background image

 

PSD1206

 

- PSD1210 

- SIL 3 - SIL 2 Switching Power Supply 24 Vdc 

G.M. International ISM0076-7 

• 

DC

: Diagnostic coverage (safe or dangerous) of the safety logic solver for the considered module. 

• 

DCs

: Diagnostic coverage for safe failures = 

λ

sd / (

λ

sd + 

λ

su). 

• 

DCd

: Diagnostic coverage for dangerous failures = 

λ

dd / (

λ

dd + 

λ

du). 

• 

FIT

: Failure In Time (1x10 E-9 failures per hour). 

• 

Failure Rates

: The failure rate data used in the FMEDA analysis are the basic failure rates from the Siemens SN 29500 failure rate database. The rates where chosen in a way 

that is appropriate for safety integrity level verification calculations, and to mach operating stress conditions typical of an industrial field environment similar to IEC 60654-1, 
class C. It is expected that the actual number of field failures will be less than the number predicted by these failure rates. 

• 

FMEA

: Failure Modes and Effects Analysis is a systematic way to identify and evaluate the effects of different component failure modes, to determine what could eliminate or 

reduce the chance of failure, and to document the system in consideration. 

• 

FMEDA

: Failure Modes Effects and Diagnostic Analysis is an FMEA extension. It combines standard FMEA techniques with extension to identify online diagnostics techniques 

and the failure mode relevant to safety instrumented system design. It is a technique recommended to generate failure rates for each important category (safe detected, safe 
undetected, dangerous detected, dangerous undetected, fail high, fail low) in the safety modules. The format for the FMEDA is an extension of the FMEA format MIL STD 1629A. 

• 

Low demand mode

: Mode where the frequency of demands for operation made on Safety-related system is no greater than one per year and no greater than twice the proof test 

frequency. 

• 

MTBF

: Mean Time Between Failure. 

• 

MTTF

: Mean Time To Failure. 

• 

MTTF

S

: Mean Time To safe Failure. 

• 

MTTF

D

: Mean Time To dangerous Failure. 

• 

MTTR

: Mean Time To Repair. 

• 

PFDavg

: Average Probability of Failure on Demand. 

• 

SFF

: Safe Failure Fraction, according IEC 61508 summarizes the fraction of failures, which lead to a safe state and the fraction of failures which will be detected by diagnostic 

measures and lead to a defined safety action.

 

General Terms 

 

 

 

SU

SD

DU

DD

DU

SU

SD

DU

DD

SU

SD

DD

SFF

λ

λ

λ

λ

λ

λ

λ

λ

λ

λ

λ

λ

+

+

+

=

+

+

+

+

+

=

1

with: 

λ

DD: Dangerous Detected failure rate;  

λ

DU: Dangerous Undetected failure rate 

 

λ

SD: Safe Detected failure rate; 

 

λ

SU: Safe Undetected failure rate 

 

• 

SIF

: Safety Instrumented Function. 

• 

SIS

: Safety Instrumented System. 

• 

SIL

: Safety Integrity Level. 

• 

T Proof Test & Maintenance (TI)

: Proof Test Interval (for example 1 - 5 - 10 years, with 1 year = 8760 hours). Maintenance time is considered 8 hours. 

The following assumptions have been made during the Failure Modes, Effects, and Diagnostic Analysis of the Switching Power Supply Types PSD1206 and PSD1210. 

• 

Failure rates are constant, wear out mechanisms are not included. 

• 

Propagation of failures is not relevant. 

• 

Failures during parameterization are not considered. 

• 

Sufficient test are performed prior to shipment to verify the absence of component supplier and/or manufacturing defects that prevent proper operation of specified functionality to 
product specifications or cause operation different from design analyzed. 

• 

The device is operated in the low demand mode of operation. 

• 

The time to restoration or repair time after a safe failure is 8 hours, as MTTR. 

• 

Only the described versions are used for safety applications. 

• 

Practical fault insertion tests can demonstrate the correctness of the failure effects assumed during the FMEDAs. 

• 

The fault output is not part of the safety function. 

• 

The common cause factor 

β

 between the two crowbars is estimated at be 5 %. 

• 

The stress levels are average for an industrial environment and the assumed environment is similar to IEC 60654-1, Class C (Sheltered location) with temperature limits within the 
manufacturer’s rating and an average temperature over a long period of time of 40 °C. Humidity levels are assumed within manufacturer’s rating. 

• 

The listed failure rates are valid for operating stress conditions typical of an industrial field environment similar to IEC 60654-1 class C with an average temperature over a long 
period of time of 40 °C. For a higher average temperature of 60 °C, the failure rates should be multiplied with an experience based factor of 2.5. A similar multiplier should be 
used if frequent temperature fluctuation must be assumed. 

• 

Over voltage protection has a diagnostic coverage of 99 %. 

• 

Safety Integrity Levels as defined in IEC 61508 and IEC 61511: 

Assumptions 

 

SIL 

Safety Integrity Level 

SIL 4 

SIL 3 

SIL 2 

SIL 1 

PFDavg 

Average probability of failure 

on demand per year 

(low demand) 

 10-5 to < 10-4 

 10-4 to < 10-3 

 10-3 to < 10-2 

 10-2 to < 10-1 

RRF 

Risk Reduction Factor 

From 100000 to 10000 

From 10000 to 1000 

From 1000 to 100 

From 100 to 10 

PFDavg 

Average probability of dangerous 

failure on demand per hour 

(high demand) 

 10-9 to < 10-8 

 10-8 to < 10-7 

 10-7 to < 10-6 

 10-6 to < 10-5 

Summary of Contents for PSD1206

Page 1: ...0076 7 PSD1206 PSD1210 INSTRUCTION MANUAL INSTRUCTION MANUAL SIL 3 SIL 2 Switching Power Supply 24Vdc 10A 250W Output Zone 2 Div 2 DIN Rail Mounting Model PSD1210 SIL 3 SIL 2 Switching Power Supply 24Vdc 6A 150W Output Zone 2 Div 2 DIN Rail Mounting Model PSD1206 ...

Page 2: ...e event and continue to operate without interruption Refer to instruction manual ISM0076 for a detailed diagram of the output current PSD1206 Switching Power Supply 24 Vdc 6A Output PSD1210 Switching Power Supply 24 Vdc 10A Output Characteristics 2 Technical Data 2 Ordering Information 3 Features 3 Function Diagram 3 Warning 4 Storage 4 Disposal 4 Operation 5 Installation 5 Start up 6 High load fu...

Page 3: ...Class I Zone 2 Group IIC IIB IIA T3 installation Protection class IP 20 Dimensions PSD1206 width 200 mm height 95 mm depth 110 mm Features SIL 3 according to IEC 61508 for Tproof 3 6 years 10 20 of total SIF two units in parallel with NE Load SIL 2 according to IEC 61508 for Tproof 9 10 years 10 20 of total SIF two units in parallel with ND Load SIL 2 according to IEC 61508 for Tproof 1 3 years 10...

Page 4: ...re The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative any unauthorized modification must be avoided Warning PSD1206 PSD1210 Power Supply FM Approved under non incendive field wiring Unclassified Locations or Hazardous Classified Locations Class I Division 2 Groups A B C D T Code T3 Class I Zone 2 Group IIC IIB IIA T Code T3 Hazardo...

Page 5: ...wly rotate until the LED turn off in this way you set the threshold value at 26 3 V Finally rotate the Vout Adjust trimmer until the output voltage has reached the new requested value of 25 V Installation The terminal block are not usable as breaking device according to EN60950 The wiring cables have to be proportionate in base to the current and the length of the cable For PSD1206 typical cable s...

Page 6: ...d particularly their polarity Check conductors for exposed wires that could touch each other causing dangerous unwanted shorts Turn on power the power on green led must be lit check the supply voltage generated by PSD1206 PSD1210 is 24 Vdc High load fuse breaking capacity Figure below shows the current waveform through the short circuit connection 1 The peak short circuit current is about 430 A 2 ...

Page 7: ...tic 79 with diagnostic 112 with diagnostic In order to judge the failure behavior of the considered modules the following definitions for the failure of the product must be considered Fail Safe State The fail safe state is defined as the output reaching the user defined threshold In normally energized NE loads is defined as the output being between 20 V and 30 V load current up to 80 of rated or l...

Page 8: ...ected failure rate λSU Safe Undetected failure rate SIF Safety Instrumented Function SIS Safety Instrumented System SIL Safety Integrity Level T Proof Test Maintenance TI Proof Test Interval for example 1 5 10 years with 1 year 8760 hours Maintenance time is considered 8 hours The following assumptions have been made during the Failure Modes Effects and Diagnostic Analysis of the Switching Power S...

Page 9: ...0 Λsd 0 00 FIT λsu 542 20 FIT λdd 0 00 FIT λdu 134 80 FIT SFF 80 09 PFDavg vs T Proof with determination of SIL supposing module contributes 10 of entire safety function T Proof 1 year PFDavg 5 90 E 04 Valid for SIL 2 See Note 2 in the section Notes T Proof 3 years PFDavg 1 77 E 03 See Note 3 and Note 4 In the section Notes T Proof 6 years PFDavg 3 54 E 03 See Note 3 and Note 4 In the section Note...

Page 10: ...f Total Fail Ann Undet Total Fail Safe Undetected λsu Fail High 99 of Total Fail High Fail Low Fail Annunciation Undetected 99 of Total Fail Ann Undet Fail Not Part λnotpart MTBF MTTF MTTR 1 λsd λsu λdd λdu λnotpart MTTR MTTFS 1 λsd λsu 349 80 134 00 0 21 0 59 327 20 20 79 215 00 58 41 174 00 134 years 349 years Fail No Effect 214 00 Total Fail Dangerous Detected λdd 0 00 Total Fail Safe Detected ...

Page 11: ...for SIL 2 See Note 2 in the section Notes T Proof 5 years PFDavg 4 65 E 04 Valid for SIL 2 See Note 2 in the section Notes T Proof 9 years PFDavg 9 40 E 04 Valid for SIL 2 See Note 2 in the section Notes T Proof 10 years PFDavg 1 10 E 03 See Note 3 and Note 4 in the section Notes In following table it s reported the _System AVG TI x years PFD with determination of SIL supposing module contibutes 2...

Page 12: ... be 1 00 E 02 This limit is satisfied from the calculated PFDavg value therefore the module is valid for SIL 1 application Note 5 Considering a SIL 1 application the total PFDavg value of the SIF must be 1 00 E 01 according to table 2 of IEC 61508 1 and table 3 1 of ANSI ISA 84 01 1996 However as the module under consideration contributes for only 10 of the entire SIF the PFDavg value of the modul...

Page 13: ...IL 3 with T proof 6 years or SIL 2 with T proof 10 years For ND load c SIL 2 with T proof 9 years or SIL 1 with T proof 10 years d SIL 2 with T proof 10 years During T proof of each power supply unit the power supply system can sustain the maximum load current but SIL value changes from SIL 3 to SIL 2 for NE load or from SIL 2 to SIL 1 for ND load because redundancy N 2 is absent For NE load a SIL...

Page 14: ...t 1 Current sharing capability Proof test 2 Paralleling diode operation Proof test 3 Crowbar A operation Proof test 4 Crowbar B operation Proof test 5 Over voltage protection Possible Proof Tests to reveal Dangerous Undetected Faults Ammeter range 0 to 10 A 0 1 A resolution or better 300 W variable resistor load from 2 to 25 Ω current up to 10 A to test PSD1210 or 150 W variable resistor load from...

Page 15: ...pply voltage V2 by rotating its Vout Adjust trimmer clockwise until obtaining 24 6 V 3 Verify that output current A3 is at 75 of full load and that output current A2 is instead at 25 4 Re connect current sharing connection and verify that voltage are approximately the same V1 V2 5 Verify that output current A3 is about 60 of full load and that output current A2 is instead about 40 6 Regulate the s...

Page 16: ...g and check that voltage drop is between 0 3V and 0 7V 3 Turn on the second PS 4 Turn off the PS under test 5 Check that voltage V2 between the diodes is between 22 V and 26 V 6 Paralleling diode operation Connect the two power supplies as shown in the following image Turn off also the second PS and disconnect voltmeter V2 from the Out diodes pins of the overvoltage crowbar test jig 7 MODELS PSD12...

Page 17: ...d observe that the corresponding output voltage V1 increases simultaneously while rotating 4 At this point Crowbar A will trigger the shortcircuit and output voltage V1 will be 2 V Maximum voltage V1 obtained just before the crowbar s trigger point should be between 27 0 V and 29 0 V 5 Turn off the PS immediately by opening the supply switch I1 so that the crowbar is reset 6 Rotate potentiometer P...

Page 18: ...e PS immediately by opening the supply switch I1 so that the crowbar is reset 5 Crowbar B operation Connect the power supply as shown in the following image Output voltage value V1 should be greater than 24 V nominal at 80 of full load Now after checking this condition rotate potentiometer P1 counter clockwise slowly to decrease its resistance and observe that the corresponding output voltage V1 i...

Page 19: ...the PS by closing switch I1 2 Verify that the output voltage V1 is between 25 5V and 28V nominal at 80 of full load and without load 3 Overvoltage Protection operation Connect the power supply as shown in the following image MODELS PSD1210 PSD1206 Turn off the PS 4 CS Sharing current I1 _ PR A1 V1 L N 220 Vac 4 3 2 1 ON OFF Vout adjust Diode test TPF1210 C2 C1 B2 B1 A2 A1 D2 D1 S2 COM S1 ...

Page 20: ...The equation of PFDavg applicable when the component or sub system is new and when λdu are 99 known by proof test is When these tests do not detect at least 99 of λdu the same equation changes to where Et is the effectiveness of proof test 0 100 SL can be intended as 1 Time between two proof tests with 99 100 effectiveness 2 Time between two replacements 3 Component Life time if no substitution an...

Page 21: ... Sharing Current Sharing L N CS L N CS L N CS _ _ _ Fault Output 2 Supply Input 2 Fault Output 3 Supply Input 3 Fault Output 4 Supply Input 4 To obtain higher output voltage of 48 V with 100 redundance it is possible to connect two modules in series plus two redundant modules in parallel as shown in the figure Output voltage can be furtherly increased maintaining redundancy by paralleling more uni...

Page 22: ...Voltage Example of setting output voltage and alarm threshold suppose to have a power supply standard with 24 Vdc output and thresholds set at 22 8 25 2 V Suppose you want to set the output at 25 V with 23 7 26 3 V threshold value The procedure to be used is the following rotate the Vout Adjust trimmer until the voltage has reached the new upper threshold value of 26 3 V Rotate the Alarm Adjust tr...

Page 23: ...nder normal operating conditions They are designed to operate trouble free and with high stability for long time If a unit is found not meeting specifications or in a failure condition then it requires recalibration or servicing Any repair made by unauthorized personnel may completely invalidate the safety characteristics of the unit Repair not made by GM International is prohibited If a unit fail...

Reviews: