Glow-worm COMPACT 75e Instructions For Use Installation And Servicing Download Page 22

22

221895A

Please ensure the “Benchmark” logbook is completed and left
with the user.

10.1 Filling Domestic Water Circuit

Check that the boiler is isolated from the electrical supply, at the
external isolator.

Fully open the domestic water supply stop cock or valve in the
supply to the boiler.

Open the inlet domestic water isolation valve, lever in line with
the valve body, see diagram 6.1.

Open all hot water draw-off taps and close them when water
flows.  Check for water soundness of the whole domestic water
system and boiler.

10.2 Filling the Heating System

Open the two central heating isolating valves, levers in line with
the valve body, see diagram 6.1.

Flush, fill and vent the system refer to Section 4.8 “Filling
Sealed Systems”.

WARNING.  SEVERAL COMPONENTS OPERATE ON MAINS
VOLTAGE AND WITH THE OUTER CASE REMOVED, LIVE
COMPONENTS BECOME EXPOSED.

Make sure that the automatic air vent is operating correctly.

Take care not to splash any of the electrical components.

Open the controls cover.

Refer to diagram 4 Instructions for Use.  Operate  button “J”
between “L” summer and “K” winter to ensure that water flows
through all parts of the boiler and air is not trapped in the boiler
internal bypass.

Pressurise the system until the pressure is 1.5bar.  Check the
heating system and boiler for water soundness.

Check the operation of the safety valve by turning the safety
valve knob in the direction of the arrow.

Lower the pressure to the initial cold fill design pressure, refer
to Table 1.  Position the set pointer on the boiler pressure gauge
at this pressure also.

Refit inner case front.

10.3 Preparation for Lighting

Isolate the boiler from the mains electrical supply at the external
isolator.

Purge gas supply test for soundness .  Turn on the gas service
cock, slot in line with the length of the cock.

Loosen the burner pressure test point screw and connect a
suitable pressure gauge, see diagram 10.1.

10.4 Burner Pressure - Hot Water

Connect the electrical supply; the pump will operate for about
30 seconds, then the pump will stop.

Fully open the largest hot water draw off tap whereby the main
burner will light, the flames gradually increasing to the maximum.

Check the soundness of the boiler gas joints, with the main
burner on, using a leak detection fluid.  Take care not to splash
any of the electrical components.

To achieve this flow rate a water pressure of at least 0.8bar is
required during commissioning, although subsequently the
appliance will work at a minimum pressure of 0.5bar.

This flow rate should prevent any modulation of the gas
pressure.

10 Commissioning

The burner pressure is factory preset and no adjustment should
be required.

Check the burner pressure is /-0.2mbar. of 14.7mbar. If
this is incorrect, the burner pressure may be adjusted to the
correct setting by turning the hot water gas pressure adjuster
(potentiometer), located on the control board.  To gain access
remove the two screws securing the controls facia, see diagram
9.1.

Hinge the control facia forward.

Remove the plastic plugs.  Using the burner adjusting tool
supplied. (clockwise to increase), see diagram 10.2.  Turn the
adjuster slowly, always making adjustment by reducing below
the required pressure then increasing up to the required setting.

Close the hot water draw off.

If the maximum pressure cannot be obtained, check that the gas
supply of adequate size, refer to Section 1.7.

10.5 Gas Rate Modulation

The burner pressures are factory preset and no adjustment
should be required.

When checked if they are not consistant with the information in
table 1. the following steps should be taken.

Fully open a domestic hot water tap ensure there is no modulation.
Turn the domestic burner pressure potentiometer to minimum
by turnining anticlockwise with the tool supplied (do not force it),
see diagram 10.2.

Carefully turn the minimum stop screw on the gas control valve.
When the correct setting is achieved adjust the potentiometer
on the control board (PCB) until the maximum is achieved.  If it
is not possible to abtain the maximum required turn the
potentiometer fully clockwise (do not force it).  Removing the
cover screw on the main gas control valve and turn the adjustment
screw until a pressure of 1mbar above the maximum stated in
table 1. is achieved.  Refit the cover and adjust the potentiometer
to give the stated maximum setting by turning below the setting,
then slowly increasing upwards.

10.6 Domestic Water Flow Rate

This is factory preset and can not be adjusted.

10.7 Burner Pressure  - Heating

The burner pressure is factory preset and no adjustment should
be required.

Check that all remote heating system controls, room thermostats,
integral clock and the like are switched on/programmed and
calling for heat.

Refer to diagram 4 Instructions for Use.  Set button “J” to “K”
winter, see diagram 4.

The pump will circulate water through the boiler and the main
burner will light.

Check that the burner pressure, with the heating system cold to
prevent any modulation of the gas pressure, is /-
0.2mbar of 14.7mbar, the central heating  pressure.

If the burner pressure is incorrect, it may be adjusted to the
correct setting by turning the central heating gas pressure
adjuster (potentiometer), located on the control board to gain
access remove the two screws securing the controls facia.

Using the burner adjusting tool supplied. (clockwise to increase),
see diagram 10.2.  Turn the adjuster slowly, always making
adjustment by reducing below the required pressure then
increasing up to the required setting.

Summary of Contents for COMPACT 75e

Page 1: ...liances are manufactured to the very highest standard so we are pleased to offer our customers a Comprehensive First Year Guarantee In the centre pages are to be found your Guarantee Registration Card...

Page 2: ...atibility Substances Hazardous to Health The adhesives and sealants used in this appliance are cured and give no known hazard in this state INSULATION PADS CERAMIC FIBRE GLASSYARN MINERAL WOOL These c...

Page 3: ...o its use Alternatively a fused 3A 3 pin plug and shuttered unswitched socket may be used Thecoloursofthreecoreflexiblecableare blue neutral brown live green and yellow earth As the markings on your p...

Page 4: ...l not operate Soft Override button indicated by the symbol this function will override the current central heating programme for the next available ON time programmes are indicated by the symbol 3 Set...

Page 5: ...is opened while the boiler is on for heating priority will be given to hot water Toturntheheatingoffforshortperiods setbutton J tosummer Off light L will illuminate To turn on again set button J to wi...

Page 6: ...ief Safety Valve CAUTION A pressure relief safety valve and discharge pipe is fittedtotheboiler Thisvalvemustnotbetouched Shouldthere be any discharge from the pipe turn the boiler off isolate from th...

Page 7: ...rating of dwellings The test data from which it has been calculated have been certified by B S I Diagram 1 1 Optional flue kits are available Horizontal top outlet and Vertical Lift Weight 31 7kg 69...

Page 8: ...General Data Thermostatic radiator valves may be installed however they must not be fitted in a room where the room thermostat is located Note All systems must have at least one radiator not fitted w...

Page 9: ...he installation of the boiler will be in an unusual position the current issue of BS6798 gives detailed guidance on these requirements An existing cupboard or compartment modified for the purpose may...

Page 10: ...painted gutter an aluminium shield 750mm long should be fitted immediately beneath the guttering or eaves 3 3 Flue Options There are various flue systems to choose from as follows Standard Top Outlet...

Page 11: ...the flow diagram 4 2 This valve must be lockable and positioned so that inadvertent closure or unauthorisedinterferenceisnotpossible Thedesigndifferential can be between 11 C 20 F and 17 C 30 F depend...

Page 12: ...domestic hot water service must be in accordance with the rules in force in the countries of destination 5 2 Water Pressure For the minimum and maximum working pressures of the domestic hot water circ...

Page 13: ...r also to Section 5 Domestic Hot Water System Provision is made for the water connections to be connected from below or from above passing down either side of the boiler Take care that any pipework co...

Page 14: ...ion kits may be joined together STD EXTD X plus 254mm RH flue length X plus 10mm LH flue length EASYFIT X plus 282mm RH flue length X plus 38mm LH flue length must include 50mm min side clearance REAR...

Page 15: ...site the expanded end If the boiler is not to be fitted for some time cover the hole in the wall 7 3 Internal Access Flue If access to the outside wall is not practical the flue system can be installe...

Page 16: ...ove the fan and flue collector assembly by pulling it forward see diagram 8 3 Remove the rear outlet restrictor plate and retain if using the rear flue outlet see diagram 8 4 REAR FLUE ONLY Fit the fl...

Page 17: ...screws provided in the fittings pack see diagram 8 6 An anti theft kit is available Kit No 457110 8 4 Discharge Pipe Fit the short discharge pipe to the safety valve using the nut and sealing washer s...

Page 18: ...PE 8 Mounting the boiler SAFETY VALVE DISCHARGE SEAL PRESSURE GAUGE CONNECTION DISCHARGE PIPE 7405 Diagram 8 7 Fit the air duct into the flue spigot by pulling the air duct into the flue spigot locati...

Page 19: ...m the flue collector secured with a screw and retaining lip Fit the flue connecting sleeve onto the fan see diagram 8 12 Fit the fan to the flue ducting Holding it up in position fit the flue collecto...

Page 20: ...equired to provide a minimum of reinforced insulation at 250Vrms between the parts of those devices operating at mains hazardous voltage and the user accessible parts af those devices Note For further...

Page 21: ...T STAT L N R1 R2 3 AMP FUSE L N 230V 50Hz PERMANENT MAINS SUPPLY POTENTIAL FREE ROOM STAT NO FROST STAT TO BOILER RED LINK REMOVE WHEN CONNECTING SYSTEM CONTROLS 5 WAY TERMINAL BLOCK POTENTIAL FREE RO...

Page 22: ...should be required Check the burner pressure is within 0 2mbar of 14 7mbar If this is incorrect the burner pressure may be adjusted to the correct setting by turning the hot water gas pressure adjuste...

Page 23: ...from the electrical supply and drain the system rapidly whilst still hot Remove the inner case front Fill and vent the system as described in Section 10 2 Filling the Central Heating Circuit Add inhi...

Page 24: ...e Gas Safety Installation and Use Regulations Section 35 which imposes a duty of care on all persons who let out any property containing a gas appliance It is the Law that any servicing is carried out...

Page 25: ...to release then remove see diagram 10 5 11 5 Inner Case Front Remove the inner case front secured by two clamps at the bottom lift up and unhook at the top see diagram 8 1 11 6 System Pressures and Dr...

Page 26: ...he burner thoroughly making sure that all burner ports are clear and unobstructed Diagram 12 1 9408 BURNER SECURING SCREW 3 LEADS 3 SENSING ELECTRODE SILICONE SLEEVE 3 EARTH ELECTRODE IGNITION ELECTRO...

Page 27: ...s 0 7bar minimum and that the automatic air vent works Refer to Installation Instructions Section 10 2 3 That the gas supply is available at the boiler and purged of air 4 That the boiler is set for t...

Page 28: ...TIMER 7467 Diagram 13 2 MAINS FUNCTIONAL FLOW 7670 grey orange PCB purple white black X5 X5 X4 X4 X4 X4 X4 X3 X3 X5 DHW FLOW SWITCH purple purple orange orange X5 CH THERMISTOR DHW THERMISTOR CONTROL...

Page 29: ...e temporarily unplugged from the electrodes and laid where they cannot spark and ignite the gas and are electrically safe This indicates that the APS changes state when the fan is run The three way va...

Page 30: ...kout L E D is illuminated press reset Check 230V supply to pump Check 230V supply to fan Check spark electrodes and cables If domestic hot water demand is still illuminated Faulty domestic hot water s...

Page 31: ...eck continuity of clock timer harness ensure an electrical supply is available ensure that remote controls are calling for heat NB The clock can be by passed by refitting the plug link which should be...

Page 32: ...ectrode lead and silicone sleeve remove the securing screw and electrode see diagram 12 1 14 5 Ignition Earth and Sensing Leads Before starting refer to Section 11 Disconnect the silicone sleeve and l...

Page 33: ...starting refer to Section 11 Remove the two screws securing the controls cover door and controls fascia see diagram 9 1 Hinge the assembly open Disconnect multi pin connector Support the gas control...

Page 34: ...move the plastic cover Remove the electrical connectors Refer to wiring diagram 14 29 when fitting 14 12 Safety Valve Before starting refer to Section 11 Remove the two screws securing the controls co...

Page 35: ...bly forward Disconnect the electrical connections unclip to remove themistor see diagram 14 4 14 17 Flow Regulator Filter Before starting refer to Section 11 Drain domestic hot water Remove outer case...

Page 36: ...O RING PRESSURE DIFFERENTIAL MICRO SWITCH Diagram 14 16 6987 SECURING CLIP Diagram 14 17 6983 SECURING CLIP DOMESTIC HOT WATER MICRO SWITCH REGULATOR SECURING PIN O RING 6991 DIVERTER SWITCH DIVERTER...

Page 37: ...ve multi pin connector Remove securing pins 4 5 and 6 see diagram 14 18 ELECTRICAL PLUG 7019a PRESSURE DIFFERENTIAL MICRO SWITCH Diagram 14 18 HYDRO BLOCK ASSEMBLY DIVERTER SWITCH 14 Replacement of Pa...

Page 38: ...bracket Pull the boiler from the isolating valves Unhook the boiler at the top easing the boiler from the flue outlet and lift off Carefully lay the boiler down on its side for access to the expansio...

Page 39: ...et pipes Remove the combustion chamber main panel securing screws Remove the heat exchanger combustion chamber assembly Remove heat exchanger front retaining clips Remove the heat exchanger from its r...

Page 40: ...see diagram 14 25 Slide out both side insulation pieces Pull the lower rear insulation forwards then slide the upper rear insulation down from behind the heat exchanger 14 28 Viewing Window Before sta...

Page 41: ...secured with two screws When replacing the tubes to the air pressure switch make sure that the red tube from the fan connects to the upper connection of the switch The polarity of the electrical conn...

Page 42: ...HITE b BLUE bk BLACK br BROWN g y GREEN g GREY or ORANGE r RED y YELLOW p PURPLE YELLOW CHASSIS EARTH FUSED AT 2A PUMP E N L 230V 50Hz PERMANENT MAINS SUPPLY FUSED AT 3A KEY NOTE w w w bk bk b y g g b...

Page 43: ...ated E27211 14 202226 Fuse not illustrated 278136 15 801182 Gas control valve E27124 16 227070 Air pressure switch assy 17 801186 Automatic air vent assembly E27166 18 801208 Safety valve assembly E27...

Page 44: ...221895A Because of our constant endeavour for improvement details may vary slightly from those shown in these instructions Diagram 15 1 7007a 15 Spare Parts 9 5 11 12 8 1 16 3 4 17 18 6 9 2 7 20 10 19...

Reviews: