9.3 Thermocouple
Remove casing as described in Section 3.1.
To test a thermocouple, a meter with a range of 0 to 30 mV
is required together with a thermocouple interrupter test
unit.
Refer to fault finding diagram 9.3 and diagnosis graph,
diagram 9.4, 9.5 and 9.6.
9.4 Combustion Products Discharge Safety
Device
If the device operates it indicates there could be a problem
with the chimney or, the pilot filter in the gas tap is
blocked. First make sure air vents are free from
obstructions, by carrying out spillage checks as Section 6.3.
If all is in order refer to diagram 9.4 to check if the pilot
filter is blocked.