background image

14

F

IX

 3 - R

EBUILD

 

THE

 C

ROWN

If the chimney crown is damaged, a qualified mason must re-
pair it in accordance with nationally recognized building codes
or standards. One such standard which may be referenced is
the Standard for Chimneys, Fireplaces, Vents, and Solid Fuel
Burning Appliances, ANSI/NFPA 211.

F

IX

 4 - R

ELINING

Relining options include B vent and flexible liners.

If the chimney has diagonal offsets, B vent probably cannot be
used.

If  B vent is to be used, it must be supported adequately. Sup-
ports (such as fire stops or thimbles) must be used to prevent
the B vent from coming into direct contact with the tile liner or
chimney walls. Direct contact would result in higher heat loss,
with an increased possibility of poor venting system perfor-
mance.

It is not acceptable to vent one appliance inside the B vent and
other appliances outside. The excess space between the B
vent and the chimney walls must be covered at the top of the
chimney by a weatherproof, corrosion resistant flashing.

The B vent should then be topped with a listed vent cap. The
listed vent cap will, when installed per the manufacturer’s in-
structions, prevent problems due to rain, birds, or wind effects.

A B-vent installed as described in this section is considered to
be an enclosed vent system, and the sizing tables in National
Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition and in
the National Standard of Canada, CAN/CSA B149.1 and CAN/
CSA B149.2 - latest editions and amendments may be used.

If a flexible liner is to be used, it must be made of the proper
materials:

For most residential applications, an aluminum liner
should be acceptable.

If the combustion air supplied to the furnace will be
contaminated with compounds containing chlorine or
fluorine, a liner of AL 29-4C stainless steel should be
used. Common sources of chlorine and fluorine
compounds include indoor swimming pools and
chlorine bleaches, paint strippers, adhesives, paints,
varnishes, sealers, waxes (which are not yet dried)
and solvents used during construction and remodeling.
Various commercial and industrial processes may also
be sources of chlorine/fluorine compounds.

Heavier gauge 300 and 400 series stainless steel liners
were developed for use with oil or solid fuel appliances.
They are not suitable for use with gas-fired appliances.
Flexible liners specifically intended and tested for gas
applications are listed in the UL “Gas and Oil
Equipment Directory”. (UL Standard 1777).

National Standard of Canada, CAN/CSA B149.1 and CAN/CSA
B149.2 - latest editions and amendments, then the clay tile
liner can probably be used as a vent for the gas appliances.
However, the installer must keep in mind the following factors
which may render the tile liner unsuitable for use as a vent:

Extremely cold weather

Long vent connectors

Masonry chimneys with no air gap between the liner
and the bricks. (In practice, this can be difficult to
detect.)

Exterior chimneys (The tables in  National Fuel Gas
Code NFPA 54/ANSI Z223.1 - latest edition and in the
National Standard of Canada, CAN/CSA B149.1 and
CAN/CSA B149.2 - latest editions and amendments
assume interior chimneys.)

If, in the judgment of the local gas utility, installer, and/or local
codes; one or more of the above factors is likely to present a
problem, the chimney must be relined (Fix 4).

F

IX

 1 - L

INER

 T

ERMINATION

Any cap or roof assembly used with a liner must be approved
by the liner manufacturer for such use. The liner and cap/roof
assembly must then terminate above the roof in accordance
with the manufacturer’s instructions.

In some cases, a shorter extension above the roof may be
possible with a liner than would be required with a masonry
chimney.

For further information on relining, see Fix 4.

F

IX

 2 -C

HANGE

 V

ENTING

 A

RRANGEMENTS

If the masonry chimney has more than one channel, it may be
possible to vent the gas appliances into one channel and vent
the solid or liquid fuel appliance(s) into another channel(s). Do
not vent an 80+ Furnace inside of a metal liner with other appli-
ances vented outside the liner.

Alternatively, the homeowner may agree to discontinue use of
the fireplace (solid fuel appliance). If so, the tile liner must be
cleaned to remove creosote buildup. The fireplace opening must
then be permanently sealed.

If oil-fired appliance(s) are being replaced by gas-fired
appliance(s), the tile liner must first be cleaned to remove the
fuel oil residue.

If none of the above options is practical, the furnace may need
to be vented vertically with a B Vent.

Under some conditions, a 90%+ furnace could be installed rather
than an 80% furnace. The 90%+ furnace can be vented hori-
zontally or vertically through PVC pipe.

Summary of Contents for DVC80603B

Page 1: ...s a matter of common sense a matter of thinking before acting Most dealers have a list of specific good safety practices follow them The precautions listed in this Installation Manual are intended as...

Page 2: ...LEANOUT 13 CHECK 5 LINER CONDITION 13 CHECK 6 DILUTION AIR 13 CHECK 7 COMPLETE THE INSTALLATION 13 FIX 1 LINER TERMINATION 14 FIX 2 CHANGE VENTING ARRANGEMENTS 14 FIX 3 REBUILD THE CROWN 14 FIX 4 RELI...

Page 3: ...ATION 34 POWER UP 34 HEATING MODE 34 COOLING MODE 35 FAN ONLY MODE 35 OPERATIONAL CHECKS 35 SAFETY CIRCUIT DESCRIPTION 36 INTEGRATED CONTROL MODULE 36 PRIMARY LIMIT 36 AUXILIARY LIMIT 36 ROLLOUT LIMIT...

Page 4: ...AND IN SUCH CASE ALTERNATIVE HEAT SOURCES SHOULD BE UTILIZED WARNING TO PREVENT POSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK THE FURNACE MUST BE LOCATED TO PROTECT THE ELE...

Page 5: ...trol module to electrostatic discharge This procedure is applicable to both installed and non installed ungrounded furnaces 1 Disconnect all power to the furnace Do not touch the integrated control mo...

Page 6: ...els currently in pro ductioncanbeviewedatwww goodmanmfg comor www amana hac com If your model is not currently in production or does not appear on the website please contact your installing con tracto...

Page 7: ...hese pub lications are available from National Fire Protection Association Inc 1 Batterymarch Park Quincy MA 02269 NOTE Furnaces with NOx screens meet the California NOx emission standards and Califor...

Page 8: ...ing salts or chemicals carbon tetrachloride halogen type refrigerants cleaning solutions such as perchloroethylene printing inks paint removers varnishes hydrochloric acid cements and glues antistatic...

Page 9: ...ing Turn on clothes dryers and any appliance not connected to the venting system Turn on any exhaust fans such as range hoods and bathroom exhausts so they shall operate at maximum speed Do not operat...

Page 10: ...ap pliances i e water heaters All installations must be vented in accordance with National Fuel Gas Code NFPA54 ANSI Z223 1 latest edition In Canada the furnaces must be vented in ac cordance with the...

Page 11: ...t on the suitability of this type of venting In most situations the existing masonry chimneys will require a properly sized metallic liner POSSIBILITY OF PROPERTY DAMAGE PERSONAL INJURY OR DEATH DAMAG...

Page 12: ...clude fireplaces wood stoves coal fur naces and incinerators Proper Chimney Termination Check 1 Chimney channel free of solid and liquid fuel appliances Check 2 Change venting arrangements Fix 2 Crown...

Page 13: ...air will not be available the chimney must be relined Fix 4 CHECK 7 COMPLETE THE INSTALLATION If Checks 1 through 6 have been satisfactory and the liner is an acceptable size as determined by the tabl...

Page 14: ...or solid fuel appliances They are not suitable for use with gas fired appliances Flexible liners specifically intended and tested for gas applications are listed in the UL Gas and Oil Equipment Direc...

Page 15: ...N AFTER SERVICING CAUTION HIGH VOLTAGE TO AVOID THE RISK OF INJURY ELECTRICAL SHOCK OR DEATH THE FURNACE MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES OR IN THEIR ABSENCE WITH THE LATES...

Page 16: ...CODE WARNING To ensure proper unit grounding the ground wire should run from the furnace ground screw located inside the furnace junc tion box all the way back to the electrical panel NOTE Do not use...

Page 17: ...ermine the time to transition from low stage to high stage To use a single stage thermostat turn off power to the fur nace move the thermostat selection DIP switch to the OFF position Set the desired...

Page 18: ...inals for controlling power to an optional field supplied humidifier and or electronic air cleaner The accessory load specifications are as follows Humidifier 1 0 Amp maximum at 120 VAC Electronic Air...

Page 19: ...iring rate by changing orifices or increasing the manifold pressure This can cause poor combustion and equipment failure High altitude installations may require both a pressure switch and an orifice c...

Page 20: ...the furnace Use two pipe wrenches when making connection to the gas valve to keep it from turning The orientation of the gas valve on the manifold must be maintained as shipped from the factory Instal...

Page 21: ...AK SINCE PROPANE GAS IS HEAVIER THAN AIR ANY LEAKING GAS CAN SETTLE IN ANY LOW AREAS OR CONFINED SPACES PROPANE GAS ODORANT MAY FADE MAKING THE GAS UNDETECTABLE EXCEPT WITH A WARNING DEVICE WARNING A...

Page 22: ...e blower from interfering with combustion air or draft when a cen tral return is used a connecting duct must be installed be tween the unit and the utility room wall A room closet or alcove must not b...

Page 23: ...or dirty filter Circulating air filters must be inspected monthly for dirt accumulation and replaced if necessary Failure to maintain clean filters can cause prema ture heat exchanger failure A new ho...

Page 24: ...losethemanualgasshutoffvalveexternaltothefurnace 4 Replace the burner compartment door GASSUPPLYPRESSUREMEASUREMENT CAUTION TO PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE THE INLET GAS SUPPLY PRE...

Page 25: ...The manifold pressure must be measured with the burners operating To measure and adjust the manifold pressure use the following procedure 1 Turn OFF gas to furnace at the manual gas shutoff valve exte...

Page 26: ...justment for details NOTE The final manifold pressure cannot vary by more than 0 3 w c from the specified setting Consult your local gas supplier if additional input rate adjustment is required 5 Repe...

Page 27: ...Acooling airflow of 990 CFM can be attained by setting the cooling speed to C and the adjustment to minus 4 Continuous fan speed in legacy mode is 25 of the furnace s maximum airflow capability For co...

Page 28: ...et System Airflow Consideration section for details DVC81005C DVC80805C DVC80603B MVC81005C MVC80805C MVC80604B To set airflow C 7 5 min 82 60 sec 100 A 60 sec 100 TAP 1 2 3 4 5 6 7 8 To set Comfort M...

Page 29: ...he dual 7 segment LED display In general lower heating speeds will reduce electrical consump tion lower operating sound levels of the blower and increase the outlet air temperature delivered to the ho...

Page 30: ...he CTK0 thermostat provides the airflow demand The thermostat may be configured for a low medium or high continuous fan speed The low medium and high fan speeds correspond to 25 50 and 75 respec tivel...

Page 31: ...ee tables below for listing of furnace submenus Touch the or _ to step through the list of submenus and view settings If a setting can be adjusted _ and keys will appear Use the _ or keys to adjust th...

Page 32: ...y repeated faults are shown a maximum of 3 times DIAGNOSTICS Submenu Item Indication for Display Only not User Modifiable Model Number MOD NUM Displays the furnace model number Serial Number SER NUM D...

Page 33: ...m CL TRM 10 to 10 in 2 increments default is 0 Selects the airflow trim amount for the non communicating compatible single stage AC unit Cool Airflow Profile CL PRFL A B C or D default is A Selects th...

Page 34: ...tions LED 2 Flashes Out of box reset Control power up Learn button depressed None None Off No power Communications error No power to furnace Open fuse Communications error Check fuses and circuit brea...

Page 35: ...balance of the heat off delay period 60 90 120 or 150 seconds Circulator blower and electronic air cleaner terminal is de energized Circulator blower ramps down to OFF during the 30 seconds following...

Page 36: ...and or blocked condensate drain condi tions FLAME SENSOR The flame sensor is a probe mounted to the burner manifold assembly which uses the principle of flame rectification to de termine the presence...

Page 37: ...ear This check should be per formed at the beginning of the heating season This will ensure that all furnace components are in proper working order and that the heating system functions appropriately...

Page 38: ...ect the flue pipe system from the induced draft blower 4 Remove the induced draft blower and collector box cover 5 Clean the primary heat exchanger tubes using a wire brush attached to a length of hig...

Page 39: ...nse signal Sand sensor if coated and or oxidized x Check flue piping for blockage proper length elbows and termination x Verify proper induced draft blower performance x Turn power OFF prior to repair...

Page 40: ...l for heat IMPROPER FLAME E4 x Short to ground in flame sense circuit x Lingering burner flame x Slow closing gas valve x Correct short at flame sensor or in flame sensor wiring x Check for lingering...

Page 41: ...Repair replace if necessary x Inspect flue and or inlet air piping for blockage proper length elbows and termination Check drain system Correct as necessary x Check induced draft blower performance C...

Page 42: ...has lost communications with circulator blower motor MOTOR COMM b1 x Loose wiring connection at circulator motor control leads x Failed circulator blower motor x Failed integrated control module x Ti...

Page 43: ...et thermostat Call for Service icon illuminated x ComfortNet thermostat scrolls Check Furnace message b6 x Circulator blower motor shuts down for over or under voltage condition x Circulator blower mo...

Page 44: ...G CYCLE HIGH STAGE PRESSURE SWITCH STUCK OPEN REVERSED 115 VAC POLARITY DATA NOT YET ON NETWORK INVALID MEMORY CARD DATA BLOWER MOTOR NOT RUNNING BLOWER COMMUNICATION ERROR BLOWER HP MIS MATCH BLOWER...

Page 45: ...30 sec 50 7 5 min 82 30 sec 50 Select desired Comfort Mode profile see profiles above Set switches 5 and 6 to the appropriate ON OFF positions A OFF OFF OFF OFF OFF OFF OFF OFF Model Tap Low Stage Hig...

Page 46: ...CIRCULATOR BLOWER R 1 GND JUNCTION BOX SWITCH TEMP NEUTRAL 115kBTU MODELS BLOWER COMPARTMENT DOOR SWITCH OPEN WHEN DOOR OPEN C LINE BK 4 NEUTRAL POLARIZED AND C FS 2 PLUG CONNECTION DISCONNECT PU 3 I...

Page 47: ...47 THIS PAGE LEFT INTENTIONALLY BLANK...

Page 48: ...48 Goodman Manufacturing Company L P 5151 San Felipe Suite 500 Houston TX 77056 www goodmanmfg com 2011 2012 Goodman Manufacturing Company L P...

Reviews: