background image

4

www.goodmanmfg.com

SS-GACNF

SS-GACNF

www.goodmanmfg.com

5

P

roduct

 S

PecificationS

P

roduct

 S

PecificationS

s

peCifiCAtions

 (

Cont

.)

ACNF24

081

ACNF24

101

ACNF30

001

ACNF30

051

ACNF30

061

ACNF30

081

ACNF30

101

Performance Ratings
Cooling (BTU/h)

24,000

24,000

30,000

30,000

30,000

30,000

30,000

Airflow Rate CFM (High/ Low)¹

880/840

880/840

1005/890

1005/890

1005/890

1005/890

1005/890

Piston Size

0.057

0.057

0.061

0.061

0.061

0.061

0.061

Blower
Diameter

6.31

6.31

6.75

6.75

6.75

6.75

6.75

Width

8.25

8.25

8.25

8.25

8.25

8.25

8.25

Coil Drain Connect FPT

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

Blower Motor
FLA

1.34

1.34

1.34

1.34

1.34

1.34

1.34

HP

 1/4

 1/4

 1/4

 1/4

 1/4

 1/4

 1/4

Refrigerant Line Connection Size
Liquid 

⅜"

⅜"

⅜"

⅜"

⅜"

⅜"

⅜"

Suction

¾"

¾"

¾"

¾"

¾"

¾"

¾"

Electrical Data
Voltage

208/230

208/230

208/230

208/230

208/230

208/230

208/230

Min Circuit Ampacity @ 230V

41.3

54.9

1.68

27.8

34.3

41.3

54.9

Min Circuit Ampacity @ 208V

36.1

47.8

1.68

24.3

29.9

36.1

47.8

Max. Overcurrent Device @ 230V

45

60

15

30

35

45

60

Max. Overcurrent Device @ 208V

40

50

15

25

30

40

50

Minimum Voltage VAC

197

197

197

197

197

197

197

Maximum Voltage VAC

253

253

253

253

253

253

253

Electric Heat
kW @ 230 Volts

7.3

9.8

0.0

4.8

6.0

7.3

9.8

BTU/h @ 230 Volts

24,900

33,500

0

16,400

20,500

24,900

33,500

Ship Weight (lbs)

69

69

79

79

79

79

79

¹   CFM @ .2 static

Note:  When the room thermostat calls for second stage heat, the first stage (heat pump) operation must be locked out. When matching the “AC” unit that 
has electric heat with a heat pump, order “HEAT PUMP SHUT OFF KIT HPSK-01.” The ACXX-00 units do not require this kit.

Summary of Contents for ACNF Series

Page 1: ...h efficiency evaporator coil Quiet operation Available with and without heat AHRI Certified ETL Certified Complete warranty details available from your local dealer or at www goodmanmfg com To receive...

Page 2: ...igerant Compatability R Mul Posi on PSC Motor 4 R 410A S Mul Posi on EEM Motor W Wall Mount PSC Motor Electrical 1 208 240 V 1 Phase 60 Hz Cabinet Finish U Unpainted Nominal Width P Painted B 17 Wide...

Page 3: ...30 208 230 208 230 Min Circuit Ampacity 230V 0 9 27 33 5 40 6 1 68 27 8 34 3 Min Circuit Ampacity 208V 0 9 23 5 29 2 35 3 1 68 24 3 29 9 Max Overcurrent Device 230V 15 30 35 45 15 30 35 Max Overcurren...

Page 4: ...Liquid Suction Electrical Data Voltage 208 230 208 230 208 230 208 230 208 230 208 230 208 230 Min Circuit Ampacity 230V 41 3 54 9 1 68 27 8 34 3 41 3 54 9 Min Circuit Ampacity 208V 36 1 47 8 1 68 24...

Page 5: ...4 0 82 Multiply the 230 volt capacity by factors Model Motor Speed CFM delivered against External Static Pressure 0 1 0 2 0 3 0 4 0 5 ACNF180 High 710 660 590 515 435 Low 650 595 540 480 390 ACNF240 H...

Page 6: ...6 www goodmanmfg com SS GACNF Product Specifications Dimensions Model A B C D ACNF18 37 3411 16 30 6 ACNF24 43 4011 16 36 6 ACNF30 49 4611 16 42 6...

Page 7: ...ect to change Always refer to the wiring diagram or the unit for the most up to date wiring W arning High Voltage Disconnect all power before servicing or installing this unit Multiple power sources m...

Page 8: ...hange at any time specifications or designs without notice or without incurring obligations 2013 Goodman Manufacturing Company L P Houston Texas Printed in the USA Accessories Model Description HPSK 0...

Reviews: