SERVICING
77
Cool Adjust Profile
Selection Selection Selection
Switches Switches Switches
D ON ON ON ON ON ON
C OFF ON OFF ON OFF ON
(1) Select model and desired
high stage cooling airflow. Determine the cooresponding tap
( A, B, C, or D ). Set dip switches 1 and 2 to the appropriate
ON / OFF positions. (2) Select model and installed electric
heater size. Set switches 9, 10, and 11 to the appropriate
ON/OFF positions. (3) Select the airflow adjustment factor tap
A and D are 0%; Tap B is +10%; Tap C - 10%. Set dip switches 3
and 4 to the appropriate ON / OFF positions.
Select desired Comfort Mode profile
(see profiles above). Set switches 5 and 6 to the approriate
ON / OFF positions.
A ------- -------- 60 sec/100%
B ON OFF ON OFF ON OFF
TAP 1 2 3 4 5 6
To set airflow:
D 30 sec/50% 7.5 min/82% 30 sec/50%
A OFF OFF OFF OFF OFF OFF
0140A00045
Speed Selection Dip Switches
B ------- 30 sec/50% 60 sec/100%
To set Comfort Mode:
Profiles Pre-Run Short-Run OFF Delay
C ------- 7.5 min/82% 60 sec/100%
Model Tap Low Stage High Stage
Cool Cool
MBVC1200
*
A 400 600
B 540 800
C 670 1000
D 800 1200
MBVC1600
*
A 670 1000
B 800 1200
C 940 1400
D 1070 1600
*
MBVC2000
A 800 1200
B 1070 1600
C 1200 1800
D 1340 2000
Htr Kw 9 10 11 MBVC1200* MBVC16000* MBVC2000*
3 ON ON ON 600 800 800
5 ON ON OFF 600 800 800
6 ON OFF ON 635 800 800
8 ON OFF OFF 740 1000 1000
10 OFF ON ON 1000 1000 1200
15 OFF ON OFF 1400 1500 1500
20 OFF OFF ON NR NR 2000
MBVC Airflow Table