Goodman GMH80453AN Series Technical Manual Download Page 12

FURNACE SPECIFICATIONS

12

NOTES:

1.

For elevations above 2000 feet the rating should be reduced by 4% for each 1000 feet above sea level. The furnace must not be derated,
orifice changes should only be made if necessary for altitude.

2.

The total heat loss from the structure as expressed in TOTAL BTU/HR must be calculated by the manufacturers method or in accordance with
the "A.S.H.R.A.E. GUIDE" or "MANUAL J-LOAD CALCULATIONS" published by the AIR CONDITIONING CONTRACTORS OF AMERICA. The total
heat loss calculated should be equal to or less than the heating capacity. Output based on D.O.E. test procedures, steady state efficiency times
output.

*

Low NOx model available

1.

These furnaces are manufactured for natural gas operation. Optional kits are available for conversion to propane operation.

2.

Minimum Circuit Ampacity calculated as: (1.25 x Circulator Blower Amps) + I.D. Blower Amps. Wire sizes should be determined in accordance
with National Electrical Codes.Extensive wire runs will require larger wire sizes.

3

Maximum Overcurrent protections Device refers to maximumrecommended fuse or circult breaker size. May use time delay fuses or HACR-
type circuit breakers of the same sizes as noted.

MODEL

G

M

H8045

3AN*

G

M

H8070

3AN*

G

M

H8

0704BN*

G

M

H809

03BA

G

M

H8

0904BN*

G

M

H8

0905CN*

G

M

H8

1155CN*

G

M

H8

1405DN*

Input, Natural Gas (BTUH)

45,000

70,000

70,000

90,000

90,000

90,000

115,000

140,000

    Output, Natural Gas (BTUH) 

1

36,000

56,000

56,000

72,000

72,000

72,000

92,000

112,000

     Output, LP (BTUH)

32,000

48,000

48,000

64,000

64,000

64,000

80,000

96,000

     A.F.U.E.

80.0%

80.0%

80.0%

80.0%

80.0%

80.0%

80.0%

80.0%

Rated External Static (" w.c.)

0.20 - 0.50

0.20 - 0.50

0.20 - 0.50

0.20 - 0.50

0.20 - 0.50

0.20 - 0.50

0.20 - 0.50

0.20 - 0.50

Temperature Rise (°F)

25 - 55

25 -55

20 - 50

30 - 60

35 - 65

35 - 65

35 - 65

40 - 70

Pressure Switch Trip Point (" w.c.)

-0.60

-0.60

-0.60

-0.60

-0.60

-0.70

-0.70

-1.35

Blower Wheel (D" x W")

10x6

10x6

10x8

10x8

10x8

10x10

10x10

10x10

Blower Horsepower

1/3

1/3

1/2

1/3

1/2

1/2

1/2

3/4

Blower Speeds 

4

4

4

4

4

4

4

4

Max CFM @ 0.5 E.S.P.

1344

1273

1897

1493

1895

2051

2076

2152

Power Supply (Volts/Hz/Ph)

115/60/1

115/60/1

115/60/1

115/60/1

115/60/1

115/60/1

115/60/1

115/60/1

     Minimum Circuit Ampacity (MCA) 

2

8.1

8.1

12.5

8.1

12.5

12.5

12.5

14.7

     Maximum Overcurrent Device 

3

15

15

15

15

15

15

15

15

Transformer (VA)

40

40

40

40

40

40

40

40

ID Blower Pressure Switch
    Trip Point (" w.c.)
        Square Nose Blowers

-.60

-.60

-.60

-.60

-.60

-.70

-.70

-.75

ID Blower Pressure Switch
    Trip Point (" w.c.)
        Round Nose Blowers

-.60

-.60

-.47

-.75

-.75

-.60

-.70

-.60

Primary Limit Setting (°F)

210

160

170

150

170

200

150

150

Auxiliary Limit Setting (°F)

120

120

120

120

120

120

120

120

Rollout Limit Setting (°F)

300

300

300

300

300

300

300

300

Fan Delay On Heating 

30

30

30

30

30

30

30

30

           Off Heating *

150

150

150

150

150

150

150

150

Fan  Delay  On  Cooling 

5

5

5

5

5

5

5

5

           Off Cooling 

45

45

45

45

45

45

45

45

Fan  Delay  On  -  Fan  Only 

5

5

5

5

5

5

5

5

Gas Supply Pressure
    (Natural/Propane) (" w.c.)

7 / 11

7 / 11

7 / 11

7 / 11

7 / 11

7 / 11

7 / 11

7 / 11

Manifold Pressure
    (Natural/Propane) (" w.c.)

