background image

0020239568_04 Ultimate 3 Installation and maintenance instructions

27

Ensure that all other gas appliances in the property are
turned off.

Measure the gas flow rate at the gas meter.

Compare the measured values with the corresponding
values in the table.

Qnw from the data
plate

H gas in m

³

/h

Nom.

+5%

10%

15.3

1.62

1.70

1.46

18.4

1.95

2.05

1.76

24.7

2.61

2.74

2.35

25.7

2.72

2.86

2.45

28.6

3.03

3.18

2.73

30.6

3.24

3.40

2.92

35.7

3.78

3.97

3.40

Condition

: Gas flow rate not in the permissible range

Check all of the piping and ensure that the gas flow rates
are correct.

Only put the product into operation once the gas flow
rates have been corrected.

Condition

: Gas flow rate in the permissible range

End the check programme

P.01

.

Allow the boiler to cool down by allowing pump overrun to
operate for a minimum of 2 minutes.

Record the boiler maximum gas flow rate onto the
Benchmark gas boiler commissioning checklist.

9.7.3

Checking the gas connection pressure (gas
flow pressure)

1

2

1.

Ensure that the gas inlet working pressure can be
obtained with all other gas appliances in the property
working.

2.

Close the gas stopcock

(1)

.

3.

Undo the sealing screw on the test nipple

(2)

.

4.

Connect a manometer to the test nipple

(2)

.

5.

Open the gas stopcock

(1)

.

6.

Start up the product with check programme

P.01

(sys-

tem with eBUS control) or

P.03

(installation without

eBUS control).

7.

In addition, ensure that maximum heat can be dissip-
ated into the heating system by turning up the room
thermostat.

8.

With the boiler operating at full load check that the gas
inlet working pressure at the reference test point

(2)

complies with the requirements.

Permissible gas flow pressure for operation with

Natural gas H

1.3 to 2.3 kPa
(13.0 to 23.0 mbar)

9.

Should the pressure recorded at the reference test point
in the boiler be lower than indicated check if there is
any blockage in the pipework or if the pipework is un-
dersized.

Condition

: Gas flow pressure

not

in the permissible range

Caution.
Risk of material damage and operating
faults caused by incorrect gas connec-
tion pressure.

If the gas connection pressure lies outside
the permissible range, this can cause oper-
ating faults in and damage to the product.

Do not make any adjustments to the
product.

Do not start up the product.

If you cannot correct the failure, notify the gas supply
company and proceed as follows:

End check programme P.01.

Allow the boiler to cool down by allowing pump overrun
to operate for a minimum of two minutes.

Close the gas stopcock.

Remove the pressure gauge and retighten the sealing
screw

(2)

for the measuring nipple.

Open the gas stopcock

(1)

.

Check the test nipple for gas tightness.

Close the gas stopcock

(1)

.

Install the front casing.

Disconnect the product from the electrical installation.

You must not start up the boiler.

Condition

: Gas flow pressure

in the

permissible range

End the check programme

P.01

.

Allow the boiler to cool down allowing pump overrun to
operate for a minimum of two minutes.

Close the gas stopcock

(1)

.

Remove the pressure gauge and retighten the sealing
screw

(2)

for the measuring nipple.

Open the gas stopcock

(1)

.

Check the test nipple for gas tightness.

Remove the front casing.

Reset boiler controls for normal operation.

Record the appliance gas inlet working pressure (kPa
resp. mbar) in the Benchmark gas boiler commissioning
checklist.

9.7.4

Checking the CO

content

1.

Start up the product with the check programme

(P.01)

and set the value.

Setting value for the programme P.01: 100

Check programmes

Overview (

Page 35)

2.

Wait until the value that is read is stable.

Waiting period for reading a stable value: 5 min

3.

Unscrew the cover from the flue gas analysis point.

4.

Measure the CO

content at the flue gas analysis point.

5.

Compare the measured value with the corresponding
value in the table.

Summary of Contents for 0010021408

Page 1: ...en Installation and maintenance instructions Ultimate 3 25r A H GB 0020239568_04 07 10 2020...

Page 2: ...king and treating the heating water filling and supplementary water 25 9 3 Filling the condensate trap 26 9 4 Switching on the product 26 9 5 Flushing the heating installation for the first time cold...

Page 3: ...direct use in industrial or commercial processes Any use other than those described in these instructions and any use that goes beyond what is described here 1 2 Qualification The person carrying out...

Page 4: ...cially available soft soap to aid installa tion 1 3 3 Electricity The power supply terminals L and N remain live even if the unit main switch is switched off To prevent electric shocks proceed as fol...

