background image

4

www.goodmanmfg.com

SS-GACNF

SS-GACNF

www.goodmanmfg.com

5

P

roduct

 S

PecificationS

P

roduct

 S

PecificationS

A

irflow

 d

AtA

H

eAting

 C

ApACity

/

k

w C

orreCtion

 f

ACtor

Supply Voltage

240

230

220

210

208

Correction Factor

1.08

1.00

0.92

0.84

0.82

(Multiply the 230-volt capacity by factors)

Model

Motor 

Speed

CFM delivered against External Static Pressure

0.1”

0.2”

0.3”

0.4”

0.5”

ACNF180***

High

710

660

590

515

435

Low

650

595

540

480

390

ACNF240***

High

955

880

820

740

675

Low

885

840

775

725

620

ACNF300***

High

1,075

1,005

920

820

730

Low

945

890

835

760

650

Note: Airflow data for 240 Vac with dry coil and no filter in place.

Summary of Contents for ACNF Series

Page 1: ...h efficiency evaporator coil Quiet operation Available with and without heat AHRI Certified ETL Certified Complete warranty details available from your local dealer or at www goodmanmfg com To receive...

Page 2: ...igerant Compatability R Mul Posi on PSC Motor 4 R 410A S Mul Posi on EEM Motor W Wall Mount PSC Motor Electrical 1 208 240 V 1 Phase 60 Hz Cabinet Finish U Unpainted Nominal Width P Painted B 17 Wide...

Page 3: ...30 208 230 208 230 Min Circuit Ampacity 230V 0 9 27 33 5 40 6 1 68 27 8 34 3 Min Circuit Ampacity 208V 0 9 23 5 29 2 35 3 1 68 24 3 29 9 Max Overcurrent Device 230V 15 30 35 45 15 30 35 Max Overcurren...

Page 4: ...Liquid Suction Electrical Data Voltage 208 230 208 230 208 230 208 230 208 230 208 230 208 230 Min Circuit Ampacity 230V 41 3 54 9 1 68 27 8 34 3 41 3 54 9 Min Circuit Ampacity 208V 36 1 47 8 1 68 24...

Page 5: ...4 0 82 Multiply the 230 volt capacity by factors Model Motor Speed CFM delivered against External Static Pressure 0 1 0 2 0 3 0 4 0 5 ACNF180 High 710 660 590 515 435 Low 650 595 540 480 390 ACNF240 H...

Page 6: ...6 www goodmanmfg com SS GACNF Product Specifications Dimensions Model A B C D ACNF18 37 3411 16 30 6 ACNF24 43 4011 16 36 6 ACNF30 49 4611 16 42 6...

Page 7: ...ect to change Always refer to the wiring diagram or the unit for the most up to date wiring W arning High Voltage Disconnect all power before servicing or installing this unit Multiple power sources m...

Page 8: ...hange at any time specifications or designs without notice or without incurring obligations 2013 Goodman Manufacturing Company L P Houston Texas Printed in the USA Accessories Model Description HPSK 0...

Reviews: