Low pressure regulator Type NDR 0515 and Type NDR 0516
3 / 12
INTENDED USE
Must not be used in potentially explosive ex-zone 0!
Can cause an explosion or serious injuries.
Installation outside ex-zone 0.
May be used in potentially explosive ex-zones 1 or 2.
Installation by a company that specialises in explosion protection (ATEX Directive
1999/92/EC).
Installation within defined ex-zones 1 or 2.
Operating media
•
LPG (gas phase)
You will find a
list of operating media
with descriptions, the relevant
standards and the country in which they are used in the Internet at
www.gok-online.de/de/downloads/technische-dokumentation.
Place of operation
•
operate in buildings, in special installation rooms (acc. to TRF 2012) and outdoors, if
protected against the weather
If used in buildings, a ventilation line must be installed from the breather of the product to
outdoors!
Installation position
•
optional
•
observe installation direction
Installation location
•
For installation upstream from the house connection, tank systems acc. to A3 B3/4
•
For installation downstream from the house connection, tank systems acc. to A3 B3/4-t
Examples of applications:
Tank system according to A3 B3/4 for
outdoor installations "f"
Tank system according to A4 B3/4-t for
indoor installations "t"
INAPPROPRIATE USE
All uses that are not appropriate:
•
e.g. operating with different media, pressures
•
use of gases in the liquid phase
•
installation against the flow direction
•
changes to the product or parts of the product
•
use at ambient temperature varying from: see TECHNICAL DATA