D5291
- 10 A SIL 3 Relay Output Module for ND Load with ND or NE Relay condition
G.M. International ISM0112-10
Configuration
An eight position DIP Switch is located on component side of pcb in order to set four mutually exclusive configurations:
1) line input monitoring, to allow DCS/PLC line input monitoring function (driving line pulse testing);
2) low voltage input monitoring (UVLO—under voltage lock out): module reflects a high impedance state to the control unit when the driving voltage is below the specified threshold;
3) T-proof relay testing.
WARNING:
dip-switch 2-4-6
must be set to “OFF” position
for any configuration.
Start-up
Before powering the inputs of unit check that all wires are properly connected, also verifying their polarity. Check conductors for exposed wires that could touch each other causing
dangerous unwanted shorts. Enabling input, the corresponding “RELAY STATUS” yellow led must be lit and load circuit must be according to the connection required.
Indeed, disabling each input, the corresponding “RELAY STATUS” yellow led must be turned off and load circuit must change the status.
ON
1) line input monitoring:
2) low voltage input monitoring:
3) T-proof relay testing:
DIP switch configurations:
1
2
3
4
5
6
7
8
ON
OFF OFF OFF OFF OFF OFF ON ON
1
2
3
4
5
6
7
8
ON
OFF OFF OFF OFF OFF OFF ON OFF
T-proof relays enable
1
3
5
1
3
5
Normal Operation
ON ON
OFF
ON
OFF
OFF
T-proof relays (dip1 = relay1;
dip3 = relay2; dip5 = relay3)
1
2
3
4
5
6
7
8
ON
ON OFF ON OFF ON OFF ON ON
Please, see next page for testing procedure at T-proof.
WARNING:
after T-proof test, dip-switch 1-3-5 must be set to “OFF” position for normal operation.
To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram on data sheet.
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation
requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation.
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts.
If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5291S must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided.
Relay output contact must be connected to load non exceeding category II overvoltage limits.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock
when connected to live hazardous potential.
This is factory settings