D5091-103
- SIL3 Relay Out Module for 5 A ND Loads
G.M. International ISM0457-1
2
Technical Data
Characteristics
Isolation (test voltage):
In/Outs 2.5 kV.
Input:
24 Vdc nom (20 to 28.8 Vdc), reverse polarity protected. Relay coils are internally protected with suppressor diodes.
Current consumption:
30 mA @ 24 Vdc, typical.
Power dissipation:
0.72 W @ 24 Vdc, typical.
Output:
1 Voltage free SPDT relay contact. Terminals 7-8, open when relay de-energized, close in energized condition. Terminals 9-10, close when relay de-energized, open in
energized condition.
Contact material:
Ag Alloy (Cd free), gold plated.
Contact rating:
5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W (resistive load), 1 A 24 Vdc, 220 mA 125 Vdc, 110 mA 250 Vdc for UL.
Contact min. switching current:
1 mA.
Contact inrush current:
6 A @ 24 Vdc, 250 Vac.
DC and AC load breaking capacity:
Mechanical / electrical life:
5 * 10
⁶
/ 3 * 10
⁴
operation, typical.
Operate / release time:
55 / 30 ms, typical.
Bounce time NO / NC contact:
3 / 8 ms, typical.
Frequency response:
10 Hz maximum.
Compatibility:
CE mark compliant, conforms to Directive: 2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS.
Environmental conditions:
Operating temperature:
temperature limits -40 to +70 °C.
Operating relative humidity:
relative humidity 95 %, up to 55 °C.
Max altitude:
2000 m a.s.l.
Storage temperature:
temperature limits -45 to +80 °C.
Safety description:
ATEX:
II 3G Ex nA nC IIC T4 Gc
IECEx:
Ex nA nC IIC T4 Gc
UL:
NI / I / 2 / ABCD / T4
C-UL:
NI / I / 2 / ABCD / T4
non-sparking electrical equipment.
-40 °C
≤
Ta
≤
70 °C.
Approvals:
BVS 10 ATEX E 114 conforms to EN60079-0, EN60079-15.
IECEx BVS 10.0072 X conforms to IEC60079-0, IEC60079-15.
UL & C-UL E222308 conforms to UL 61010-1, UL 121201 for UL
and CAN/CSA C22.2 No. 61010-1-12, CSA C22.2 No. 213-17 for C-UL.
TUV Certificate No. C-IS-272994-01 SIL 3 conforms to IEC61508:2010 Ed. 2.
TÜV Certificate No. C-IS-236198-09, SIL 3 Functional Safety Certificate conforms to IEC61508:2010 Ed.2, for Management of Functional Safety.
Mounting:
EN/IEC60715 TH 35 DIN-Rail or on customized Termination Board.
Weight:
about 125 g.
Connection:
by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG).
Location:
installation in Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4 or Class I, Division 2, Group A,B,C,D, T4 or Class I, Zone 2, Group IIC, T4.
Protection class:
IP 20.
Dimensions:
Width 12.5 mm, Depth 123 mm, Height 120 mm.
General Description:
The D5090-103 is a relay module suitable for switching safety related circuits, up to SIL 3 level, for high risk industries. It provides isolation between input and output contacts. It makes
available two NO contacts for Normally Energized (NE) loads, in order to disconnect the load on both supply lines, and a NC contact for service purpose. This model is specifically
designed to reach high functional safety at minimum power consumption.
Compatibility with specific DO cards with pulse testing needs to be verified.
Mounting on standard DIN-Rail or on customized Termination Boards, in Safe Area / Non Hazardous Location or in Zone 2 / Class I, Division 2.
Functional Safety Management Certification:
G.M. International is certified by TUV to conform to IEC61508:2010
part 1 clauses 5-6 for safety related systems up to and included SIL3.
FSM
SIL 3
0.2
0.0
V (V)
I (A)
10
20
30
40
50
100
0.3 0.4 0.5
1
2
3
Resistive
Load
200
4
300
250
0.1
5
6
DC
resistive
AC
Resistive