- SIL 2 Switch/Proximity Detector Repeater, Relay Output
G.M. International ISM0407-0
ON
Line fault detection
SW1
Disabled
(switch/proximity sensor)
OFF
Enabled, for SIL application
(proximity sensor or switch with end of line resistors,
detects field open circuit and short circuit,
de-energizes relay in fault condition)
ON
IN/OUT Operation
SW2
NO-NE or NC-ND
ON
NO-ND or NC-NE
(for SIL application)
OFF
D6036S Configuration Summary Table
Channel
1
2
Line fault detection
SW1
SW3
Disabled
(switch/proximity sensor)
OFF OFF
Enabled, for SIL application
(proximity sensor or switch with end of line resistors,
detects field open circuit and short circuit,
de-energizes relay in fault condition)
ON ON
IN/OUT Operation
SW2
NO-NE or NC-ND
ON
NO-ND or NC-NE
(for SIL application)
OFF
Channel
1
2
SW4
ON
OFF
D6036D Configuration Summary Table
D6036S
A configuration DIP switch is located on component side of pcb. This switch allows the configuration of input/output relationship, fault detection functions and operating mode.
Configuration
Dip switch configuration
CH1
Setting
Line fault
detection
IN / OUT
Operation
NO-NE or
NC-ND
NO-ND or
NC-NE
2
ON
2
OFF
Disabled
(switch / proximity sensor)
Enabled
(proximity sensor or switch
with end of line resistors,
de-energizes relay in fault condition)
1
OFF
1
ON
Input Input
Input
Input
7
NO
8
OR
NC
7
8
7
NO
8
OR
NC
7
8
Output
1-3
2
4
NE
Output
1-3
2
4
NE
Output
1-3
2
4
ND
Output
2
4
ND
1-3
Position in fault condition
1-3
2
4
SW1 SW2 SW3 SW4
OFF OFF OFF OFF
DIP Switch factory settings (valid for D6036S and D6036D)
Configuration
1
2
3
4
ON
Dip switch factory settings. All Switches are OFF
1
2
3
4
ON
CH1
3-4 not used
Note: SW3 and SW4 not used.
Note: SW3 and SW4 used only in D6036D.
For SIL Application
For SIL Application