background image

 

 

17

 

 
VENT PRESSURE SWITCH 

This heater uses a vent pressure switch that prevents the heater from operating should any 
portion of the vent system become restricted or a venter failure occur. To check this switch, 
place the heater in operation and remove the hose from the switch. The gas burners will extin-
guish. Replacing the hose will allow the heater to operate normally. 
 
 

 
FLAME ROLL-OUT SWITCH 

This heater is equipped with a flame roll-out switch(s). This manually resetable switch is a disc 
type and is non-adjustable. This switch is designed to shut down the burner gas if there are 
flames outside the heat exchanger. Should this switch function, contact a qualified service per-
son to determine the cause of function before resetting. To reset this switch press the button 
on top of the switch after the heater has cooled. To test the operation, place the heater in op-
eration and place an open flame on the flat surface of the switch. The switch should function to 
shut down the

 

burner gas

. Wait until the heater has cooled sufficiently before resetting 

the switch. 
 
FLAME SENSOR 

The ignition is provided by an electronic ignition system. The burner flames will become extin-
guished if the flame sensor fails to detect the presence of flame. To test, disconnect the flame 
sensor wire before placing the heater in operation. The electronic ignition device should at-
tempt the burners. However, the burners should shut off after a few seconds of operation. Dis-
connect the electrical supply to the heater, reinstall the disconnected sensor wire and reset the 
power supply to restore the heater to its normal operation. 

 
BLOWER DOOR INTERLOCK SWITCH 

The purpose of the switch is to disconnect electrical power to the heater should the blower 
door become dislodged, removed, or not properly reinstalled. ALLOWING THE HEATER TO 
OPERATE WITHOUT THE BLOWER DOOR BEING SECURELY IN PLACE CAN CAUSE 
COMBUSTION PRODUCTS TO BECOME CIRCULATED THROUGHOUT THE LIVING AREA 
WHICH CAN CAUSE SERIOUS ILLNESS OR 

CARBON MONOXIDE

 POISONING. To test 

the operation of this switch, place the heater in operation and remove the blower access door. 
The burner flames should become extinguished and the venter and circulating air blowers 
should both stop. To restore the unit to normal operation, shut off the electrical power to the 
unit, replace the blower access door and restore the electrical power. 

 
INTEGRATED FAN / IGNITION CONTROL 

This heater is equipped with a combination ignition module and fan control. The ignition source 
is an electronic device. This device ignites the burners upon a call for heat. It also controls the 
venter blower and the various speed selections and timings of the circulating air blower. This 
control is located in the circulating air blower compartment. 
Upon a demand for heat the venter is energized. After a short purge, the electronic ignition de-
vice is energized. The burners are ignited, and after a slight delay, are proven. 
The circulating air blower is energized approximately thirty (30) seconds after the burners are 
ignited. The circulating air blower is de-energized by a field selectable fan off timer. 
THIS CONTROL IS NOT FIELD REPAIRABLE. 
 
 

Summary of Contents for GMP Series

Page 1: ...re and the current state adjustments of the appliance are compatible FACTORY FITTED FOR NATURAL 2H 20 mbar 230V 50Hz 15A 2kW GAS SUPPLY PRESSURE BURNER PRESSURE COUNTRIES OF DESTINATION 2L G25 25Mbar...

Page 2: ...SERVICE INSTRUCTIONS 19 SEQUENCE OF OPERATION 19 REMOVING AN EXISTING APPLIANCE 20 INSPECTING AND CLEANING THE HEAT EXCHANGER 21 ILLUSTRATIONS 22 24 TROUBLESHOOTING 25 26 WIRING DIAGRAM 27 TABLES 28...

Page 3: ...6 MM 318 MM 075 32 35W BSPT 106 MM hp 1 40A 25 40 CM 15 24 CM 43 356 MM 318 MM 100 42 35W BSPT 106 MM hp 2 25A 25 40 CM 20 32 CM 43 446 MM 408 MM 125 52 35W BSPT 106 MM hp 4 70A 27 94 CM 25 40 CM 43 5...

