Global Power Products SURGE SAFE SM Series Installation, Operation And Maintenance Manual Download Page 1

SURGE SAFE

 

SM Series 

Surge Protective Device (SPD) 

    Installation, Operation and Maintenance Manual 

 
 

Introduction

 

 

Surge Safe™ SM Series Surge Protective Device is a high quality, high energy surge current diverting 

system designed to protect sensitive equipment from damaging transient voltage surges resulting from load 
switching, lightning strikes, and other sources.   

 
Installer should perform the following instructions carefully to ensure a quality installation. Please read all 

instructions before starting the installation of this product.  These instructions do not replace national or local 
electrical codes.  Please check applicable electrical codes to ensure compliance.   

             

 

             

 

Part Number 

100-SM3W 

300-SM4W 

310-SM4W 

Applied Voltage 

120/240VAC 

120/208VAC 

277/480VAC 

Phase 

Single Phase 

Three/Wye 

Three/Wye 

Wiring 

2 Wire + Neutral 

3 Wire + Neutral 

3 Wire + Neutral 

Operating Frequency                                                                                                                               47-60Hz 

Nominal Discharge Current (In)                                                                                                                   20kA 

Maximum Surge Current Capacity (8 x 20µs)                                                                                              50kA 

Short Circuit Current Rating (SCCR)

1                                                                                                                                                                

200kA

            

Voltage Protection Rating (VPR)

                                                  

100-SM3W, 300-SM4W @ L-N 700V, L-L 1200V 

                                                                                                                   310-SM4W @ L-N 1200V, L-L 2000V 

Wire type                                                                                                                        

#12 Wire leads, 24” long 

Enclosure Size (in)                                                                                                  3.543 L x 3.543 W x 2.362 H 

Enclosure Rating                                                                                           UL Type IP66, NEMA 4, 4X, 12, 13 

Conduit Hub                                                                                                                                   Weather Tight 

Operation Temperature                                                                                                                -40°C to +85°C 

UL Location Type                                                                                    Type 1 Surge Protective Device (SPD) 

1

 Suitable for Use on a Circuit capable of delivery not more than 200kA rms symmetrical Amperes.   

 

 

 

 
 
WARNING 
 

 

ONLY QUALIFIED PERSONNEL/ELECTRICAN SHOULD INSTALL OR SERVICE SURGE SAFE™ 
DEVICES.  

 

ELECTRICAL SAFETY PRE-CAUTIONS MUST BE FOLLOWED WHEN INSTALLING OR SERVICING 
THIS EQUIPMENT.  

 

TO PREVENT RISK OF FIRE, ELECTRICAL SHOCK, OR DEATH; ALL POWER SOURCES TO THE 
UNIT MUST BE TURN OFF AND LOCK OUT BEFORE MAKING ELECTRICAL CONNECTIONS OR 
SERVICING.  

 

SURGE SAFE™ DEVICES ARE NOT TO BE USED WITH A HI-LEG DELTA VOLTAGE 
CONFIGURATION.   

 

THIS SPD MAY NOT SURVIVE SUSTAINED OVERVOLTAGES.   
 

Caution

 

– Ungrounded power systems are inherently unstable and can produce excessively high line to ground voltages 

during certain fault conditions. During these fault conditions any electrical equipment, including an SPD, may be subjected to 
voltages which exceed their designated ratings. This information is being provided to the user so that an informed decision can 
be made installing any electrical equipment on an ungrounded power system.  

 

Verify the system voltage and wiring configuration is the same as the enclosed 

Surge Safe™ by checking it 

against the product label. 
 

USE SUPPLY WIRE SUITABLE FOR 90°C 

EMPLOYER DES FILS D'ALIMENTATION POUR 90°C 

 
Wiring 

 

#12 AWG wring is provided with the unit.  All wiring must comply with the National Electrical Code (NEC) 

and applicable local codes.   

GENERAL SPECIFICATION 

INSTALLATION 