background image

 

D5038 

- I.S. SIL3 Line-Fault Transp. Switch/Prox. Repeater 

G.M. International ISM0427-1 

General Description:

 

The Switch/Proximity Detector Repeater D5038 is a module suitable for applications requiring SIL 3 level in safety related systems for high risk industries. The unit can be configured 
for switches or proximity detectors, located in Hazardous Area, and repeats the input state to the output in Safe Area. The output port can assume two different impedance values (RL 
or RH) or it can open completely. The module output repeats the input state according to the following correspondence: low input state -> RL, high input state -> RH. Alternatively, the 
output can be configured to invert the input state. In both cases, the output opens if any fault (open or short circuit) occurs at the corresponding input. 

 

Functional Safety Management Certification: 

G.M. International is certified by TUV to conform to IEC61508:2010  
part 1 clauses 5-6 for safety related systems up to and included SIL3. 

 

 

 

Technical Data 

Characteristics 

Supply: 

24 Vdc nom (18 to 30 Vdc), reverse polarity protected. 

Current consumption:

 30 mA (D5038D), 25 mA (D5038X), 15 mA (D5038S), @ 24 Vdc, typical. 

Power dissipation:

 1.0 W (D5038D), 1.0 W (D5038X), 0.4 W (D5038S), @ 24 Vdc, typical. 

Isolation (test voltage): 

I.S. In/Out 1.5 kV; I.S. In/Supply 1.5 kV; I.S. In/ I.S In 500 V; Out/Supply 500 V; Out/Out 500 V. 

Input: 

Input switching current levels:

 ON 

 2.1 mA, OFF 

 1.2 mA. 

Open fault:

 current 

 0.05 mA. 

Short fault:

 resistance 

 100 

No fault:

 current 

 0.35 mA and resistance 

 360 

Input equivalent source:

 8 V 1 k

 typical (8 V no load, 8 mA short). 

Output: 

Voltage free SPST solid-state relays, with series (RL) and parallel (RH-RL) resistances, ±5% tolerance. 

Fault impedance:

 > 1 M

Max voltage:

 30 Vdc. 

Max current:

 15 mA. 

Response time:

 500 

μ

s. 

Frequency response:

 1 kHz maximum. 

Compatibility: 

CE mark compliant, conforms to Directives:  
2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS. 

Environmental conditions: 

Operating:

 temperature limits – 40 to + 70 °C, relative humidity 95 %, up to 55 °C. 

Max altitude:

 2000 m a.s.l. 

Storage:

 temperature limits – 45 to + 80 °C. 

Safety description: 

ATEX:

 II 3(1)G Ex ec [ia Ga] IIC T4 Gc; II (1)D [Ex ia Da] IIIC; I (M1) [Ex ia Ma] I 

IECEx:

 Ex ec [ia Ga] IIC T4 Gc; [Ex ia Da] IIIC; [Ex ia Ma] I 

UL:

 NI / I / 2 / ABCD / T4, AIS / I, II, III / 1 / ABCDEFG, AEx nA [ia Ga] IIC T4 Gc; 

C-UL:

 NI / I / 2 / ABCD / T4, AIS / I, II, III / 1 / ABCDEFG, Ex nA [ia Ga] IIC T4 Gc X 

associated apparatus and non-sparking electrical equipment. 
Uo/Voc = 10.5 V, Io/Isc = 22 mA, Po/Po = 56 mW at terminals 7-8, 9-10 
Um = 250 Vrms or Vdc, -40 °C 

 Ta 

 70 °C. 

Approvals: 

DEMKO 19 ATEX 2290X conforms to EN60079-0, EN60079-11, EN60079-7. 
IECEx ULD 19.0029X conforms to IEC60079-0, IEC60079-11, IEC60079-7. 
UL & C-UL E222308 conforms to UL 61010-1, UL913, UL 60079-0, UL60079-11, UL60079-15, UL121201 for UL 
and CAN/CSA C22.2 No. 61010-1-12, CSA-E60079-0, CSA-E60079-11, CSA-E60079-15 and CSA-C22.2 No. 213 for C-UL. 
TUV Certificate No. C-IS-272994-01  SIL 3 conforms to IEC61508:2010 Ed. 2. 
TÜV Certificate No. C-IS-236198-09, SIL 3 Functional Safety Certificate conforms to IEC61508:2010 Ed.2, for Management of Functional Safety. 

Mounting: 

EN/IEC60715 TH 35 DIN-Rail, with or without Power Bus or on customized Termination Board. 

Weight:

 about 135 g (D5038D and D5038X), 120 g (D5038S). 

Connection:

 by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG). 

Location:

 installation in Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4 or Class I, Division 2, Group A,B,C,D, T4 or Class I, Zone 2, Group IIC, T4. 

Protection class:

 IP 20. 

Dimensions:

 Width 12.5 mm, Depth 123 mm, Height 120 mm. 

FSM

SIL 3

Ordering Information 

 

 

Model:  

D5038 

1 channel 

2 channels 

Power Bus and DIN-Rail accessories: 
Bus connector JDFT049 

 

Bus mounting kit OPT5096 

duplicator 

RL = 2.2k

, RH = 14.3k

 

RL = 476

, RH = 1.38k

 

Summary of Contents for D5038S Series

Page 1: ...Line Fault Transp Switch Prox Repeater G M International ISM0427 1 I S SIL3 Line Fault Transp Switch Prox Repeater DIN Rail and Termination Board Models D5038S D5038D D5038X D5038S D5038D D5038X INST...

Page 2: ...ximum Compatibility CE mark compliant conforms to Directives 2014 34 EU ATEX 2014 30 EU EMC 2014 35 EU LVD 2011 65 EU RoHS Environmental conditions Operating temperature limits 40 to 70 C relative hum...

Page 3: ...e monitoring transparency In field programmability by DIP Switch Three port isolation Input Output Supply High Density two channels per unit Input Ch 1 for proximity or voltage free contact Terminal b...

Page 4: ...nals Ch1 7 8 D5038 Terminals D5038 Associated Apparatus Parameters Cenelec US Ci Ci device C cable IIC A B Co Ca 2 4 F Ch1 7 8 Ch2 9 10 Io Isc 22 mA Ii Imax Ch1 7 8 Ch2 9 10 Io Isc 56 mW Pi Pi Ch1 7 8...

Page 5: ...2 Out 1 SIL 3 In 1 Proximity voltage free Contact 7 8 Power and Fault Bus F Supply 24 Vdc voltage free Contact R1 R2 RH RL RL Termination board connector MODEL D5038D 5 6 1 2 Out 1 SIL 3 10 In 1 Prox...

Page 6: ...locks which can be plugged in out into a powered unit without suffering or causing any damage for Zone 2 installations check the area to be nonhazardous before servicing Connect only one individual co...

Page 7: ...fault detection Dip switch factory settings Switches 1 and 3 are ON switches 2 and 4 are OFF 1 2 3 4 ON ON OFF ON OFF CH1 CH2 OFF 1 CH1 Enabled proximity sensor or switch with end of line resistors o...

Reviews: