GMDE GEatom 315/318KTL
Global Mainstream Dynamic Energy Technology Ltd.
40
Warning Message
Explanation
Action
Offset-Iac-Warning
The DC injection of grid current
is out of range.
Acknowledge error. Contact the service if the
error occurs repeatedly.
ENS-Mess-Warning
Different value between master
and slave CPU.
Wait until the controller has re-stabilized.
Curr-Sensor-
Warning
The current sensor is abnormal.
Wait until the controller has re-stabilized.
Inverter-Curr-
Warning
Inverter current is over the
tolerable value.
Acknowledge error.
Rly-Warning
Relay is Fail.
Wait until the controller has re-stabilized.
Vac-Master-
Warning
Master-grid voltage
measurement-value out of
tolerable range.
Re-measure line voltage Service if line voltage
is within normal range.
Fac-Master-
Warning
The master-frequency is out of
tolerable range.
Check system frequency and line voltage.
Service if system frequency is within normal
range.
No-Utility
Grid voltage =0.
Re-measure line voltage Service if line voltage
is within normal range.
Battery Voltage high
Warning
DC input voltage is over the
tolerable maximum value.
Check voltage of battery packs Contact the
service if the error occurs repeatedly.
Master-Slave-
Warning
Communication between
microcontrollers is failing.
Acknowledge error. Contact the service if the
error occurs repeatedly.
Temperature-
Warning
The internal temperature is out
of tolerable value.
Allow the unit to cool down. Acknowledge
error.
ENS-Vac-Warning
Different value between master
and slave for grid voltage.
Possibly caused by switching actions on the
net. Re-measure line voltage. Service if line
voltage is within normal range.
ENS-DCI-Warning
Different value between master
and slave for output AC
current.
Wait until the controller has re-stabilized.