Goodman GMP Series Installation & Operating Instructions Manual Download Page 13

 

 

13

 

WARNING 

NEVER USE AN OPEN FLAME TO CHECK FOR GAS LEAKS. THIS PRACTICE MAY 
CAUSE A FIRE, EXPLOSION, BODILY HARM INCLUDING DEATH OR PROPERTY 
DAMAGE. 
Pipe joint compound must be resistant to the action of L.P. gas. 
A union and listed manual shutoff must be installed exterior to the heater cabinet so the control 
assembly may be easily removed. 
A plug on the supply pipe at the manual valve for the purpose of making pressure measure-
ment must also be installed. The valve should be readily accessible for turning on or off. A 
capped sediment trap, sometimes referred to as a drip leg, should be installed in the gas sup-
ply pipe as close to the heater as possible. This trap must incorporate a change of direction of 
the gas flow. 
Refer to local codes or other available publications for proper location of the manual shutoff 
and sediment trap lengths. 
The gas pipe must be sized to eliminate undue pressure drop. See pipe capacity table or con-
sult your local utility. 
Both the supply and manifold pressure must be measured and adjusted, if necessary. 
   
NOTE: Copper tubing must not be used for natural gas installations where more than .3 grains 
of hydrogen sulfide per 2.83 standard cubic meters of gas is present. 
Capacity of gas pipe of different diameters and length in M

3

/HR with a pressure drop of 1.24 

Mbar and a specific gravity of 0.60 (natural gas). 
 
PIPE   

 

 

LENGTH OF PIPE IN METERS  

SIZE* 

  3  6  9  12 15 18 21 24 

1/2  4.29 3.40 2.74 2.32 2.06 1.87 1.72 1.61 
3/4 10.20 7.08 5.66 4.81 4.27 3.91 3.54 3.34 

  19.27 13.17 10.62  9.06 8.07 7.36 6.80 6.23 

1/4  39.67 26.92 21.82 18.70 16.43 15.02 13.88 13.03 

1/2  59.51 41.37 33.43 28.05 25.50 22.95 21.25 19.55 

* Nominal size of Iron Pipe in inches. 
 
After the length of pipe has been determined, select the pipe size, which will provide the mini-
mum gas flow for the required input of the appliance. In the case where more than one appli-
ance utilizes the same supply pipe be sure to consider the sum of all  appliances. 
Gas pipe must not run through or inside circulating air ducts. 
Do not use piping of a smaller size than the gas valve inlet size.  
The gas input of the appliance is marked on the specification plate. The heating value of the 
gas may be determined by contacting the gas utility or gas supplier. 
 

CIRCULATING AIR SUPPLY AND RETURN AIR 

 
The circulating air supply may be taken from; 1) outside the building, 2) return ducts from sev-
eral rooms, 3) central return, 4) any combination of the above. 
It is recommended that the supply duct have an access panel so the heat exchanger can be 
viewed. This panel shall be of sufficient size to permit the entrance of a light or probe to assist 
in the observation of the heat exchanger integrity or sampling the air stream. It should sealed 
to prevent air leakage during normal operation. 

Summary of Contents for GMP Series

Page 1: ...re and the current state adjustments of the appliance are compatible FACTORY FITTED FOR NATURAL 2H 20 mbar 230V 50Hz 15A 2kW GAS SUPPLY PRESSURE BURNER PRESSURE COUNTRIES OF DESTINATION 2L G25 25Mbar...

Page 2: ...SERVICE INSTRUCTIONS 19 SEQUENCE OF OPERATION 19 REMOVING AN EXISTING APPLIANCE 20 INSPECTING AND CLEANING THE HEAT EXCHANGER 21 ILLUSTRATIONS 22 24 TROUBLESHOOTING 25 26 WIRING DIAGRAM 27 TABLES 28...

Page 3: ...6 MM 318 MM 075 32 35W BSPT 106 MM hp 1 40A 25 40 CM 15 24 CM 43 356 MM 318 MM 100 42 35W BSPT 106 MM hp 2 25A 25 40 CM 20 32 CM 43 446 MM 408 MM 125 52 35W BSPT 106 MM hp 4 70A 27 94 CM 25 40 CM 43 5...

Page 4: ...1 54 4 B13701 54 4 B13701 54 4 15 B13768 51 16 B13680 34 B13680 34 B13680 16 B13680 00 B13680 34 B13680 46 17 25393 00 25393 00 25393 01 25393 03 18393 01 25393 00 18 B11416 64 B11416 64 B11416 64 B11...

Page 5: ...5...

Page 6: ...W AREAS AND MAY NOT DISPERSE NATURALLY UNLESS ALLOWED BY LOCAL CODE APPLIANCES SO FUELED SHALL NOT BE INSTALLED IN AN ABOVE GRADE UNDER FLOOR SPACE OR BASEMENT UNLESS SUCH LOCATION IS PROVIDED WITH AP...

Page 7: ...EPT FREE OF ALL COMBUSTIBLE MATERIAL INCLUDING PETROL AND OTHER FLAMMABLE VAPORS AND LIQUIDS THE HEATER ROOM MUST NOT BE USED AS A BROOM CLOSET OR FOR ANY OTHER STORAGE PURPOSE WARNING THIS HEATER IS...

Page 8: ...hould be at least a 100mm separation between these entries The vent of a lower input appliance must enter the vent above the higher capacity appliance The vent terminal must be located not less than 6...

Page 9: ...REQUIRED IN ANY COMBINATION SHOWN GAS WATER HEATER FURNACE AIR FROM HEATED SPACE GABLE VENT VENTILATED ATTIC GABLE OR SOFFIT VENT SOFFIT VENTS NOTE EACH OPENING SHALL HAVE A FREE AREA OF NOT LESS THA...

Page 10: ...END ABOVE INSULATION OUTLET AIR 6 45 cm2 PER 1 170 kW INTLET AIR 6 45 cm2 PER 1 170 kW VENTILATED CRAWL SPACE GAS WATER HEATER FURNACE MINIMUM OF ONE AIR INLET AND ONE AIR OUTLET REQUIRED IN ANY COMBI...

Page 11: ...jacent location or the outdoors may become necessary When the heater is installed in a confined space the ductwork must be brought to a location outside that space It must also be sealed airtight to t...

Page 12: ...crawl space combustion air ducts or direct open ings The following installations may require OUTDOOR AIR for combustion due to chemical expo sures Commercial buildings Hobby or craft rooms Indoor poo...

Page 13: ...ure drop of 1 24 Mbar and a specific gravity of 0 60 natural gas PIPE LENGTH OF PIPE IN METERS SIZE 3 6 9 12 15 18 21 24 1 2 4 29 3 40 2 74 2 32 2 06 1 87 1 72 1 61 3 4 10 20 7 08 5 66 4 81 4 27 3 91...

Page 14: ...SAPPEAR IN A SHORT AMOUNT OF TIME IT IS RECOMMENDED THAT THE DOORS AND WINDOWS BE OPENED UPON INITIAL START UP TO VENT THE BUILDING OF THIS NON TOXIC NON STAINING SMOKE CAUTION One of the most common...

Page 15: ...RODUCTS INCLUDING CARBON MONOXIDE TO ENTER THE LIVING SPACE CREATING A POTENTIALLY HAZARDOUS CONDITION SUCH AS CARBON MONOXIDE POISONING OR DEATH ELECTRICAL SUPPLY CONNECTIONS The electrical requireme...

Page 16: ...d rating plate Turn off gas and electrical supply remove manometers and replace any plugs that were removed Use a pipe joint compound that is suitable for use with L P gas Restore any other appliances...

Page 17: ...ical supply to the heater reinstall the disconnected sensor wire and reset the power supply to restore the heater to its normal operation BLOWER DOOR INTERLOCK SWITCH The purpose of the switch is to d...

Page 18: ...measure and adjust the temperature rise Before starting the heater visually inspect all joints and seams in the supply and return air ducts for leaks Repair them if necessary Adjust the room thermosta...

Reviews: