0020239562_04 EASICOM 3 Installation and maintenance instructions
11
6
Set-up
6.1
Checking the scope of delivery
▶
Check that the scope of delivery is complete and intact.
Quantity
Description
1
Heat generator
1
Bag with accessories
–
Bag with seals
–
Condensate drain hose
–
Drain spigot of the expansion relief valve
–
Hanging bracket
–
Bag containing the hydraulic connections
1
Enclosed documentation
6.2
Dimensions
A
C
B
D
Dimensions
A
B
C
D
740 mm
130 mm
300 mm
418 mm
6.3
Installation site
This boiler is not suitable for outdoor installation. This boiler
may be installed in any room. However if the boiler is being
installed in a room containing a bath or shower it must only
be installed in zones 2 or 3. In GB this is the current I.E.E.
WIRING REGULATIONS and BUILDING REGULATIONS. In
IE reference should be made to the current edition of I.S.813
“Domestic Gas Installations” and the current ETCI rules.
If the boiler is to be installed in a timber frame building it
should be fitted in accordance with the current version of the
Institute of Gas Engineers document IGE/UP/7. If in doubt
seek advice from local gas undertaking or the manufacturer.
6.4
Minimum clearances
C
C
D
A
B
Minimum clearances
A
B
C
D
≥
150 mm
≥
150 mm
≥
0 mm
Note
≥
50 mm (re-
quired clear-
ance for re-
moving the
side section)
≥
500 mm
Note
≥
5 mm (for
cupboard
installation)
The boiler and flue are suitable for installation onto and
through combustible materials provided that:
1.
Minimum 5 mm clearance is maintained around the
circumference of the flue (air intake).
2.
The combustible surface and fixings are suitable for
supporting the load.
3.
The minimum clearances from the boiler case are main-
tained.
6.5
Compartment Ventilation
The boilers are very high efficiency appliances.
As a consequence the heat loss from the appliance casing
during operation is very low.
Compartment ventilation is not required as the products are
only certified, and can only be fitted with a concentric flue
system.