BLOWER PERFORMANCE SPECIFICATIONS
20
1. Units are shipped without filter(s). CFM in chart is without filter(s).
2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed
as needed. The first task is to determine the proper aiflow for the cooling system.
3. For most cooling applications, about 400 CFM per ton is desirable.
4. The chart is for information only. For satisfactory operation, external static pressure not to exceed value shown on
rating plate.
5. Do not operate above 0.5" w.c. ESP in heating mode. Operating between 0.5" w.c. and 0.8" w.c. is tabulated for cooling
purposes only.
6. * Motor CFM minimum.
GMVC95/AMVC95 Continuous Fan Speed Chart
Model
Furnace Maximum
CFM
Continuous Fan
Speed
1,2
GMVC950453BX*
AMVC950453BX*
1400
420
GMVC950704CX*
AMVC950704CX*
1760
530
GMVC950905DX*
AMVC950905DX*
2200
660
GMVC951155DX*
AMVC951155DX*
2200
660
1
Continuous fan speed is 30% of furnace maximum CFM
2
Three continuous fan speeds are possible with the CTK01AA
thermostat: 30%, 50%, and 70% of furnace maximum CFM
GCVC9/ACVC9 Continuous Fan Speed Chart
Model
Furnace Maximum
CFM
Continuous Fan
Speed
1,2
GCVC90704CX*
ACVC90704CX*
1760
530
GCVC90905DX*
ACVC90905DX*
2200
660
GCVC91155DX*
2350
705
1
Continuous fan speed is 30% of furnace maximum CFM
2
Three continuous fan speeds are possible with the CTK01AA
thermostat: 30%, 50%, and 70% of furnace maximum CFM.