F870S
3 Mounting and connection
Page 17
Gönnheimer Elektronic GmbH
Tel.: +49 (6321) 49919-0
Fax: +49 (6321) 49919-41
3.2.5 Default
parameter
Parameter defaults ex works.
Description
Display
Settings
Unit
Structure
Language setting of FS870S
Language
English
Do you use a proportional (SVP..) or
digital (SVD…) working valve
Valve
SVP3
Operation mode:
- Leakage compensation
- Continuous flow
Operation mode
Leakage compen-
sation
Function of the free programmable alarm
contact
Output function
Bypass is active
Contact order
Normally closed (NC)
Normally open (NO)
NC/NO
NO
The external alarm loop is programmable
to work in special situation only
Ext-Alert mode
Inactive
External sensor ES872 is connected to
the system or not
ES872 connected
No
Parameter
Purge volume
Purge volume
500
Ltr.
Set point of pressure controller while pre
purging phase
Setpoint Pres.Purge
2.0
mbar
Monitored minimum flow while pre
purging phase
Min.Flow Purge
0,5
Ltr./s
Set point of flow controller while pre
purging phase
Setpoint-Flow Purge
2,0
Ltr./s
Set point of pressure controller while
normal operation (after pre purging
phase)
Setpoint - Pres.Oper
2,0
mbar
Monitored minimum pressure inside Ex p
housing - at all times
Min. Pressure
0,8
mbar
Monitored maximum pressure inside Ex
p housing - at all times
Max. Pressure
15,0
mbar
Pressure limit of alarm pressure
Alarm Pressure
Codes
Code word main menu
Menu code
0001
Code word to activate bypass function
Bypass code
0002
Code word to switch on or off the ignition
capable apparatus inside the Ex p
cabinet
On/Off code
0001
Network
IP- Address
IP-Address
192.168.0.48
Subnet mask
Subnet Mask
255.255.255.0
Gateway
Gateway
192.168.0.1
Summary of Contents for F870S
Page 1: ...User s manual Pressurized enclosure system F870S Manual_F870S_v1 0 2_2016 doc...
Page 34: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......