FURY X-3 TECHNICAL SPECIFICATIONS
Model
Number
FX3M-
MV48-
0603
0606
0609
0612
0615
0618
1021
1024
1027
1030
Max Output Power
3kW
6kW
9kW
12kW
15kW
18kW
21kW
24kW
27kW
30kW
Maximum
Output
Amperage
24V*
64A
128A
192A
256A
320A
384A
448A
512A
576A
640A
36V*
64A
128A
192A
256A
320A
384A
448A
512A
576A
640A
48V*
52A
104A
156A
208A
260A
312A
364A
416A
468A
520A
Number of Modules
1
2
3
4
5
6
7
8
9
10
Input Amps (480V 3Ph)
4.2
8.4
12.6
16.8
21
25.2
29.4
33.6
37.8
42
Min Circuit Breaker Size
(A)
6
11
16
21
27
32
37
42
48
53
Max Circuit Breaker Size
(A)
10
15
20
25
35
40
45
50
60
70
Min. AC Input Wire Size
(AWG)
16
14
12
10
10
8
6
6
4
4
Min. DC Output Wire
Size (AWG)
1/0
1/0
2/0
3/0
4/0
4/0
3/0
(qty 2)
3/0
(qty 2)
4/0
(qty 2)
4/0*
(qty 2)
Cabinet Size
6 Bay
10 Bay
Dimensions
(HxWxD)
27”H x 18.6”W x 14.5”D
39.5”H x 18.6”W x 14.5”D
Weight
42 lbs + (# modules * 9 lbs)
65 lbs + (# modules * 9 lbs)
Input Voltage
480VAC ± 10% 3PH 60Hz
Efficiency and
Power Factor
Efficiency = 0.94
Power Factor = 0.95 max
Control
Manual and fully automatic control of charge, finish, and equalization
Environmental
0º to +40ºC (32º to 104ºF), NEMA1
Display
4.3” Backlit Color Graphic
Power Device
Silicon Carbide MOSFET
AC Line Disconnect
Yes, Contactor
Certifications*
CSA Certified to UL1564, CSA 22.2, CEC
IoT Data Capability
Wireless configuration, communication, and control capabilities via Bluetooth
®
, Wi-Fi and PLC, USB port
Field Repair
Module Replacement
Installation
Wall, stand, or shelf mounting options
* Stated output currents will require connectors and electrical cables of adequate capacity