GMI D5291S Instruction & Safety Manual Download Page 8

 

D5291 

- 10 A SIL 3 Relay Output Module for ND Load with ND or NE Relay condition 

G.M. International ISM0112-10 

 

Configuration 

An eight position DIP Switch is located on component side of pcb in order to set four mutually exclusive configurations: 

1) line input monitoring, to allow DCS/PLC line input monitoring function (driving line pulse testing); 
2) low voltage input monitoring (UVLO—under voltage lock out): module reflects a high impedance state to the control unit when the driving voltage is below the specified threshold; 
3) T-proof relay testing. 

WARNING: 

dip-switch 2-4-6 

must be set to “OFF” position 

for any configuration. 

Start-up 

 Before powering the inputs of unit check that all wires are properly connected, also verifying their polarity. Check conductors for exposed wires that could touch each other causing 
dangerous unwanted shorts. Enabling input, the corresponding “RELAY STATUS” yellow led must be lit and load circuit must be according to the connection required. 
Indeed, disabling each input, the corresponding “RELAY STATUS” yellow led must be turned off and load circuit must change the status. 

 

ON 

1) line input monitoring: 

2) low voltage input monitoring: 

3) T-proof relay testing: 

DIP switch configurations: 

1

2

3

4

5

6

7

8

ON

OFF OFF OFF OFF OFF OFF  ON   ON

1

2

3

4

5

6

7

8

ON

OFF OFF OFF OFF OFF OFF  ON  OFF

T-proof relays enable

1

3

5

1

3

5

Normal Operation

ON ON

OFF

ON

OFF

OFF

T-proof relays (dip1 = relay1;

dip3 = relay2; dip5 = relay3)

1

2

3

4

5

6

7

8

ON

 ON  OFF  ON  OFF  ON OFF  ON   ON

 

Please, see next page for testing procedure at T-proof. 

    

WARNING: 

after T-proof test, dip-switch 1-3-5 must be set to “OFF” position for normal operation. 

To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram on data sheet. 

The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation 
requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. 
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. 
If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water. 

Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5291S must be cleaned only with a damp or antistatic cloth. 

Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. 
Relay output contact must be connected to load non exceeding category II overvoltage limits. 

Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock 
when connected to live hazardous potential. 

This is factory settings 

Summary of Contents for D5291S

Page 1: ...Module for ND Load with ND or NE Relay condition G M International ISM0112 10 10 A SIL 3 Relay Output Module for ND Load with ND or NE Relay condition DIN Rail and Termination Board Model D5291S D529...

Page 2: ...te No A 13625 and KR No MIL20769 EL002 Certificates for maritime applications Mounting T35 DIN Rail according to EN50022 or on customized Termination Board Weight about 165 g Connection by polarized p...

Page 3: ...state 2 SIL 3 for ND load energized in fail safe state with NE relay condition de energized in fail safe state 16 A inrush current at 24 Vdc 250 Vac Line input monitoring in field DIP Switch selectabl...

Page 4: ...nergized in fail safe state is available at terminal blocks 13 15 In this case the Safety Function is met when the relay is de energized closed contact SIL3 Safety Function for ND load energized in fa...

Page 5: ...defined fail safe state so that the output load remains de energized fail No effect failure mode of a component that plays a part in implementing the safety function but is neither a safe failure nor...

Page 6: ...e defined fail safe state so that the output load remains de energized fail No effect failure mode of a component that plays a part in implementing the safety function but is neither a safe failure no...

Page 7: ...t 99 of all possible Dangerous Undetected failures in the relay module Warning Operation D5291S relay module is suitable for the switching of safety related circuits providing isolation between the in...

Page 8: ...proof relays dip1 relay1 dip3 relay2 dip5 relay3 1 2 3 4 5 6 7 8 ON ON OFF ON OFF ON OFF ON ON Please see next page for testing procedure at T proof WARNING after T proof test dip switch 1 3 5 must be...

Reviews: