background image

OPERATION

JUNO-NET

1.9 CARETAKER TEST MODE (One-Man Walk-Through Test)

Entry and Exit of Caretaker Test Mode

Press the QUEUE REVIEW - TEST

first, then the CONTROLS - LAMP TEST

momentarily.

(The FAULTS - PROC FAULT

button

button

LED will light momentarily, this is OK).

Test mode can be activated at anytime except when:

·

There is a FIRE

·

SOUND ALARMS have been activated

·

Something is already in TEST MODE (Test Sounders or Test Zones)

·

The system is in ALERT MODE (pulsing sounders requested by PC graphics package)

·

You are in Programming Mode

·

You are Installation Mode

When Caretaker Test Mode is entered 'INITIALISING' may be displayed for up to 20 seconds
depending on the system size.

Caretaker Test Mode is exited by pressing

.

·

The TEST LED will be lit

·

The buzzer will sound for 0.5 seconds every 5 seconds (same as FAULT indication). ALARM
SILENCE will not stop this.

·

The message “ DETECTOR TEST MODE “ will be displayed on the LCD

·

The Zones in test mode will be displayed on the LCD - “ ALL ZONES “

SYSTEM RESET

Indication of Caretaker Test Mode

STATUS

FIRE ALARM SYSTEM

FIRE

FAULT

PRE-ALARM

TEST

DISABLED

SYSTEM ON

ALARM FAULT

SUPPLY FAULT

PROC. FAULT

TRANS. FAULT

SOUND ALARMS

PAPER FEED

LAMP TEST

SYSTEM RESET

ALARM SILENCE

DISABLED

TEST

FAULT

FIRE

AUXILIARY

RELAYS

FIRE BRIGADE

TRANSMISSION

SELECTED

DETECTORS

ACTIVE

DELAYS

FIRE BRIGADE

ACKNOWLEDGED

ALARM DISPLAY

JUNO-NET

MANUFACTURED TO THE

REQUIREMENTS OF

EN54 Pt 2 & Pt 4 1999

FAULTS

CONTROLS

DISABLEMENTS

QUEUE REVIEW

1

2

3

4

5

6

7

8

10

11

12

13

14

15

16

17

18

19

21

23

22

20

25

24

27

26

29

30

32

33

31

28

34

35

LCD DISPLAY

10

OPERATION & MAINTENANCE MANUAL
REVISION 0.7a
16-04-2004

Summary of Contents for JUNO-NET

Page 1: ...OPERATION MAINTENANCE MANUAL JUNO NET Fire Alarm Control Panel REVISION 0 7a 16 04 2004...

Page 2: ...g into Programming Mode 2 9 Logbook 2 10 Event data sheet OPERATION 1 3 Reset the system 1 4 Sound and silence the alarms 1 5 Read the Fire Fault Test and Disabled queues 1 6 Active Delays 1 7 Lamp Te...

Page 3: ...n the LEDs in the FAULTS section of the main panel i e 7 8 9 10 If the LED is AMBER it indicates that a detector is in PRE ALARM If the LED is AMBER it indicates that the panel is in a test mode If th...

Page 4: ...eans that the relay and I O module outputs are disabled If there are disablements then pressing this button will show the disablements on the LCD display If there are more disablements than can be sho...

Page 5: ...TEST TEST DISABLED DISABLED SYSTEM ON SYSTEM ON ALARM FAULT ALARM FAULT SUPPLY FAULT SUPPLY FAULT PROC FAULT PROC FAULT TRANS FAULT TRANS FAULT SOUND ALARMS SOUND ALARMS PAPER FEED PAPER FEED LAMP TES...

Page 6: ...5 LCD DISPLAY This procedure should be used if There has been an alarm and the alarm condition no longer exists There has been a fault and the fault condition no longer exists Press the button The sys...

Page 7: ...NTROLS CONTROLS CONTROLS DISABLEMENTS DISABLEMENTS DISABLEMENTS DISABLEMENTS QUEUE REVIEW QUEUE REVIEW QUEUE REVIEW QUEUE REVIEW 1 1 1 1 2 2 2 2 3 3 3 3 4 4 4 4 5 5 5 5 6 6 6 6 7 7 7 7 8 8 8 8 9 9 9 9...

Page 8: ...1 23 22 20 24 27 26 29 30 32 33 31 28 34 35 LCD DISPLAY During installation via the programming functions delays can be set for the sounders I O modules and fire brigade transmission These delays are...

Page 9: ...T PROC FAULT TRANS FAULT SOUND ALARMS PAPER FEED LAMP TEST SYSTEM RESET ALARM SILENCE DISABLED TEST FAULT FIRE AUXILIARY RELAYS FIRE BRIGADE TRANSMISSION SELECTED DETECTORS ACTIVE DELAYS FIRE BRIGADE...

Page 10: ...Pt 4 1999 FAULTS CONTROLS DISABLEMENTS QUEUE REVIEW 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 18 19 21 23 22 20 25 24 27 26 29 30 32 33 31 28 34 35 LCD DISPLAY To start the fire drill press the SOUND AL...

Page 11: ...sing The TEST LED will be lit The buzzer will sound for 0 5 seconds every 5 seconds same as FAULT indication ALARM SILENCE will not stop this The message DETECTOR TEST MODE will be displayed on the LC...

Page 12: ...Panel and Repeater LCD displays for 15 seconds Testing More Than One Device Disablements Sensor sensitivity Other Detectors and callpoints can only be tested one at a time The LED must be extinguishe...

Page 13: ...THE REQUIREMENTS OF EN54 Pt 2 Pt 4 1999 FAULTS CONTROLS DISABLEMENTS QUEUE REVIEW 1 2 3 4 6 7 8 9 10 11 12 13 14 15 16 17 18 19 21 23 22 20 24 27 26 29 30 32 33 31 28 34 35 LCD DISPLAY SELECTED DETEC...

Page 14: ...UFACTURED TO THE REQUIREMENTS OF EN54 Pt 2 Pt 4 1999 FAULTS FAULTS CONTROLS CONTROLS DISABLEMENTS DISABLEMENTS QUEUE REVIEW QUEUE REVIEW 1 1 2 2 3 3 4 4 6 6 7 7 8 8 9 9 10 10 11 11 12 12 13 13 14 14 1...

Page 15: ...AULT PROC FAULT TRANS FAULT SOUND ALARMS PAPER FEED LAMP TEST SYSTEM RESET ALARM SILENCE DISABLED TEST FAULT FIRE AUXILIARY RELAYS FIRE BRIGADE TRANSMISSION SELECTED DETECTORS ACTIVE DELAYS FIRE BRIGA...

Page 16: ...e new roll The pointing towards the main circuit board Thread the paper into the printer Close the fascia and replace the screws Press the PAPER FEED and check that the paper feeds smoothly from the p...

Page 17: ...TURNED OFF SIM CARD The SIM CARD is mounted on the back of the main board Release the by pulling in the direction of the arrows With the retaining clips held in the released position push the SIM CARD...

Page 18: ...ARDS ELECTRO STATIC SENSITIVE DEVICES ESD TAKE SUITABLE ESD PRECAUTIONS WHEN REMOVING OR INSTALLING PRINTED CIRCUIT BOARDS ELECTRO STATIC SENSITIVE DEVICES ESD TAKE SUITABLE ESD PRECAUTIONS WHEN REMOV...

Page 19: ...and check that the battery voltage does not drop significantly Carry out a test on a detector or manual callpoint with the primary supply disconnected to ensure that the batteries are healthy NOTE BA...

Page 20: ...l the printer is free before starting a new print job If you wish to stop a printout enter the function again and you will be given the option of canceling the printout This function cannot be accesse...

Page 21: ...ces connected to the Analogue Loops Note that in Installation Mode all information is live i e the count of devices will change as the panel learns and device types will be updated if they change In A...

Page 22: ...Select the Zones you wish to put into test mode Exit programming mode but DO NOT press SYSTEM RESET as this clears all test modes In test mode when a detector is activated the LED on the detector will...

Page 23: ...one detector LED can be lit at any one time Select the device and SWITCHED ON and press ENTER The device will typically take a few seconds to respond Selecting NORMAL for that device or selecting SWI...

Page 24: ...e INFRA RED KEYPAD 0 A 4 E 8 I 1 B 5 F 9 J 2 C 6 G K 3 D 7 H L M N O P Q R S T U V W X Y HOME SHIFT ENTER B SP Z SPACE ESC EXIT HOME Return to first loop zone device etc ENTER Accept current selection...

Page 25: ...ER RESET PRINTER CONNECTOR PRINTER FUSE PS2 PC KEYBOARD ADAPTOR STANDOFFS 4 FOR LOOPCARD SIM CARD CONNECTOR QUAD UART 50 WAY BOX HEADER FOR J NET CON 16 WAY BOX HEADER FOR LOOP CONNECTOR LOOPCARD HEAD...

Page 26: ...IFT is off 0 9 are used to input numbers and are used to select items B SP and are often used to change fields move the cursor are often used to select the loop ENTER is used to select items and to st...

Page 27: ...ion or sub menu use either and ENTER or 0 9 and ENTER HOME takes you to 1 Review ESC takes you up a menu level Any number presses 0 9 will append a digit to what you see unless 1 You are at the very t...

Page 28: ...be made Sample pages of the logbook are provided here and can be photocopied to produce a logbook that conforms to EN54 14 The sample below is for the reference data e g the name of the responsible pe...

Page 29: ...MAINTENANCE JUNO NET 2 10 EVENT DATA SHEET DATE TIME EVENT INITIALS ACTION REQUIRED DATE COMPLETED 28 OPERATION MAINTENANCE MANUAL REVISION 0 7a 16 04 2004...

Reviews:

Related manuals for JUNO-NET