3.5 / 10

3.5 / 10

3.5 / 10

3.5 / 10

3.5 / 10

3.5 / 10

3.5 / 10

3.5 / 10

Orifice Size (Natural/Propane)

43 / 55

43 / 55

43 / 55

43 / 55

43 / 55

43 / 55

43 / 55

43 / 55

Number of Burners

2

3

3

4

4

4

5

6

Vent  Connector Diameter (inches)

4

4

4

4

4

4

4

4

Shipping Weight (lbs.)

120

130

143

153

153

163

163

183

Summary of Contents for GMH80453AN Series

Page 1: ...or services performed by an unqualified person Refer to Service Manual RS6610004 for installation operation and troubleshooting information All safety information must be followed as provided in the...

Page 2: ...power before servicing or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death Installation and repair of this unit should be...

Page 3: ...into this unit Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines These regulations may vary by jurisdiction Should questions arise conta...

Page 4: ...ombustion products An interlock switch prevents furnace operation if the blower door is not in place Keep the blower access door in place except for inspection and maintenance This furnace is also equ...

Page 5: ...es The kit will provide the proper design certified input rate within the specified altitude range 2000 3000 4000 4500 5000 6000 7000 8000 US BURNER ORIFICE 44 55 44 55 45 56 45 56 46 57 47 58 47 58 C...

Page 6: ...Draft Blower 11 Blower Door Interlock Switch 12 Integrated Control Module with fuse and diagnostic LED 13 Transformer 40 VA 14 Circulator Blower 15 Junction Box Pressure Switch Flue Pipe Connection C...

Page 7: ...PRODUCT DIMENSIONS 7 GMH8 UNITS A B GMH80453AN GMH80703AN 14 12 5 GMH80704BN GMH80903BN GMH80904BN 17 5 16 GMH80905CN GMH81155CN 21 19 5 GMH81405DN 24 5 23 All dimensions are in inches...

Page 8: ...5CN 0 60 B1370142 GMH81155CN 0 70 B1370158 GMH81155CN 0 70 B1370158 GMH81405DN 0 75 013070159 GMH81405DN 0 60 013070142 PRESSURE SWITCH TRIP POINTS AND USAGE CHART SQUARE NOSE ROUND NOSE PRESSURE SWIT...

Page 9: ...ights have an insulated Z bracket for use with one size smaller furnace All proper coil combinations are subject to being AHRI rated with a matched outdoor unit C A P F 1824 A 6 A PRODUCT TYPE C Indoo...

Page 10: ...m such as a central return Upflow Filters FURNACE INPUT FILTER SIZE TYPE 45M 160 in2 permanent 70M 241 in2 permanent 90M 320 in2 permanent 115M 400 in2 permanent 140M 370 in2 permanent 45M 320 in2 dis...

Page 11: ...lows Off On Mode 5 Min Fixed Auto Mode Dipswitch 2nd Stage Delay Dipswitch Note This furnace is designed to be used with a single stage room thermostat Start Start Call for Heat Call for Heat Safety C...

Page 12: ...000 80 000 96 000 A F U E 80 0 80 0 80 0 80 0 80 0 80 0 80 0 80 0 Rated External Static w c 0 20 0 50 0 20 0 50 0 20 0 50 0 20 0 50 0 20 0 50 0 20 0 50 0 20 0 50 0 20 0 50 Temperature Rise F 25 55 25...

Page 13: ...5 694 681 663 640 625 591 562 522 HIGH 4 0 2234 23 2151 24 2076 25 1990 26 1897 27 1803 1710 1569 GMH80704BN MED 3 5 1676 31 1653 31 1648 31 1581 33 1555 33 1492 1414 1 35 MEDIUM MED LO 3 0 1342 38 13...

Page 14: ...0 120 100 130 140 150 100 90 80 70 60 50 40 30 20 10 OUTPUT BTU HR x 1000 BTU OUTPUT vs TEMPERATURE RISE CHART TEMPERATURE RISE 600 CFM 700 900 1000 1100 1200 1400 1600 1800 2000 2200 2400 CFM FORMULA...

Page 15: ...ST BE USED WHEN SERVICING 1 SET HEAT ANTICIPATOR ON ROOM THERMOSTAT AT 0 7 AMPS BLOWER PRIMARY LIMIT WH GR BK IGNITER SURFACE HOT PU RD 15 PIN PLUG C NO SWITCH PRESSURE BR SENSOR FLAME BK WH ROLLOUT L...