Optional installation of metal filter cover PS = 16 bar 

 

  Turn retaining ring anti-clockwise 

 to loosen it, hold and remove filter cover 

  

  Take care not to damage the O-ring. Replace it if necessary (a new O-ring must be oiled!) 

  Hold the metal filter cover and the O-ring in position and tighten by hand by turning the retaining ring 

 

clockwise. 

 

Check for existing leaks, make sure no leaks will occur!

 

START-UP 

If a pressure test is required before starting up the oil-fired installation, e.g. according to OFTEC Technical Book 
3 section 5, the GS Pro-Fi 3 can be subjected to a test pressure of a maximum of 6 bar with plastic cover, or 16 
bar with metal cover. Avoid any pressure increase beyond 6 bar or 16 bar caused by heating of the test medium. 
Higher test pressures can damage the GS Pro-Fi 3. 
Before start-up, the GS Pro-Fi 3 and all the connections must be checked for leaks. This test can be included in 
the pressure, leak, or function test of the oil-fired installation. Any leaks must be sealed, e.g. by re-assembly of 
the connections with new conical nipples or tightening of the screwed connections. 
Observe the safety information under 

MAINTENANCE

Unless defined otherwise in the start-up 
instructions of the burner/furnace 
manufacturer, proceed as follows: 

Deaerate the installed oil lines (burner flow 
and return lines) and the deaerator with a 
suction pump and fill them with fuel. To this 
end, open the quick-acting valve 

 

and the 

deaeration screw 

. Connect the suction 

pump directly at the deaeration screw by 
means of the enclosed adapter, Art. no. 
13610-60.  We recommend continuing the 
suction process until the upper cover is filled 
with oil as well. After that, re-tighten the 
deaeration screw. 
 

 

 

OPERATION

 

In ongoing operation of the oil-fired  installation, the GS Pro-Fi 3 does not require any attendance. Set the 

integrated quick-acting valve 

 - a ball valve - to the 

open

 position

 by turning the handle in flow direction, as 

shown in the figure on Page 1. 
Turn the handle of the quick-acting valve to ‘closed’ position – vertical to the flow direction – for longer standstill 
periods or MAINTENANCE measures. 
Due to the intelligent design of the GS Pro-Fi 3, the full fuel oil column will be available on burner start-up without 
any noticeable air particles.  

INFORMATION ON THE FILTER ELEMENT 

There is no universal filter element. Select a filter element according to the  specification of the burner 
manufacturer, taking into account filter fineness and the respective operating conditions. The IWO Institute for 
Economically Efficient Fuel Oil Heating Systems recommends filter elements of sintered plastic of a mesh width 
of  30 to 75 

µ

m. For oil-fired installations with so-called “low NO

burners“ and burners of lower thermal output, 

GOK filter elements FEINFILTERUNG of a mesh width of < 35 

µ

m are recommended.

 

SAFETY FUNCTION

 

In case of hose rupture in the flow 

 

or return line 

, the aspired ambient air will cause the burner to go to 

“lock out” state. 
 

For pressure testing, unscrew the manometer blind screw 

 and screw in the manometer G 1/8. 

Make sure that the O-ring remains in the manometer blind screw. 
After testing, unscrew the manometer and screw in the manometer blind screw with O-ring. 
 
 
 

 

 

Diagram: 
Fuel oil filter-and-deaerator combination GS Pro-Fi 3 

 

 

Summary of Contents for 13512 Series

Page 1: ...n system of the 3 generation It is designed as a closed system Geschlossenes System GS It corresponds to the requirements of EN 12514 2 2000 the code of practice for oil firing according to BS 5410 1...

Page 2: ...VS 6 RVS 8 RVS 10 EN ISO 8434 1 GOK universal connection fittings UA 6 8 10 mm Screwed clamping ring connection brass Initial testing of construction products by a notified body HP Burner flow line Fe...

Page 3: ...The bleeder line dimensions should provide for a mean fuel flow rate of 0 2 to 0 5 m s If the diameter of the pipes is too large low flow rates occur which can result in formation of undesirable gas...

Page 4: ...of a screwed connection with brass or steel cutting ring for your information Component Connection via Explanations GS Pro Fi 3 Connecting branch in RVS 6 8 10 or 12 optionally available as factory mo...

Page 5: ...at the deaeration screw by means of the enclosed adapter Art no 13610 60 We recommend continuing the suction process until the upper cover is filled with oil as well After that re tighten the deaerat...

Page 6: ...deaerator cover can only be replaced as a complete assembly i e together with deaerator screw If the system has been submerged any outside soiling of the filter should be cleaned off with a commercial...

Page 7: ...perating medium and environment Maximum permissible pressure PS 6 bar with plastic cover PS 10 bar with easy change filter element PS 16 bar with metal cover Material of housing Metal ZP0410 Normal fl...

Page 8: ...ersion 10 2012 Page 8 GOK Regler und Armaturen Gesellschaft mbH Co KG Obernbreiter Stra e 2 16 D 97 340 Marktbreit Phone 49 9332 404 0 Fax 49 9332 404 43 E mail info gok online de Internet www gok onl...

Reviews: