background image

 

PSD1004 

- Intrinsically Safe 5 V Supply Module 

G.M. International ISM0074-5 

Terminal block connections 

Parameters Table 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Device Parameters 

PSD1004 Associated 

Apparatus Parameters 

Uo / Voc 

Ui / Vmax 

In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check 
its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded 
by the safety parameters (Uo/Voc, Io/Isc, Po/Po) indicated in this manual and enclosure side of the PSD1004 Intrinsically Safe Apparatus connected to it. 

Io / Isc 

 

Ii/ Imax 

 

 

Po / Po 

Pi/ Pi 

 

When checking the power matching also consider the maximum operating temperature of the field device, check that added connecting cable and field device capacitance and 
inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro / La/Ra) given in the Associated Apparatus parameters for the effective gas group (see parameters on enclosure side). 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Cable Parameters 

PSD1004 Associated 

Apparatus Parameters 

Co / Ca 

Ci / Ci  C cable 

Lo / La 

 

Li / Li L cable 

 

If the cable parameters are unknown, the following value may be used: Capacitance 60 pF per foot (180 pF per meter), Inductance 0.20 mH per foot (0.60 mH per meter). 
Note that for the PSD1004 the system analysis must be performed for the input and also for the output connection. 

Storage 

 

If after an incoming inspection the unit is not installed directly on a system (parts for spare or expansion with long storage periods) it must be conveniently stocked. Stocking area 
characteristics must comply with the following parameters: 
Temperature –10 to +30 °C  the – 40 to +80 °C in the data sheet is meant for limited periods, mainly to arrange for air transport. 
Humidity 0 to 70%   

long period high humidity affects the package integrity and promotes corrosion of metal parts. 

Vibration:  

 

no  vibration should be perceivable in the stocking area to avoid loosening of parts or fatigue ruptures of components terminals. 

Pollution:  

 

presence of pollutant or corrosive gases or vapors must be avoided to prevent corrosion of conductors and degradation of insulating surfaces. 

Disposal (Waste Electrical and Electronic Equipment) 

 

This marking shown on the products indicates that it should not be disposed with other wastes at the end of its working life. It may content hazardous substances for the health and the 
environment, to prevent possible harm from uncontrolled waste disposal, please separate this equipment from other types of wastes and recycle it responsibly to promote the sustainable 
reuse of material resources. Users should contact either the supplier or their local government office for details of where and how they can take this equipment for environmentally safe 
recycling. This product should not be mixed with other commercial wastes for disposal. 

 

 

HAZARDOUS AREA 

SAFE AREA 

Output - S 

Output - O 

13

 

14

 

15

 

16

 

Positive terminal for terminal 13 of model PSD1001C 

1

 

Negative terminal for terminal 14 of model PSD1001C 

2

 

Positive terminal 

3

 

Negative terminal 

4

 