D5038 

- I.S. SIL3 Line-Fault Transp. Switch/Prox. Repeater 

G.M. International ISM0427-1 

Parameters Table 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Device Parameters 

D5038 Associated 

Apparatus Parameters 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Cable Parameters 

Uo / Voc = 10.5 V 

Ui / Vmax 

In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check 
its suitability for the Hazardous Area/Hazardous Locations and group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded 
by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5038 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, 
check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the 
effective group. See parameters indicated in the table below: 

D5038 Terminals 

Ch1 

7 - 8 

 

D5038 Terminals 

D5038 Associated Apparatus 

Parameters Cenelec (US) 

Ci / Ci  C cable 

 

IIC (A, B) 

Co / Ca = 2.4 µF 

 

Ch1 

7 - 8 

Ch2 

9 - 10 

Io / Isc = 22 mA 

Ii / Imax 

Ch1 

7 - 8 

 

Ch2 

9 - 10 

Io / Isc = 56 mW 

Pi / Pi 

Ch1 

7 - 8 

 

Ch2 

9 - 10 

IIB (C) 

Co / Ca = 16.7 µF 

IIA (D) 

Co / Ca = 74.9 µF 

Co / Ca = 94.9 µF 

IIIC (E, F, G) 

Co / Ca = 16.7 µF 

Ch2 

9 - 10 

Li / Li L cable 

 

IIC (A, B) 

Lo / La = 78.3 mH 

Ch1 

7 - 8 

IIB (C) 

Lo / La = 313.5 mH 

IIA (D) 

Lo / La = 627.1 mH 

Lo / La = 1028.8 mH 

IIIC (E, F, G) 

Lo / La = 313.5 mH 

Ch2 

9 - 10 

Li / Ri device and 

L cable / R cable 

 

IIC (A, B) 

Lo / Ro = 635 µH/

 

Ch1 

7 - 8 

IIB (C) 

Lo / Ro = 2543 µH/

 

IIA (D) 

Lo / Ro = 5087 µH/

 

Lo / Ro = 8347 µH/

 

IIIC (E, F, G) 

Lo / Ro = 2543 µH/

 

Ch2 

9 - 10 

For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 % of the Co and Lo parameters of the Associated Apparatus (excluding the cable), 
then 50 % of Co and Lo parameters are applicable and shall not be exceeded 

(50 % of the Co and Lo become the limits which must include the cable such that Ci C cable 

 50 % of Co and Li  L cable 

 50 % of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 

μ

F for Groups I, IIA, IIB and 600 nF for 

Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 180pF per meter (60pF per foot), Inductance 0.60µH per meter (0.20µH per foot). 

Summary of Contents for D5038S Series

Page 1: ...Line Fault Transp Switch Prox Repeater G M International ISM0427 1 I S SIL3 Line Fault Transp Switch Prox Repeater DIN Rail and Termination Board Models D5038S D5038D D5038X D5038S D5038D D5038X INST...

Page 2: ...ximum Compatibility CE mark compliant conforms to Directives 2014 34 EU ATEX 2014 30 EU EMC 2014 35 EU LVD 2011 65 EU RoHS Environmental conditions Operating temperature limits 40 to 70 C relative hum...

Page 3: ...e monitoring transparency In field programmability by DIP Switch Three port isolation Input Output Supply High Density two channels per unit Input Ch 1 for proximity or voltage free contact Terminal b...

Page 4: ...nals Ch1 7 8 D5038 Terminals D5038 Associated Apparatus Parameters Cenelec US Ci Ci device C cable IIC A B Co Ca 2 4 F Ch1 7 8 Ch2 9 10 Io Isc 22 mA Ii Imax Ch1 7 8 Ch2 9 10 Io Isc 56 mW Pi Pi Ch1 7 8...

Page 5: ...2 Out 1 SIL 3 In 1 Proximity voltage free Contact 7 8 Power and Fault Bus F Supply 24 Vdc voltage free Contact R1 R2 RH RL RL Termination board connector MODEL D5038D 5 6 1 2 Out 1 SIL 3 10 In 1 Prox...

Page 6: ...locks which can be plugged in out into a powered unit without suffering or causing any damage for Zone 2 installations check the area to be nonhazardous before servicing Connect only one individual co...

Page 7: ...fault detection Dip switch factory settings Switches 1 and 3 are ON switches 2 and 4 are OFF 1 2 3 4 ON ON OFF ON OFF CH1 CH2 OFF 1 CH1 Enabled proximity sensor or switch with end of line resistors o...

Reviews: