Global Power Technologies
ASSEMBLY AND INSTALLATION
302842 Rev0 | Sentinel
Page 18 of 61
3.4.2
FUEL FILTER INSTALLATION
Figure 7 – Mounting the Fuel Filter
Before mounting or connecting the fuel filter to the fuel supply, install two filter cartridges within the
fuel filter assembly. Refer to Section 5.2.1 for instructions on filter cartridge installation.
Install the fuel filter in a vertical position with the flow arrow pointing upwards. The fuel filter can be
mounted on a wall or pole. For ease of maintenance, mount the fuel filter 12 to 14” from the bottom
of the Sentinel TEG.
To mount the fuel filter to a pole:
1.
Remove the locknuts from the ends of the two supplied U-clamps.
2.
Attach the U-clamps to the pole and insert the ends of the U-clamps through the holes in the fuel
filter’s mounting bracket.
3.
Secure the mounting bracket to the pole by rethreading the locknuts onto the U-clamps. Ensure
the fasteners are fully tight before proceeding to the next step.
For Sentinel TEGs that are mounted to a wall, install the fuel filter in an upright position with the flow
arrow pointing upwards. Allow 12 to 14” of clearance above the filter so that it is easily accessible
when replacing the filter cartridges. As with the TEG mounting bracket, the fuel filter bracket has
been designed to accept 3/8” diameter fasteners. Ensure the appropriate length and type of
fasteners are chosen for the mounting application.
CAUTION!
Using the Sentinel without fuel filter will void product warranty.