GMVM97 Airflow Data

GMVM970603BNA

Cooling Speed 

(@ .1" - .8" w.c. ESP)

GMVM970603BNA

Heating Speed

(@ .1" - .5" w.c. ESP; Rise Range:   25 - 55°F)

Tap

Adjust

High-Stage

CFM

Low-Stage

CFM

Tap

Adjust

High-Stage

CFM

Rise

(°F)

A

Minus 10%

539

358

A

Minus 10%

858

n/a

Normal  

599

398

Normal  

953

n/a

Plus 10%

659

438

Plus 10%

1,048

51

B

Minus 10%

735

501

B

Minus 10%

953

n/a

Normal  

817

557

Normal  

1,059

51

Plus 10%

899

613

Plus 10%

1,165

46

C

Minus 10%

906

626

C

Minus 10%

1,042

52

Normal  

1,007

696

Normal  

1,158

47

Plus  10%

1,108

766

Plus 10%

1,274

42

D

Minus 10%

1,091

729

D

Minus 10%

1,134

48

Normal  

1,212

810

Normal  

1,260

43

Plus 10%

1,333

891

Plus 10%

1,386

39

GMVM970803BNA

Cooling Speed 

(@ .1" - .8" w.c. ESP)

GMVM970803BNA

Heating Speed

(@ .1" - .5" w.c. ESP; Rise Range:  30 - 60°F)

Tap

Adjust

High-Stage

CFM

Low-Stage

CFM

Tap

Adjust

High-Stage

CFM

Rise

(°F)

A

Minus 10%

566

363

A

Minus 10%

1,082

n/a

Normal  

629

403

Normal  

1,202

60

Plus 10%

692

443

Plus 10%

1,322

54

B

Minus 10%

725

486

B

Minus 10%

1,184

n/a

Normal  

806

540

Normal  

1,316

55

Plus 10%

887

594

Plus 10%

1,448

50

C

Minus 10%

921

635

C

Minus 10%

1,250

57

Normal  

1,023

705

Normal  

1,389

52

Plus 10%

1,125

776

Plus 10%

1,528

47

D

Minus 10%

1,107

737

D

Minus 10%

1,256

57

Normal  

1,230

819

Normal  

1,396

51

Plus 10%

1,353

901

Plus 10%

1,536

47

GMVM970804CNA

Cooling Speed 

(@ .1" - .8" w.c. ESP)

GMVM970804CNA

Heating Speed

(@ .1" - .5" w.c. ESP; Rise Range:  25 - 55°F)

Tap

Adjust

High-Stage

CFM

Low-Stage

CFM

Tap

Adjust

High-Stage

CFM

Rise

(°F)

A

Minus 10%

710

462

A

Minus 10%

1,105

n/a

Normal  

789

513

Normal  

1,228

n/a

Plus 10%

868

564

Plus 10%

1,351

53

B

Minus 10%

870

594

B

Minus 10%

1,203

n/a

Normal  

967

660

Normal  

1,337

54

Plus 10%

1,064

726

Plus 10%

1,471

49

C

Minus 10%

1,064

712

C

Minus 10%

1,287

n/a

Normal  

1,182

791

Normal  

1,430

50

Plus 10%

1,300

870

Plus 10%

1,573

46

D

Minus 10%

1,238

822

D

Minus 10%

1,364

53

Normal  

1,375

913

Normal  

1,516

47

Plus 10%

1,513

1,004

Plus 10%

1,668

43

Notes:

•  All furnaces ship as high speed for cooling.  Installer must adjust blower speed as needed.
• 

For most jobs, about 400 CFM per ton when cooling is desirable.

• 

Do not operate above .5" w.c. ESP in heating mode.  

INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.

Summary of Contents for GCVM97

Page 1: ...icient and quiet variable speed airflow system gently ramps up or down according to heating or cooling demand Multiple continuous fan speed options offer quiet air circulation Auto Comfort and enhance...

Page 2: ...w Horizontal A Initial Release B 1st Revision Motor V Variable Speed ECM ComfortNet NOx E Multi Speed ECM N Low NOx S Single Speed Cabinet Width Gas Valve B 17 5 M Modulating C 21 C Two Stage D 24 5 S...

Page 3: ...on System ICS Installer must supply one or two PVC pipes one for combustion air optional and one for the flue outlet required Vent pipe must be either 2 or 3 in diameter depending upon furnace input n...

Page 4: ...C 5 9 19 23 24 31 A 21 2 14 23 1 1 28 2 1 2 2 2 6 1 26 23 Unfolded Flanges 22 Folded Flanges D Folded Flanges E Unfolded Flanges Air Discharge Side Cut out Side Cut Out Air Discharge LEFT SIDE VIEW FR...

Page 5: ...s Supply Location High Voltage Electrical Outlet Standard Drain Trap Connection PVC Left Side Exterior Drain Trap Holes Air Intake Pipe 2 PVC Vent Flue Pipe 2 PVC Alternate Gas Supply Location Alterna...

Page 6: ...rmal 1 316 55 Plus 10 887 594 Plus 10 1 448 50 C Minus 10 921 635 C Minus 10 1 250 57 Normal 1 023 705 Normal 1 389 52 Plus 10 1 125 776 Plus 10 1 528 47 D Minus 10 1 107 737 D Minus 10 1 256 57 Norma...

Page 7: ...djust High Stage CFM Rise F A Minus 10 780 492 A Minus 10 1 702 63 Normal 867 547 Normal 1 891 57 Plus 10 954 602 Plus 10 2 080 52 B Minus 10 1 044 748 B Minus 10 1 746 62 Normal 1 160 831 Normal 1 94...

Page 8: ...Cooling Speed 1 8 w c ESP GCVM970803BNA Heating Speed 1 5 w c ESP Rise Range 35 65 F Tap Adjust High Stage CFM Low Stage CFM Tap Adjust High Stage CFM Rise F A Minus 10 562 365 A Minus 10 950 n a Norm...

Page 9: ...Adjust High Stage CFM Rise F A Minus 10 706 472 A Minus 10 1 583 57 Normal 784 524 Normal 1 759 51 Plus 10 862 576 Plus 10 1 935 46 B Minus 10 970 670 B Minus 10 1 617 56 Normal 1 078 744 Normal 1 797...

Page 10: ...TU HR x 1000 BTU OUTPUT vs TEMPERATURE RISE CHART TEMPERATURE RISE 600 CFM 700 900 1000 1100 1200 1400 1600 1800 2000 2200 2400 CFM FORMULAS BTU OUTPUT CFM x 1 08 x RISE RISE BTU OUTPUT 1 08 CFM 800 T...

Page 11: ...TO 60HZ 115 VAC 1 POWER SUPPLY WITH POWER BEFORE SERVICING WIRING TO UNIT MUST BE TO UNIT MUST BE PROPERLY POLARIZED EQUIPMENT GND FIELD SPLICE SWITCH TEMP SWITCH PRESSURE PROT DEVICE LOW VOLTAGE FIE...

Page 12: ...it 3 or 2 0170K00001S Flush Mount Vent Kit 2 AFE18 60A Fossil Fuel Dual Fuel Kit LPLP03 Low LP Gas Pressure Switch LPM 09 LP Conversion Kits Notes Indicates available for this model For installation i...

Reviews: