D5072-096 

- SIL 2 Thermocouple/mV Repeater 

G.M. International ISM0388-4 

When used with separately powered intrinsically safe devices, check that maximum allowable voltage, current (Ui/Vmax, Ii/Imax) of the D5072-096 Associated Apparatus are not 
exceeded by the safety parameters (Uo/Voc, Io/Isc) of the Intrinsically Safe device, indicated in the table below: 

For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 % of the Co and Lo parameters of the Associated Apparatus (excluding the cable), 
then 50 % of Co and Lo parameters are applicable and shall not be exceeded 

(50 % of the Co and Lo become the limits which must include the cable such that Ci C cable 

 50 % of Co and Li  L cable 

 50 % of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 

μ

F for Groups I, IIA, IIB and 600 nF for 

Group IIC. 
If the cable parameters are unknown, the following value may be used: Capacitance 200 pF per meter (60 pF per foot), Inductance 1 µH per meter (0.20 µH per foot). 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Device Parameters 

D5072-096 Associated 

Apparatus Parameters 

Ui / Vmax = 12.8 V 

Uo / Voc 

D5072-096 

Terminals 

 

Ci = 0 nF, Li= 0 nH 

Function Diagram 

HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC, 

HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D, 

CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1, 

CLASS I, ZONE 0, GROUP IIC 

SAFE AREA, ZONE 2 GROUP IIC T4, 

NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2, 

GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4 

 

 

Ch1 

7 - 8 

D5072S-096 

Ch1 
Ch2 

7 - 8 

11 - 12 

D5072D-096 

Ch1 

7 - 8 

D5072S-096 

Ch1 
Ch2 

7 - 8 

11 - 12 

D5072D-096 

=

=

=

5 +

6 -

1 +

2 -

3 +

4 -

7

12

MODEL D5072D-096

=

=

=

=

mV Out 1 (SIL 2)

11

8

+

-

F

Power and

Fault Bus

Supply 24 Vdc

mV Out 2 (SIL 2)

=

=

=

In 1

In 2

+

-

TC / mV

+

-

TC / mV

=

=

=

5 +

6 -

1 +

2 -

3 +

4 -

7

MODEL D5072D-096 (Duplicator)

=

=

mV Out 1-A (SIL 2)

8

+

-

F

Power and

Fault Bus

Supply 24 Vdc

mV Out 1-B (SIL 2)

=

=

=

In 1

+

-

TC / mV

Summary of Contents for D5072S-096

Page 1: ...D5072 096 SIL 2 Thermocouple mV Repeater G M International ISM0388 4 SIL 2 Thermocouple mV Repeater DIN Rail Models D5072S 096 D5072D 096 D5072S 096 D5072D 096 INSTRUCTION MANUAL...

Page 2: ...relative humidity 95 up to 55 C Storage temperature limits 45 to 80 C Max altitude 2000 m a s l Safety Description ATEX II 3 1 G Ex ec ia Ga IIC T4 Gc II 1 D Ex ia Da IIIC I M1 Ex ia Ma I IECEx INMETR...

Page 3: ...o channels per unit Simplified installation using standard DIN Rail and plug in terminal blocks with or without Power Bus 250 Vrms Um max voltage allowed to the instruments associated with the barrier...

Page 4: ...or the effective group See parameters indicated in the table below D5072 096 Terminals Ch1 7 8 D5072S 096 Ch1 Ch2 7 8 11 12 Io Isc 23 mA Io Isc 16 mA Po Po 40 mW Po Po 27 mW Ii Imax Pi Pi D5072 096 Te...

Page 5: ...Groups I IIA IIB and 600 nF for Group IIC If the cable parameters are unknown the following value may be used Capacitance 200 pF per meter 60 pF per foot Inductance 1 H per meter 0 20 H per foot Must...

Page 6: ...fore servicing Connect only one individual conductor per each clamping point use conductors up to 2 5 mm 13 AWG and a torque value of 0 5 0 6 Nm Use only cables that are suitable for a temperature of...

Page 7: ...38 to 1832 270 to 1000 454 to 1832 0 050 0 090 J IEC 60584 GOST 8 585 ASTM E230 50 90 0 2 0 4 150 to 1200 238 to 2192 210 to 1200 346 to 2192 0 050 0 090 K IEC 60584 GOST 8 585 ASTM E230 50 90 0 3 0 5...