golmar SAR-GB2 User Manual Download Page 7

7

RELAY UNIT TSAR-GB2

Operating mode “Stairs light activation relay”:

-

This operating mode allows activation of the stairs light from the apartment.

It is activated through the push button

of the telephone T-562 GB2 or Nhea GB2 and from the monitor light function

Vesta2

or Thera.

, Vesta7, Pentha

-

See user manual for telephone or monitor installed in the apartment.

-

The dip switch SW1 of the relay unit must be configured with DIP1, DIP2 and DIP3 set to OFF.

-

Maximum of one relay unit per system.

-

.

Note: Once the relay unit has been activated, by default it will deactivate automatically after 1 minute

Relay unit light activation time:

Configuration:

Step

Remove the power supply from the SAR-GB2 relay unit by removing the relay unit Bus connector (The power

1:

supply status LED will turn off).

Step

Connect the power supply to the SAR-GB2 relay unit by inserting the relay unit Bus connector. (LED showing

2:

the power supply status will turn on).

Step

In the first 5 seconds after connecting the power supply to the relay unit, bypass the terminals '-' and 'P' with a

3:

cable for 3 seconds (the status LED “in use” will flash).

Step

Next, bypass the terminals '-' and 'AP' with a cable for 3 seconds (the status LED “in use” will light up

4:

continuously).

Step

Bypass the terminals '-' and 'P' again. The time that the terminals '-' and 'P' are bypassed will configure the

5:

activation time of the relay unit (every flash of the status LED “in use” is equivalent to 30 seconds of the activation
time). The maximum configurable time is 900 seconds.

Step

After removing the bypass from the terminals '-' and 'P', the time that has been configured will be saved and the

6:

relay unit will come out of time configuration mode.

Step

Check that the activation time of the relay unit is correct.

7:

Note: The relay unit by default has a configured activation time of 1 minute.

1

2

3

ON

INSTALLATION

Summary of Contents for SAR-GB2

Page 1: ...MANUAL Code 50121952 T E SAR GB2 N REV 0117 RELAY UNIT SAR B G 2 POWER IN USE BUS BUS SAR GB2 C N C P AP N A 12 CONTACTOS RELE RELAY CONTACTS 1 25 A 48 V M x 40w 2 A 30 V M x 40w UNIDAD DE REL RELAY...

Page 2: ...of relay contacts shall not exceed from 2Ato 30 Vdc 1 25Ato 48 Vac Before connecting the system to the mains check the connections Always follow the instructions contained in this manual Introduc 2 t...

Page 3: ...ease 2 and with the panel that has been assigned through configuration in SAR GB2 during a call or communication process or It will be activated through the push button lock release 1 or lock release...

Page 4: ...g f h The relay unit can be mounted onto a DIN rail 4 elements by applying slight pressure To remove the relay unit from the rail use a flat screwdriver and lever it off as shown in the drawing Instal...

Page 5: ...and AP 8 Step Connect the power supply see step 4 9 Step Check that the operating mode is correct activating the light or lock release depending on the configuration 10 Note Repeat the procedure steps...

Page 6: ...upply to the SAR GB2 relay unit by inserting the relay unit Bus connector LED showing 2 the power supply status will turn on Step In the first 5 seconds after connecting the power supply to the relay...

Page 7: ...o the SAR GB2 relay unit by inserting the relay unit Bus connector LED showing 2 the power supply status will turn on Step In the first 5 seconds after connecting the power supply to the relay unit by...

Page 8: ...of the SAR 12 24 IMPORTANT For the description installation configuration and programming of the system see the corresponding manual Vac lock release TF 104 Main PRI SEC Golmar additional alternating...

Page 9: ...NOT S E 9 RELAY UNIT TSAR GB2...

Page 10: ...olmar se reserva el derecho a cualquier modificaci n sin previo aviso Golmar se r serve le droit de toute modification sans pr avis Golmar reserves the right to make any modifications without prior no...

Reviews: