D5093-TB
- SIL3 24/220Vdc/Vac Transistor-Out Detector
G.M. International ISM0541-2
3
Ordering Information
Front Panel and Features
SIL 3 according to IEC 61508:2010 Ed.2 for Tproof = 6 / 20 years (
≤
10% / >10 % of total SIF)
PFDavg (1 year) 1.54 E-05, SFF 96.53 %.
Systematic capability SIL 3.
2 fully independent channels (only for D5093D-TB).
Installation in Zone 2 / Safe Area.
Input/Output and Channel/Channel isolation.
EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system.
ATEX, IECEx, UL & C-UL, EAC Ex, UKR TR n. 898, TÜV Certifications.
TÜV Functional Safety Certification
High Density, two channels per unit (D5093D-TB).
Simplified installation on customized Termination Boards.
24 to 220 Vac/Vdc Input Ch1
Terminal block connections
24 to 220 Vac/Vdc Input Ch2 (only for D5093D-TB)
7
8
9
10
Model: D5093
1 channel
S
2 channels
D
-TB
9
10
7
8
SIL 3
D5093
-TB
2
1
STS
STS
7 8
9 10