Page 4: ...1 54 4 B13701 54 4 B13701 54 4 15 B13768 51 16 B13680 34 B13680 34 B13680 16 B13680 00 B13680 34 B13680 46 17 25393 00 25393 00 25393 01 25393 03 18393 01 25393 00 18 B11416 64 B11416 64 B11416 64 B11...

Page 5: ...5...

Page 6: ...W AREAS AND MAY NOT DISPERSE NATURALLY UNLESS ALLOWED BY LOCAL CODE APPLIANCES SO FUELED SHALL NOT BE INSTALLED IN AN ABOVE GRADE UNDER FLOOR SPACE OR BASEMENT UNLESS SUCH LOCATION IS PROVIDED WITH AP...

Page 7: ...EPT FREE OF ALL COMBUSTIBLE MATERIAL INCLUDING PETROL AND OTHER FLAMMABLE VAPORS AND LIQUIDS THE HEATER ROOM MUST NOT BE USED AS A BROOM CLOSET OR FOR ANY OTHER STORAGE PURPOSE WARNING THIS HEATER IS...

Page 8: ...hould be at least a 100mm separation between these entries The vent of a lower input appliance must enter the vent above the higher capacity appliance The vent terminal must be located not less than 6...

Page 9: ...REQUIRED IN ANY COMBINATION SHOWN GAS WATER HEATER FURNACE AIR FROM HEATED SPACE GABLE VENT VENTILATED ATTIC GABLE OR SOFFIT VENT SOFFIT VENTS NOTE EACH OPENING SHALL HAVE A FREE AREA OF NOT LESS THA...

Page 10: ...END ABOVE INSULATION OUTLET AIR 6 45 cm2 PER 1 170 kW INTLET AIR 6 45 cm2 PER 1 170 kW VENTILATED CRAWL SPACE GAS WATER HEATER FURNACE MINIMUM OF ONE AIR INLET AND ONE AIR OUTLET REQUIRED IN ANY COMBI...

Page 11: ...jacent location or the outdoors may become necessary When the heater is installed in a confined space the ductwork must be brought to a location outside that space It must also be sealed airtight to t...

Page 12: ...crawl space combustion air ducts or direct open ings The following installations may require OUTDOOR AIR for combustion due to chemical expo sures Commercial buildings Hobby or craft rooms Indoor poo...

Page 13: ...ure drop of 1 24 Mbar and a specific gravity of 0 60 natural gas PIPE LENGTH OF PIPE IN METERS SIZE 3 6 9 12 15 18 21 24 1 2 4 29 3 40 2 74 2 32 2 06 1 87 1 72 1 61 3 4 10 20 7 08 5 66 4 81 4 27 3 91...

Page 14: ...SAPPEAR IN A SHORT AMOUNT OF TIME IT IS RECOMMENDED THAT THE DOORS AND WINDOWS BE OPENED UPON INITIAL START UP TO VENT THE BUILDING OF THIS NON TOXIC NON STAINING SMOKE CAUTION One of the most common...

Page 15: ...RODUCTS INCLUDING CARBON MONOXIDE TO ENTER THE LIVING SPACE CREATING A POTENTIALLY HAZARDOUS CONDITION SUCH AS CARBON MONOXIDE POISONING OR DEATH ELECTRICAL SUPPLY CONNECTIONS The electrical requireme...

Page 16: ...d rating plate Turn off gas and electrical supply remove manometers and replace any plugs that were removed Use a pipe joint compound that is suitable for use with L P gas Restore any other appliances...

Page 17: ...ical supply to the heater reinstall the disconnected sensor wire and reset the power supply to restore the heater to its normal operation BLOWER DOOR INTERLOCK SWITCH The purpose of the switch is to d...

Page 18: ...measure and adjust the temperature rise Before starting the heater visually inspect all joints and seams in the supply and return air ducts for leaks Repair them if necessary Adjust the room thermosta...

Reviews: