GOK 13512 Series Installation And Operating Manual Download Page 1

 

Installation and Operating Manual

  

Art. No. 13512-.../13513-... 
Version 10.2012    Page 1

 

 

Fuel Oil Filter and Deaerator 

Combination 

 

 

2Y115/05

 

 

 

 

Deaeration Device with Filter and 

Quick-Acting Valve acc. to EN 12514-2

 

 
Legend 
 

 – Deaerator screw 

 – Deaerator cover 

 – Retaining ring 

 – With or without Vacuum gauge (as a special version, 

        optionally also available with rotating connection), 

 – Connection for tank line (suction line) 

 – Quick-acting valve 

 – Filter element 

 – Filter cover 

 – Fixing plate for wall installation  

 – Connection of burner return line 

 – Connection of burner flow line 

 – Screw heads for mounting the fixing panel 

 + 

 – optionally available with female thread

 

 

 

This deaerator can be used with fuel oil 
with bio-components (see OPERATING 
MEDIA)

 

CONTENT

 

General 
Safety note 
Design 
Operating media 
Connections 
Labeling 
Installation

 

Page 1 
Page 1 
Page 2 
Page 2 
Page 2 
Page 2 
Page 3 

Start-up 
Operation 
Performance check 
Maintenance 
Overhaul / Repair 
Additional technical data 
List of accessories 

Page 5 
Page 5 
Page 6 
Page 6 
Page 6 
Page 7 
Page 7 

  

GENERAL

 

The fuel oil filter-and-deaerator combination GS Pro-Fi 3 is a 

Pro

fessional 

Fi

lter deaeration system of the 

3

generation. It is designed as a closed system (“Geschlossenes System” - GS). It corresponds to the 
requirements of EN 12514-2:2000 the code of practice for oil firing according to BS 5410-1 and ‘OFTEC 
Technical Book 3 chapter 2.2.

 

In the GS Pro-Fi 3, a deaeration device is combined with a filter and a quick-acting valve connected upstream. It 
filters the fuel oil while simultaneously discharging the gases released during the suction process. The gases are 
not “deaerated“ into the environment but within the “Closed System” via the burner nozzle into the combustion 
chamber. Thus, the system works odour-free.

 

It is intended only for installation into the suction line of supplying units which are designed in single-pipe system 
with return feed for suction drain operation. 

 

For usage to the intended purpose and ensuring the warranty, please observe this Installation and Operating 
Manual and give it to the operator.

 

 

SAFETY NOTE: 

Operating media as for example fuel oil pollute water! Any material leakage occurring during 
maintenance must be collected. Observe the respective legal regulations on water pollution 
control! The GS Pro-Fi 3 must be installed, commissioned, serviced and repaired by skilled 
craftsmen. It is imperative that you observe the following notes on installation and operation!

 

 

  

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for 13512 Series

Page 1: ...n system of the 3 generation It is designed as a closed system Geschlossenes System GS It corresponds to the requirements of EN 12514 2 2000 the code of practice for oil firing according to BS 5410 1...

Page 2: ...VS 6 RVS 8 RVS 10 EN ISO 8434 1 GOK universal connection fittings UA 6 8 10 mm Screwed clamping ring connection brass Initial testing of construction products by a notified body HP Burner flow line Fe...

Page 3: ...The bleeder line dimensions should provide for a mean fuel flow rate of 0 2 to 0 5 m s If the diameter of the pipes is too large low flow rates occur which can result in formation of undesirable gas...

Page 4: ...of a screwed connection with brass or steel cutting ring for your information Component Connection via Explanations GS Pro Fi 3 Connecting branch in RVS 6 8 10 or 12 optionally available as factory mo...

Page 5: ...at the deaeration screw by means of the enclosed adapter Art no 13610 60 We recommend continuing the suction process until the upper cover is filled with oil as well After that re tighten the deaerat...

Page 6: ...deaerator cover can only be replaced as a complete assembly i e together with deaerator screw If the system has been submerged any outside soiling of the filter should be cleaned off with a commercial...

Page 7: ...perating medium and environment Maximum permissible pressure PS 6 bar with plastic cover PS 10 bar with easy change filter element PS 16 bar with metal cover Material of housing Metal ZP0410 Normal fl...

Page 8: ...ersion 10 2012 Page 8 GOK Regler und Armaturen Gesellschaft mbH Co KG Obernbreiter Stra e 2 16 D 97 340 Marktbreit Phone 49 9332 404 0 Fax 49 9332 404 43 E mail info gok online de Internet www gok onl...