GMI D5291S Instruction & Safety Manual Download Page 3

 

G.M. International ISM0112-10 

D5291 

- 10 A SIL 3 Relay Output Module for ND Load with ND or NE Relay condition 

Front Panel and Features 



SIL 3 according to IEC 61508:2010 Ed. 2 for Tproof = 6 / 20 yrs (

10% / >10 % of total SIF) for ND load with ND relay (terminals 13-14). 



SIL 3 according to IEC 61508:2010 Ed. 2 for Tproof = 14 / 20 yrs (

10% / >10 % of total SIF) for ND load with NE relay (terminals 13-15). 



PFDavg (1 year) 1.58 E-05, SFF 96.35 % for ND load with ND relay. 



PFDavg (1 year) 7.01 E-06, SFF 99.17% for ND load with NE relay. 



Systematic capability SIL 3. 



Installation in Zone 2 / Division 2. 



10 A SPDT contact for 2 different Safety Functions: 
1) SIL 3 for ND load (energized in fail safe state) with ND relay condition (energized in fail safe state); 
2) SIL 3 for ND load (energized in fail safe state) with NE relay condition (de-energized in fail safe state). 



16 A inrush current at 24 Vdc / 250 Vac. 



Line input monitoring in-field DIP Switch selectable. 



Driving input voltage monitoring. 



Input/Output isolation. 



EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system. 



ATEX, IECEx, UL & C-UL, FM & FM-C, INMETRO, EAC-EX, UKR TR n. 898, NEPSI, TÜV Certifications. 



TUV Functional Safety Certification. 



Type Approval Certificate DNV and KR for maritime applications. 



Simplified installation using standard DIN-Rail and plug-in terminal blocks or customized Termination Boards. 

Ordering Information 

 

 

Model: D5291S 

DIN-Rail accessories: Cover and fix MCHP196 

SPDT Output Common 

Terminal block connections 

SAFE AREA 

SPDT Output Normally Open Contact 

SPDT Output Normally Close Contact 

13

 

14

 

15

 

+ Input 

1

 

- Input 

2

 

+ Input 

3

 

- Input 

4

 

Not used 

16

 

13 14 15 16 

4 3 2 1 

Summary of Contents for D5291S

Page 1: ...Module for ND Load with ND or NE Relay condition G M International ISM0112 10 10 A SIL 3 Relay Output Module for ND Load with ND or NE Relay condition DIN Rail and Termination Board Model D5291S D529...

Page 2: ...te No A 13625 and KR No MIL20769 EL002 Certificates for maritime applications Mounting T35 DIN Rail according to EN50022 or on customized Termination Board Weight about 165 g Connection by polarized p...

Page 3: ...state 2 SIL 3 for ND load energized in fail safe state with NE relay condition de energized in fail safe state 16 A inrush current at 24 Vdc 250 Vac Line input monitoring in field DIP Switch selectabl...

Page 4: ...nergized in fail safe state is available at terminal blocks 13 15 In this case the Safety Function is met when the relay is de energized closed contact SIL3 Safety Function for ND load energized in fa...

Page 5: ...defined fail safe state so that the output load remains de energized fail No effect failure mode of a component that plays a part in implementing the safety function but is neither a safe failure nor...

Page 6: ...e defined fail safe state so that the output load remains de energized fail No effect failure mode of a component that plays a part in implementing the safety function but is neither a safe failure no...

Page 7: ...t 99 of all possible Dangerous Undetected failures in the relay module Warning Operation D5291S relay module is suitable for the switching of safety related circuits providing isolation between the in...

Page 8: ...proof relays dip1 relay1 dip3 relay2 dip5 relay3 1 2 3 4 5 6 7 8 ON ON OFF ON OFF ON OFF ON ON Please see next page for testing procedure at T proof WARNING after T proof test dip switch 1 3 5 must be...