SERVICING
28
S-1 CHECKING VOLTAGE
1. Remove doors, control panel cover, etc. from unit being
tested.
With power ON:
Line Voltage now present.
2. Using a voltmeter, measure the voltage across terminals
L1 and L2 of the contactor for single phase units, and L3,
for 3 phase units.
3. No reading - indicates open wiring, open fuse(s) no power
or etc. from unit to fused disconnect service. Repair as
needed.
4. With ample voltage at line voltage connectors, energize
the unit.
5. Measure the voltage with the unit starting and operating,
and determine the unit Locked Rotor Voltage.
Locked Rotor Voltage
is the actual voltage available at
the compressor during starting, locked rotor, or a stalled
condition. Measured voltage should be above minimum
listed in chart below.
To measure Locked Rotor Voltage attach a voltmeter to
the run "R" and common "C" terminals of the compres-
sor, or to the T
1
and T
2
terminals of the contactor. Start
the unit and allow the compressor to run for several sec-
onds, then shut down the unit. Immediately attempt to
restart the unit while measuring the Locked Rotor Volt-
age.
6. Voltmeter should read within the voltage tabulation as
shown. If the voltage falls below the minimum voltage,
check the line wire size. Long runs of undersized wire
can cause low voltage. If wire size is adequate, notify
the local power company in regards to either low or high
voltage.
Voltage
Min.
Max.
460
437
506
208/230
198
253
Unit Supply Voltage
Three phase units require a balanced 3 phase power supply to
operate. If the percentage of voltage imbalance exceeds 3%
the unit must not be operated until the voltage condition is
corrected.
Max. Voltage Deviation
% Voltage =
From Average Voltage X 100
Imbalance
Average Voltage
To find the percentage of imbalance, measure the incoming
power supply.
L1 - L2 = 240V
L1 - L3 = 232V Avg. V = 710 =
236.7
L2 - L3 = 238V 3
Total 710V
To find Max. deviation:
240 - 236.7 = +3.3
232 - 236.7 =
-4.7
238 - 236.7 = +1.3
Max deviation was 4.7V
% Voltage Imbalance = 4.7
=
1.99%
236.7
If the percentage of imbalance had exceeded 3%, it must be
determined if the imbalance is in the incoming power supply or
the equipment. To do this rotate the legs of the incoming
power and retest voltage as shown below.
L1
L2
L3
L3
L2
L1
L1 - L2 = 240V
L1 - L3 = 227V
L2 - L3 = 238V
Rotate all 3 incoming
legs as shown.
L1 - L2 = 227V
L1 - L3 = 238V
L2 - L3 = 240V