / EER
13.0 / 11.0
13.0 / 11.0
13.0 / 11.0
13.0 / 11.0
13.0 / 11.0
Decibels
76
76
76
78
78
AHRI #
4635457
4635469
4635458
4635470
4635459
Evaporator Motor
Type
PSC
PSC
PSC
PSC
PSC
Wheel (D x W)
9 x 6
9 x 6
9 x 6
9 x 8
9 x 8
Nominal Cooling CFM
815
1,080
1,080
1,205
1,205
RLA / LRA
1.5 / 2.2
1.86 / 3.2
1.86 / 3.2
1.86 / 3.2
1.86 / 3.2
No. of Speeds
3
3
3
3
3
Horsepower - RPM
¼ - 952
⅓ - 1,020
⅓ - 1,020
⅓ - 1,020
⅓ - 1,020
Evaporator Coil
Face Area (ft²)
4.6
4.6
4.6
5.2
5.2
Rows Deep / Fins per Inch
3 / 14
3 / 14
3 / 14
3 / 14
3 / 14
Filter Size (“)
20 x 20 x 1
20 x 25 x 1
20 x 25 x 1
25 x 25 x 1
25 x 25 x 1
Drain Size (NPT)
¾"
¾"
¾"
¾"
¾"
Refrigerant Charge (oz.)
63
80
62
85
61
Condenser Fan / Coil
Horsepower - RPM
¹/6 - 815
¼ - 830
¹/6 - 815
¼ - 830
¼ - 830
RLA / LRA
1.1 / 1.7
1.5 / 3.0
1.1 / 1.7
1.5 / 3.0
1.5 / 3.0
Fan Diameter/ # Fan Blades
22 / 2
22 / 3
22 /2
22 /4
22 / 4
Face Area (ft²)
12.3
13.4
12.3
13.4
12.3
Rows Deep / Fins per Inch
1 / 26
1 / 24
1 / 26
1 / 24
1 / 26
Compressor
Quantity
1
1
1
1
1
Type
Scroll
Recip
Scroll
Scroll
Scroll
Stage
Single
Single
Single
Single
Single
Compressor RLA / LRA
13.5 / 58.3
9.8 / 55
12.8 / 64
16.7 / 79
16.7 / 79
Electrical Data
Voltage-Phase
208/230-1
208/230-1
208/230-1
208/230-1
208/230-1
Indoor Blower FLA
1.5
1.86
1.86
1.86
1.86
Outdoor Fan RLA
1.7
1.5
1.7
1.5
1.5
Total Unit Amps
16.1
13.16
15.76
20.06
20.06
Min. Circuit Ampacity¹
19.5
15.6
19
24.2
24.2
Max. Overcurrent Protection (amps)²
30
25
30
40
40
Ship Weight (lbs)
290
310
290
370
370
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.