GMI D5202S Instruction & Safety Manual Download Page 6

 

D5202S 

- 4 A, 24 Vdc, SIL 3 Power Distribution and Diagnostic Module 

G.M. International ISM0177-4 

 

Functional Safety Manual and Applications 

Safety Function and Failure behavior:

  

D5202S is considered to be operating in Low Demand mode, as a Type A module, having Hardware Fault Tolerance (HFT) = 0. 
The failure behaviour of the module is described by the following definitions: 
 

 fail-Safe State: it is defined as the output voltage (on Power Bus) to be deviated inside the allowed 18 to 30 Vdc range or below 2 Vdc; 

 

 fail Safe: this failure causes the system to go to the defined fail-safe state without a process demand; 

 

 fail Dangerous: failure mode that does not respond to a demand from the process (i.e. being unable to go to the defined fail-safe state), 

     so that the output voltage (on Power BUS) is deviated between 2 Vdc and 18 Vdc; 
 

 fail “No effect”: failure mode of a component that plays a part in implementing the safety function but is neither a safe failure nor a dangerous failure; 

 

 fail “Not part”: failure mode of a component which is not part of the safety function but part of the circuit diagram and is listed for completeness. 

     When calculating the SFF, this failure mode is not taken into account. It is also not considered for the total failure rate evaluation. 

Failure rates table according to IEC 61508:2010 Ed.2 : 

λ

sd

 

λ

su

 

λ

dd

 

λ

du

 

SFF

 

0.00 FIT 

36.88 FIT 

0.00 FIT 

0.05 FIT 

99.86% 

PFDavg vs T[Proof] table 

(assuming Proof Test coverage of 95%), with determination of SIL supposing module contributes 

10% of total SIF dangerous failures:       

T[Proof] = 1 year

 

T[Proof] = 20 years

 

PFDavg = 2.19 E-07 - Valid for 

SIL 3

 

PFDavg = 4.38 E-06 - Valid for 

SIL 3

 

Failure rate table:

 

Failure category

 

Failure rates (FIT)

 

λ

dd

 = Total Dangerous Detected failures 

0.00 

λ

du

 = Total Dangerous Undetected failures 

0.05 

λ

sd

 = Total Safe Detected failures 

0.00 

λ

su

 = Total Safe Undetected failures 

36.88 

λ

tot safe

 = Total Failure Rate (Safety Function) = 

λ

dd

 + 

λ

du

 + 

λ

sd

 + 

λ

su

 36.93 

λ

not part

 = “Not Part” failures 

293.40 

λ

tot device

 = Total Failure Rate (Device) = 

λ

tot safe

 + 

λ

no effect

 + 

λ

not part

  

449.45 

MTBF (device, single channel) = (1 / 

λ

tot device

) + MTTR (8 hours) 

254 years 

MTTF

S

 (Total Safe) = 1 / (

λ

sd

 + 

λ

su

) 3095 

years 

MTTF

D

 (Dangerous) = 1 / 

λ

du

 

2.28 E+06 years 

λ

no effect

 = “No effect” failures 

119.12 

MTBF (safety function, single channel) = (1 / 

λ

tot safe

) + MTTR (8 hours) 

3091 years 

 

The D5202S can repeat the common fault signal from the Power and Fault Bus, therefore considering all diagnostic functions enabled, the cumulative fault diagnostic functionality is 
described by the following table, where the status (open or closed) of Common Fault output contact is related to the common fault signal: 

Common Fault signal 

on Power and Fault Bus 

Common Fault - NO contact 

Pins 1-2 

Common Fault - NC contact 

Pins 1-3 

High signal between 

Fault pole and Negative (-) pole of BUS 

(Normal condition) 

Closed 

(Normal condition) 

Open 

(Normal condition) 

Low signal between 

Fault pole and Negative (-) pole of BUS 

(Common Fault condition) 

Open 

(Common Fault condition) 

Closed 

(Common Fault condition) 

COM FLT LED state 

OFF 

ON 

Testing procedure at T-proof 

 The proof test shall be performed to reveal dangerous faults which are undetected by diagnostic. This means that it is necessary to specify how dangerous undetected faults, which 

have been noted during the FMEDA, can be revealed during proof test. The Proof test consists of the following steps: 

Steps

 

Action

 

1

 

Bypass the safety-related PLC or take other appropriate action to avoid a false trip when removing the unit for test. 

2

 

Supply the D5202S by means of two DC power sources, whose values must be comprised between 20 and 30 Vdc, connected between 
terminals 9-10 (Supply Line 1) and 11-12 (Supply Line 2). Connect a DC voltmeter between Power Bus terminals 1 and 2. 
In this condition, the output supply voltage, measured by means of the DC voltmeter, should be close to the higher input supply voltage value and 
neither of the “FLT1” and “FLT2” LEDs should be lit. 
If, on the other hand, an output supply voltage comprised between 2 and 18 Vdc is measured and the “FLT1” and “FLT2” LEDs are turned off, 
a dangerous failure which has produced a wrong output voltage of the ideal diode controller circuits is detected. 

5

 

Remove the bypass from the safety-related PLC or restore normal operation inserting the unit. 

3

 

Use the same setup described in the previous step and measure, by means of an AC voltmeter, the rms value of the output voltage. 
In normal operation conditions, the output supply voltage should have no AC components, that is its rms value should be ideally null. 
If an rms value well above 0 Vrms is measured (a reasonable value could be 50% of the higher supply line value, i.e. 12 Vrms compared to 24 Vdc), 
a dangerous failure which has produced an oscillation of the ideal diode controller circuits is detected. 

4

 

Restore the loop to full operation. 

This test will reveals around 95 % of all possible Dangerous Undetected failures in this module. 

Systematic capability SIL 3 

Summary of Contents for D5202S

Page 1: ...02S 4 A 24 Vdc SIL 3 Power Distribution and Diagnostic Module G M International ISM0177 4 4 A 24 Vdc SIL 3 Power Distribution and Diagnostic Module DIN Rail Model D5202S D5202S INSTRUCTION SAFETY MANU...

Page 2: ...rtificate No C IS 224248 01 SIL 3 conforms to IEC61508 2010 Ed 2 T V Certificate No C IS 236198 09 SIL 3 Functional Safety Certificate conforms to IEC61508 2010 Ed 2 for Management of Functional Safet...

Page 3: ...ATEX IECEx UKR TR n 898 TUV Certifications T V Functional Safety Certification Type Approval Certificate DNV and KR for maritime applications Simplified installation on beginning end or both sides of...

Page 4: ...AREA ZONE 2 GROUP IIC T4 9 10 11 12 MODEL D5202S F Power and Fault Bus Power Supply 1 3 NC 2 NO Common Fault Output 1oo2 Power Fault 1 CM 7 NC 6 NO 5 CM Power Supply 2 Note In case of single power su...

Page 5: ...ble describes the OFF operation absence of supply on Power Bus and the ON operation presence of 20 30 Vdc supply on Power Bus of the D5202S according to the OFF ON state of each Power Supply source al...

Page 6: ...erefore considering all diagnostic functions enabled the cumulative fault diagnostic functionality is described by the following table where the status open or closed of Common Fault output contact is...

Page 7: ...the contact maximum rating 5 A 250 Vac 1250 VA 5 A 250 Vdc 175 W resistive load To prevent relay contacts from damaging connect an external protection fuse or similar chosen according to the relay br...

Page 8: ...detection on power supply 2 4 Operation with disabled cumulative fault detection DIP switch configurations 1 2 3 4 ON 5 6 7 8 OFF OFF OFF ON ON ON OFF OFF 1 2 3 4 ON 5 6 7 8 OFF OFF OFF ON ON ON OFF O...

Reviews: