background image

 

D5091-103 

- SIL3 Relay Out Module for 5 A ND Loads 

G.M. International ISM0457-1 

 

 

 

Technical Data 

Characteristics 

Isolation (test voltage):

 In/Outs 2.5 kV. 

Input:

 24 Vdc nom (20 to 28.8 Vdc), reverse polarity protected. Relay coils are internally protected with suppressor diodes. 

Current consumption:

 30 mA @ 24 Vdc, typical. 

Power dissipation:

 0.72 W @ 24 Vdc, typical. 

Output:

 1 Voltage free SPDT relay contact. Terminals 7-8, open when relay de-energized, close in energized condition. Terminals 9-10, close when relay de-energized, open in 

energized condition. 

Contact material:

 Ag Alloy (Cd free), gold plated. 

Contact rating:

 5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W (resistive load), 1 A 24 Vdc, 220 mA 125 Vdc, 110 mA 250 Vdc for UL. 

Contact min. switching current:

 1 mA. 

Contact inrush current:

 6 A @ 24 Vdc, 250 Vac. 

DC and AC load breaking capacity:

 

Mechanical / electrical life:

 5 * 10

 / 3 * 10

 operation, typical. 

Operate / release time:

 55 / 30 ms, typical. 

Bounce time NO / NC contact:

 3 / 8 ms, typical. 

Frequency response:

 10 Hz maximum. 

Compatibility:

 

CE mark compliant, conforms to Directive: 2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS. 

 

Environmental conditions:

 

Operating temperature:

 temperature limits -40 to +70 °C. 

Operating relative humidity:

 relative humidity 95 %, up to 55 °C. 

Max altitude:

 2000 m a.s.l. 

Storage temperature:

 temperature limits -45 to +80 °C. 

Safety description:

 

ATEX:

 II 3G Ex nA nC IIC T4 Gc 

IECEx:

 Ex nA nC IIC T4 Gc 

UL:

 NI / I / 2 / ABCD / T4 

C-UL:

 NI / I / 2 / ABCD / T4 

non-sparking electrical equipment. 
-40 °C 

 Ta 

 70 °C. 

Approvals:

 

BVS 10 ATEX E 114 conforms to EN60079-0, EN60079-15. 
IECEx BVS 10.0072 X conforms to IEC60079-0, IEC60079-15. 
UL & C-UL E222308 conforms to UL 61010-1, UL 121201 for UL 
and CAN/CSA C22.2 No. 61010-1-12, CSA C22.2 No. 213-17 for C-UL. 
TUV Certificate No. C-IS-272994-01 SIL 3 conforms to IEC61508:2010 Ed. 2. 
TÜV Certificate No. C-IS-236198-09, SIL 3 Functional Safety Certificate conforms to IEC61508:2010 Ed.2, for Management of Functional Safety. 

Mounting:

 EN/IEC60715 TH 35 DIN-Rail or on customized Termination Board. 

Weight:

 about 125 g. 

Connection:

 by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG). 

Location:

 installation in Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4 or Class I, Division 2, Group A,B,C,D, T4 or Class I, Zone 2, Group IIC, T4. 

Protection class:

 IP 20. 

Dimensions:

 Width 12.5 mm, Depth 123 mm, Height 120 mm. 

General Description: 

The D5090-103 is a relay module suitable for switching safety related circuits, up to SIL 3 level, for high risk industries. It provides isolation between input and output contacts. It makes 
available two NO contacts for Normally Energized (NE) loads, in order to disconnect the load on both supply lines, and a NC contact for service purpose. This model is specifically 
designed to reach high functional safety at minimum power consumption. 

  Compatibility with specific DO cards with pulse testing needs to be verified. 

Mounting on standard DIN-Rail or on customized Termination Boards, in Safe Area / Non Hazardous Location or in Zone 2 / Class I, Division 2. 

   

Functional Safety Management Certification: 

G.M. International is certified by TUV to conform to IEC61508:2010  
part 1 clauses 5-6 for safety related systems up to and included SIL3. 

FSM

SIL 3

0.2

0.0

V (V)

I (A)

10

20

30

40

50

100

0.3 0.4 0.5

1

2

3

Resistive

Load

200

4

300
250

0.1

5

6

DC

resistive

AC

Resistive

Summary of Contents for D5091S-103

Page 1: ...D5091 103 SIL3 Relay Out Module for 5 A ND Loads G M International ISM0457 1 SIL3 Relay Out Module for 5 A ND Loads DIN Rail and Termination Board Model D5091S 103 D5091S 103 INSTRUCTION MANUAL ...

Page 2: ...s to IEC60079 0 IEC60079 15 UL C UL E222308 conforms to UL 61010 1 UL 121201 for UL and CAN CSA C22 2 No 61010 1 12 CSA C22 2 No 213 17 for C UL TUV Certificate No C IS 272994 01 SIL 3 conforms to IEC61508 2010 Ed 2 TÜV Certificate No C IS 236198 09 SIL 3 Functional Safety Certificate conforms to IEC61508 2010 Ed 2 for Management of Functional Safety Mounting EN IEC60715 TH 35 DIN Rail or on custo...

Page 3: ...tal SIF for ND load with NE relay terminals 9 10 SIL 3 high demand mode of operation according to IEC 61508 2010 SC 3 Systematic Capability SIL 3 Installation in Zone 2 Div 2 Up to 5 A functional 6 A inrush current Low current consumption Service contact available Input Output isolation Model D5091S 103 Power Bus and DIN Rail accessories DIN Rail stopper MCHP196 Terminal block connections SPDT Out...

Page 4: ...CATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 To prevent relay contacts from damaging connect an external protection fuse or similar chosen according to the relay breaking capacity diagram MODEL D5091S 103 In 7 8 9 10 1 2 Termination board connector SIL3 SPDT Out ND Load 7 8 or 9 10 All relay contacts are shown in de energized position ...

Page 5: ...hen installed in EU Zone 2 the unit shall be mounted in a certified Ex enclosure that provides a degree of protection not less than IP54 in accordance with EN IEC60079 15 When installed in a Class I Division 2 Hazardous Location the unit shall be mounted in a supplemental enclosure that provides a degree of protection not less than IP54 The enclosure must have a door or cover accessible only by th...

Reviews: