0020117819_01 - 05/11 - Glow-worm
- 33 -
Code Function
Description
Setting
Factory
setting
Modi
fi
able
parameter
Min
Max
126 Con
fi
gurations
exterior sensor
Choose the type of exterior-temperature sensor:
1 = Remote sensor (connected onto terminal block 23 and 24)
2 = Sensor installed on the heat pump.
1
2
2
Yes
127 Exterior temperature This parameter displays the external temperature measured by the sensor
installed in the heat pump.
-
-
-
No
128
Temperature of
the cooling circuit
battery
This parameter displays the temperature of the heat pump's cooling circuit battery.
-
-
-
No
129 Compressor suction
temperature
This parameter displays the compressor's suction temperature.
-
-
-
No
130
Compressor
discharge
temperature
This parameter displays the compressor's discharge temperature.
-
-
-
No
131 Functioning state of
the heat pump
This parameter displays the functioning state of the heat pump:
0 = Stopped
2 = Cooling mode
3 = Heating mode
4 = Fault
5 = Defrost mode
-
-
-
No
132 Maximum frequency
of compressor
This parameter displays the maximum frequency of the compressor allowed by the
heat pump's command board.
-
-
-
No
133 Required compressor
frequency
This parameter displays the compressor frequency required by the heat pump's
command board.
-
-
-
No
134 Real compressor
frequency
This parameter displays the real frequency of the compressor variator.
-
-
-
No
135
Counter that times
the functioning of the
compressor
This parameter displays the number of hours during which the compressor has
functioned since
fi
rst activation.
-
-
-
No
136 Capacity of the heat
pump
This parameter displays the capacity of the heat pump.
-
-
-
No
137
Return temperature
of the heat pump
circuit
This parameter displays the return temperature of the heat pump's circuit.
-
-
-
No
138
Flow temperature
of the heat pump's
circuit
This parameter displays the
fl
ow temperature of the heat pump's circuit.
-
-
-
No
139
Temperature of
the cooling
fl
uid in
the plate to plate
exchanger
This parameter displays the temperature of the cooling
fl
uid in the plate to plate
exchanger
-
-
-
No
140 State of functioning
of the system
This parameter displays the state of functioning of the system:
0 = Stopped
1 = Standby mode
2 = Cooling mode
3 = Heating mode
4 = Booster heating functioning
5 = Booster cooling functioning
4 = Nominal heating
5 = Nominal cooling
8 = Frost protection mode
9 = Defrost
10 = Protection against overheating
11 = Guard interval
12 = System fault
-
-
-
No
141 Fault codes
This parameter displays the fault codes for the heat pump.
-
-
-
No
142 Version of the heat
pump's software
This parameter displays the version of the heat pump's software.
-
-
-
No
143 Update to the heat
pump's software
This parameter displays the latest update made to the heat pump's software.
-
-
-
No
144
Counter that times
the functioning of the
circulator
This parameter displays the number of hours during which the circulator has
functioned since
fi
rst activation.
-
-
-
No
145
Temperature setting
calculated for the
installation's water
This parameter displays the temperature setting for the installation's water
calculated by the command board according to climatic graphs.
-
-
-
No
INSTALLATION