D6036 

- SIL 2 Switch/Proximity Detector Repeater, Relay Output 

G.M. International ISM0407-0 

ON 

Line fault detection 

SW1 

Disabled 

(switch/proximity sensor)  

OFF 

Enabled, for SIL application 

(proximity sensor or switch with end of line resistors, 

detects field open circuit and short circuit, 

de-energizes relay in fault condition) 

ON 

IN/OUT Operation 

SW2 

NO-NE or NC-ND 

ON 

NO-ND or NC-NE 

(for SIL application) 

OFF 

D6036S Configuration Summary Table

 

Channel 

1  

Line fault detection 

SW1 

SW3 

Disabled 

(switch/proximity sensor) 

OFF OFF 

Enabled, for SIL application 

(proximity sensor or switch with end of line resistors, 

detects field open circuit and short circuit, 

de-energizes relay in fault condition) 

ON ON 

IN/OUT Operation 

SW2 

NO-NE or NC-ND 

ON 

NO-ND or NC-NE  

(for SIL application) 

OFF 

Channel 

SW4 

ON 

OFF 

D6036D Configuration Summary Table

 

D6036S 

A configuration DIP switch is located on component side of pcb. This switch allows the configuration of input/output relationship, fault detection functions and operating mode. 

 

 

 

Configuration 

Dip switch configuration 

CH1 

Setting 

Line fault 
detection 

IN / OUT 

Operation 

NO-NE or 

NC-ND 

NO-ND or 

NC-NE 

2

ON 

2

OFF 

Disabled 

(switch / proximity sensor) 

Enabled 

(proximity sensor or switch 

with end of line resistors, 

de-energizes relay in fault condition) 

1

 

OFF 

1

ON  

Input Input 

Input 

Input 

 

NO 

OR 

NC 

 

NO 

OR 

NC 

Output 

1-3 


NE 

Output 

1-3 


NE 

Output 

1-3 


ND 

Output 


ND 

1-3 

Position in fault condition 

1-3 


SW1  SW2  SW3  SW4 

OFF OFF OFF OFF 

DIP Switch factory settings (valid for D6036S and D6036D)

 

Configuration 

1

2

3

4

ON

Dip switch factory settings. All Switches are OFF 

1

2

3

4

ON

CH1

 

3-4 not used

 

Note: SW3 and SW4 not used.

 

Note: SW3 and SW4 used only in D6036D.

 

For SIL Application 

For SIL Application 

Summary of Contents for D6036S

Page 1: ...6036 SIL 2 Switch Proximity Detector Repeater Relay Output G M International ISM0407 0 SIL 2 Switch Proximity Detector Repeater Relay Output DIN Rail Models D6036S D6036D D6036S D6036D INSTRUCTION MANUAL ...

Page 2: ... W for 1 channel D6036S with 24 V supply voltage short circuit input and relay energized typical Isolation Test Voltage In Out 1 5 KV In Supply 1 5 KV In In 500 V Out Supply 1 5 KV Out Out 1 5 KV Input switching current levels ON 2 1 mA 1 9 to 6 2 mA range OFF 1 2 mA 0 4 to 1 3 mA range switch current 1 65 mA 0 2 mA hysteresis Fault current levels open fault 0 2 mA short fault 6 8 mA Input equival...

Page 3: ... for safety system In field programmability by DIP Switch TÜV Certification TÜV Functional Safety Certification High Density two channels per unit Simplified installation using standard DIN Rail and plug in terminal blocks with or without Power Bus Input Ch 1 for Proximity or Voltage free Contact Terminal block connections Input Ch 1 for Proximity or Voltage free Contact Input Ch 2 for Proximity o...

Page 4: ...mity voltage free Contact 7 8 Power and Fault Bus F Supply 24 Vdc 3 4 Out 2 SIL 2 In 2 Proximity voltage free Contact 9 voltage free Contact voltage free Contact R1 R2 R1 R2 MODEL D5036S 5 6 1 2 Out NO Contact SIL 2 7 8 Power and Fault Bus F Supply 24 Vdc 3 4 Out NC Contact In Proximity voltage free Contact voltage free Contact R1 R2 Relay contact shown in de energized position Terminals 1 2 and 3...

Page 5: ...red unit without suffering or causing any damage The wiring cables have to be proportionate in base to the current and the length of the cable On the section Function Diagram and enclosure side a block diagram identifies all connections Identify the number of channels of the specific card e g D6036S is a single channel model and D6036D is a dual channel model the function and location of each conn...

Page 6: ...ne resistors de energizes relay in fault condition 7 2 OFF NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 1 OFF 1 ON NE 1 2 1 ND 2 Output 1 ND 2 Output NE 1 2 Position in fault condition 1 2 Input Input Output Input Output Input CH2 Setting Line fault detection IN OUT Operation NO NE or NC ND NO ND or NC NE Disabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energize...

Page 7: ...hannel 1 2 SW4 ON OFF D6036D Configuration Summary Table D6036S A configuration DIP switch is located on component side of pcb This switch allows the configuration of input output relationship fault detection functions and operating mode Configuration Dip switch configuration CH1 Setting Line fault detection IN OUT Operation NO NE or NC ND NO ND or NC NE 2 ON 2 OFF Disabled switch proximity sensor...

Reviews: