![GMI D5290S-078 Instruction & Safety Manual Download Page 3](http://html1.mh-extra.com/html/gmi/d5290s-078/d5290s-078_instruction-and-safety-manual_2236228003.webp)
3
D5290S-078
- 5 A SIL 3 Relay Output Module
G.M. International ISM0152-8
Ordering Information
Front Panel and Features
SIL 3 according to IEC 61508:2010 for Tproof = 10 / 20 years (
≤
10% / >10 % of total SIF) with PFDavg (1 year) 7.01 E-06,
SFF = 99.17 % for two NE loads (see application n° 1, 2) or two ND loads (see application n° 4) with NE relay condition.
SIL 2 according to IEC 61508:2010 for Tproof = 7 / 20 years (
≤
10% / >10 % of total SIF) with PFDavg (1 year) 1.40 E-04,
SFF = 66.61 % for four NE loads with NE relay condition (see application n° 3).
SIL 3 according to IEC 61508:2010 for Tproof = 6 / 20 years (
≤
10% / >10 % of total SIF) with PFDavg (1 year) 1.58 E-05,
SFF = 98.81 % for a ND load with ND relay condition (see application n° 5).
SIL 2 according to IEC 61508:2010 for Tproof = 20 yrs (
≤
10% of total SIF) with PFDavg (1 year) 1.54 E-05,
SFF = 98.28 % for two ND loads with ND relay condition (see application n° 6).
Systematic capability SIL 3.
Installation in Zone 2 / Division 2.
5 A SIL 3 / SIL 2 contacts for NE or ND loads with NE or ND Relay condition.
8 A inrush current at 30 Vdc / 250 Vac.
Line input monitoring in-field DIP Switch selectable.
Driving input voltage monitoring.
Input/Output isolation.
EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system.
ATEX, IECEx, FM, FMC, EAC-EX, TÜV Certifications.
TÜV Functional Safety Certification.
Type Approval Certificate DNV and KR for maritime applications.
Simplified installation using standard DIN-Rail and plug-in terminal blocks or customized Termination Boards.
Model: D5290S-078
DIN-Rail accessories: Cover and fix MCHP196
Normally Open (NO) contact (Out S_1)
Terminal block connections
SAFE AREA
13
4 3 2 1
13 14 15 16
17 18 19 20
21 22 23 24
14
15
16
17
18
19
20
21
22
23
24
1
Input +
2
Input -
3
Input +
4
Input -
Normally Open (NO) contact (Out S_2)
Normally Closed (NC) contact (Out P_1)
Normally Closed (NC) contact (Out P_2)
Normally Open (NO) contact (Out S_4)
Normally Open (NO) contact (Out S_3)