Page 5: ...1 3 10 Safety devices Install the necessary safety devices in the installation 1 4 Regulations directives laws standards Observe the national regulations stand ards directives ordinances and laws 1 5...

Page 6: ...lant group com Spares Enquiries Telephone 01773 881383 To register your Glow worm appliance visit Glow worm is a licensed member of the Benchmark Scheme Benchmark places responsibilities on both manuf...

Page 7: ...l efficiency at 40 30 C 106 0 Nominal efficiency in par tial load operation 30 at 40 30 C 109 7 NOx class 5 Product dimensions width 375 mm Product dimensions height 602 mm Net weight 22 kg Weight whe...

Page 8: ...derside of the product at the factory Information on the data plate Meaning Barcode with serial number Serial number For quality control purposes 3rd and 4th digits year of production For quality cont...

Page 9: ...If the boiler fails to resume normal operation and all external controls are calling for heat then call your Installation Servi cing company or Vaillant service 5 6 3 Frost protection The appliance h...

Page 10: ...Rear air flue connection 6 Top air flue connection 6 3 Installation site This boiler is not suitable for outdoor installation This boiler may be installed in any room However if the boiler is being in...

Page 11: ...flue gas systems for more information about the other possibilities and associated accessories Minimum fall 44 mm m Standard flue terminal kits have an in built fall back to the boiler to drain the co...

Page 12: ...ing material Vertical flue clearance to combustible building material 500 mm 1 500 mm J Above below and either side of an opening door air vent or opening window 300 mm K Diagonally to an opening door...

Page 13: ...e from pluming depending on site conditions Terminals must be positioned so to avoid combustion products entering the building Support the flue at approximately one metre intervals and at a change of...

Page 14: ...quired if persons could come into con tact with the terminal or the terminal could be subject to dam age If a terminal guard is required it must be positioned to provide minimum of 50 mm clearance fro...

Page 15: ...te Use the mounting template to ascertain the locations at which you need to drill holes 6 7 Wall mounting the product Note If you are using the rear air flue connection in stall the air flue pipe bef...

Page 16: ...16 Installation and maintenance instructions Ultimate 3 0020239568_04 C D A B E 6 9 2 Installing the side section Refit the components in the reverse order...

Page 17: ...gas valve assembly using a pressure of 11 kPa 110 mbar 7 2 Installing the heating pump Pressure loss in the product from the product 0 50 100 150 200 250 300 350 400 0 200 400 600 800 1000 1200 1400...

Page 18: ...nd BS 7074 Part 1 Example For an initial design pressure of 0 7 bar the minimum total vessel volume required is 0 063 x Total System Volume Note A higher initial design pressure requires a larger volu...

Page 19: ...and the drain hose is not air tight Connect a condensate discharge pipe 21 5 mm not included in the scope of delivery to the drain hose 2 During installation remove all burs from inside of cut pipe wo...

Page 20: ...Seal 3 Plastic tube 100 mm diameter 4 Bottom of sealed tube 5 Limestone chippings 6 Hole depth 400 mm minimum Least preferred option must not terminate in rain water drain 7 8 1 6 Internal terminatio...

Page 21: ...om electric shock The power supply terminals L and N remain live even if the product is switched off Switch off the power supply Secure the power supply against being switched back on 7 10 1 Opening t...

Page 22: ...supply with a time switch or programmer 5 Connect the product using a fixed connection and an electrical partition with a contact gap of at least 3 mm e g fuses or power switches 6 Isolation should pr...

Page 23: ...nsure that the control is designed for a maximum nom inal current of 7 A Connect the control to the main plug X1 Terminal assignment L line N neutral conductor earth Draw the end user s attention to t...

Page 24: ...inish configuring the diagnostics codes The display switches to the basic display 8 2 Displaying the status codes The status codes display the product s current operating mode Status codes Overview Pa...

Page 25: ...stipulate more stringent requirements the following applies You must treat the heating water in the following cases If the entire filling and supplementary water quantity dur ing the operating life o...

Page 26: ...purging valves on the radiators so that the contaminated water can completely drain 4 Close the drain cocks 5 Refill the heating system with water 6 Close the filling valve and the cold water tap 9 6...

Page 27: ...he boiler be lower than indicated check if there is any blockage in the pipework or if the pipework is un dersized Condition Gas flow pressure not in the permissible range Caution Risk of material dam...

Page 28: ...energy losses an electronic restart lockout is activated for a specific period each time the burner is switched off The burner anti cycling time is only active for the heating mode Domestic hot water...

Page 29: ...full load 9 0 1 0 vol 9 2 1 0 vol CO at full load 250 ppm 250 ppm CO CO 0 0031 0 0031 The value is OK The value is not OK you cannot start up the product Set the CO content Page 29 12 5 Setting the C...

Page 30: ...er 3 Protect the open electronics box from spraying water 1 4 Clean the ribs of the heat exchanger 1 with water The water runs out via the condensate tray 12 8 Checking the burner Check the surface of...

Page 31: ...ocument 13 Troubleshooting 13 1 Eliminating faults If fault codes F XX are present consult the table in the appendix for advice or use the check programme s Overview of fault codes Page 39 Check progr...

Page 32: ...pair work use only the spare parts that are permitted for the product 13 6 Replacing defective components 13 6 1 Replacing the burner 1 Remove the gas air mixture unit Page 29 2 Remove the burner seal...

Page 33: ...e 21 2 Pull the plug out of the PCB 3 Undo the clips on the PCB 4 Remove the PCB 5 Install the new PCB in such a way that it clicks into the groove at the bottom and into the clip at the top 6 Plug in...

Page 34: ...lly 10 If the gas flow rate lies outside of the tolerances specified in these in structions eliminate the fault in accordance with the regulations and the current technology Annually 11 Check the gene...

Page 35: ...r demand the product runs in domestic hot water mode with maximum heat input If there is no domestic hot water demand the product runs in heating mode with the partial heat load that is set using diag...

Page 36: ...alue off on Not adjustable d 11 Status of the heating cir cuit s shunt pump Current value off on Not adjustable d 13 Status of the domestic hot water circuit s circulation pump Current value off on No...

Page 37: ...djustable d 40 Heating flow temperature Current value Not adjustable d 41 Heating return temperat ure Current value Not adjustable d 43 Heat curve 0 2 4 0 1 1 2 Adjustable d 45 Value for the base poin...

Page 38: ...play value x 100 Not adjustable d 84 Maintenance in 0 3000 h Number of hours Display value x 10 300 Not adjustable d 85 Increase in the min out put heating and DHW mode kW 1 Section Technical data Adj...

Page 39: ...oose multiple plug on the PCB not plugged in correctly interruption in cable harness NTC sensor defective F 01 Fault Return temperature sensor NTC plug not plugged in or has come loose multiple plug o...

Page 40: ...ult Unstable flame analogue input Air in gas gas flow pressure too low incorrect air ratio incorrect gas in jector ionisation flow interruption cable electrode F 70 Invalid product code DSN Display an...

Page 41: ...X32 X90 X12 X35 X1 RT X21 L N L N 1 5 eBUS Burner off X106 M 4 3 2 1 N L 24V 230V 24V 230V 1 2 3 2 7 9 1 4 3 5 6 10 11 12 8 1 Main PCB 2 Interface PCB 3 Control system 4 Temperature sensor on the heat...

Page 42: ...r and they should be made aware it is ultimately their responsibility to register with the manufacturer within the allotted time period It is essential that the boiler is serviced in line with the man...

Page 43: ...left at factory settings Yes No If no what is the maximum central heating output selected kW Dynamic gas inlet pressure mbar C Central heating return temperature C System correctly balanced rebalanced...

Page 44: ...R delete as appropriate Date Engineer name Company name Telephone No Gas Safe registration No Max rate CO ppm CO CO CO Min rate CO ppm CO CO CO undertaken in accordance with manufacturers instructions...

Page 45: ...R delete as appropriate Date Engineer name Company name Telephone No Gas Safe registration No Max rate CO ppm CO CO CO Min rate CO ppm CO CO CO undertaken in accordance with manufacturers instructions...

Page 46: ...pecify how to set boiler to minimum rate contact Technical Helpline for advice CHECK CO AND COMBUSTION RATIO AT MINIMUM RATE With boiler still set at minimum rate insert analyser probe into flue gas s...

Page 47: ...ouncil Number 8 Gas flow rate 26 Gas group checking 18 Gas setting 26 Gas air mixture removing 29 H Handing over to the end user 28 Heat exchanger cleaning 30 Heating pump connecting 22 Heating system...

Page 48: ...Group UK LTD Nottingham Road Belper Derbyshire DE56 1JQ Telephone 01773 824639 Technical helpline 0330 100 7679 After sales service 0330 100 3142 www glow worm co uk These instructions or parts thereo...

Reviews: