Global Power Products SURGE SAFE SM Series Installation, Operation And Maintenance Manual Download Page 2

 

Mounting 
 

1.  Locate the SPD between the meter and the main service circuit breaker panel. The SPD should be 

mounted to an electrical box or enclosure.  

2.  For the best performance, try to mount the unit as close as possible to the service panel, in close proximity 

to the breaker that will feed the Surge Protective Device.  

3.  Avoid sharp bends and turns, which will degrade the performance of the SPD. The weight of the SPD 

should be supported to avoid necessary stress on the wiring connections.   

 
Installing 
 

1.  Measure voltage at installation location between each Line and Neutral.  System voltage must not exceed 

the specified maximum continuous RMS voltage listed on the SPD label.   

2.  TURN OFF POWER at the installation location (usually by removing services to meter or disconnection of 

service supply by utility).   

3.  Switch all distribution panel circuit breakers to OFF position to reduce possibly of accidental voltage on the 

circuit.   

4.  Connect the SPD White (Neutral) wire to the Neutral service conductor, a grounding electrode conductor, 

or the equipment grounding terminal in the service equipment.   

 

For a Split-

Phase system: Connect Line 1 to one of the SPD’s Black wires and Line 2 to the remaining 

Black wire.  

See Figure 1 

 

For a Three-

Phase system: Connect Line 1 to one of the SPD’s Black wires, connect Line 2 to the 

other Black wires, and Line 3 to the remaining Black wire.  

See Figure 2.  

 

 

Keep all hook-up leads as short and straight as possible.   

5.  Restore power to the SPD and switch circuit breakers to 

“ON” position to reconnect load.  Verify that the 

Green LED is illuminated.   

 

If Green LED is not lit, remove power, re-check installation, repeat Step 2, and test again.   

 

If Red LED is lit and the buzzer sounds, contact the manufacturer and replace the unit immediately.     

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

      Figure 1 

– Split-Phase System

                                            

Figure 2 

– Three-Phase System

 

Environment 

 

The unit is designed for indoor or outdoor use in ambient temperature of -40C to +85C with a relative 

humidity of 0% to 95%.  The unit is provided in an industrial enclosure, which should not be installed in areas with 
excessive dust, corrosive vapors, flammable materials or explosive atmospheres.   
 

 

 
Global Power Products will repair or replace any Surge Protective Device that is defective in material or workmanship 

or  is  damaged  by  an  electrical  surge  (including  those  caused  by  lightning)  for  a  period  of  seven  (7)  years  from  the  date  of 
installation or seven (7) years and six (6) months from the date of manufacture, whichever comes first.   

For any further inquiries or question, call Global Power Products at  

1-800-886-3837 

All damaged/returned products returned to the factory for repair/replacement must be accompanied by a Return Authorization 

number to the following address

 

225 Arnold Road 

Lawrenceville, GA  30044 

Phone 1-800-886-3837 

Fax 1-888-886-3837 

www.globalpowerproducts.com

 

 

 
 
 
 
 
 
 
 

 

Copyright © 2012. Global Power Products, Inc.  All rights reserved 
 
This instruction manual is published solely for information purposes and should not be considered all-inclusive. No part of this manual may be 
reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying, recording, or by an information 
storage or retrieval system without the prior written permission of Global Power Products unless such copying is expressly permitted by 
federal copyright law. 
 
Address inquiries to: 
Global Power Products 

 

 

 

                         

225 Arnold Road  

 

 

 

          

Lawrenceville, GA  30044 
Phone 1-800-886-3837 Fax 1-888-886-3837 
www.globalpowerproducts.com

 

WARRANTY 

Reviews: