NOTE:
This furnace is equipped with an ignition device which
automatically lights the burner. Do not try to light the burner by
hand.
5. Move the furnace gas valve manual control to the OFF
position.
6. Wait five minutes then smell for gas. Be sure check
near the floor as some types of gas are heavier than air.
7. If you smell gas after five minutes, immediately follow
the
Safety Instructions
on page 2 of this manual. If you
do not smell gas after five minutes, move the furnace
gas valve manual control to the ON position.
8. Replace the burner compartment door.
9. Open the manual gas shutoff valve external to the furnace.
10. Turn on the electrical power to the furnace.
11. Adjust the thermostat to a setting above room
temperature.
12. After the burners are lit, set the thermostat to desired
temperature.
F
URNACE
S
HUTDOWN
1. Set the thermostat to the lowest setting.
The integrated control will close the gas valve and
extinguish flame. Following a 15 second delay, the
induced draft blower will be de-energized. After a 120,
150, 180 or 210-second delay period (field selectable
delay OFF [90, 120, 150, 180] plus 30-second ramp
down), the circulator blower de-energizes.
2. Remove the burner compartment door and move the
furnace gas valve manual control to the OFF position.
3. Close the manual gas shutoff valve external to the furnace.
4. Replace the burner compartment door.
G
AS
S
UPPLY
P
RESSURE
M
EASUREMENT
CAUTION
T
O
PREVENT
UNRELIABLE
OPERATION
OR
EQUIPMENT
DAMAGE
,
THE
INLET
GAS
SUPPLY
PRESSURE
MUST
BE
AS
SPECIFIED
ON
THE
UNIT
RATING
PLATE
WITH
ALL
OTHER
HOUSEHOLD
GAS
FIRED
APPLIANCES
OPERATING
.
The line pressure supplied to the gas valve must be within the
range specified below. The supply pressure can be measured
at the gas valve inlet pressure boss or at a hose fitting installed
in the gas piping drip leg. The supply pressure must be mea-
sured with the burners operating. To measure the gas supply
pressure, use the following procedure.
INLET
OUTLET
Gas Valve On/Off
Selector Switch
White-Rodgers Model 36G54 (Two-Stage)
Inlet
Pressure
Boss
Low Fire
Regulator
Adjust
Manometer
Manometer
Hose
High Fire Regulator
Adjust
Regulator
Vent
Outlet
Pressure Boss
Open to
Atmosphere
On/Off Switch
High Fire Coil
Terminal (HI)
Coaxial Coil
Terminal (M)
Common
Terminal(C)
White-Rodgers Model 36G54 Connected to Manometer
Gas Valve On/Off
Selector Switch
Regulator
Vent
High Fire
Regulator
Adjust
Low Fire
Regulator
Adjust
Honeywell Model VR9205 (Two-Stage)
i
Manometer
Manometer
Hose
Common
Terminal(C)
High Fire Coil
Terminal (HI)
Low Fire Coil
Terminal (LO)
Inlet Pressure Tap
1/8 NPT
Open to
Atmosphere
Outlet Pressure Tap
1/8 NPT
Honeywell Model VR9205 Connected to Manometer
1. Turn OFF gas to furnace at the manual gas shutoff valve
external to the furnace.